Advantages of variable driving temperature in solar absorption chiller

Advantages of variable driving temperature in solar absorption chiller

Accepted Manuscript Advantages of variable driving temperature in solar absorption chiller Karolina Petela, Giampaolo Manfrida, Andrzej Szlek PII: S0...

2MB Sizes 0 Downloads 43 Views

Accepted Manuscript Advantages of variable driving temperature in solar absorption chiller Karolina Petela, Giampaolo Manfrida, Andrzej Szlek PII:

S0960-1481(17)30682-1

DOI:

10.1016/j.renene.2017.07.060

Reference:

RENE 9035

To appear in:

Renewable Energy

Received Date: 15 December 2016 Revised Date:

9 July 2017

Accepted Date: 12 July 2017

Please cite this article as: Petela K, Manfrida G, Szlek A, Advantages of variable driving temperature in solar absorption chiller, Renewable Energy (2017), doi: 10.1016/j.renene.2017.07.060. This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please note that during the production process errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.

ACCEPTED MANUSCRIPT

RI PT

Advantages of variable driving temperature in solar absorption chiller Karolina Petelaa,∗, Giampaolo Manfridab , Andrzej Szleka a Silesian

SC

University of Technology, Institute of Thermal Technology, Konarskiego 22, Gliwice 44-100, Poland b University of Florence, Department of Industrial Engineering, Viale G. Morgagni 40, Firenze 50134, Italy

M AN U

Abstract

The study described in this paper results from the observation that, when dealing with solar-driven absorption chillers, a compromise situation very likely exists between the collector efficiency and the coefficient of performance (COP) of the absorption cycle. An idea of a control strategy pursuing this objective, and thereby increasing the solar fraction for a solar absorption cooling cycle is consequently presented. The advantage of operating the solar chiller on a vari-

TE D

able driving temperature is demonstrated. The theoretical analysis considers a solar chiller operated under moderate climate conditions of Poland. The model of the ammonia-water absorption chiller is described in detail, and the main assumptions of the iterative control procedure are explained. The effects of its application are computationally tested for one location and one type of solar

EP

collector, for representative days of three months during the cooling season. The results of the simulation are compared with the reference case of fixed driving

AC C

temperature. According to the simulation results, it is possible to increase the cooling power yield at various levels, up to 34 W per 1 m2 of solar collector, by adjusting the chiller driving temperature throughout the cooling season. The same, it is possible to more than double the cooling effect for some hours, with respect to fixed-temperature control operation. ∗ Corresponding

author Email address: [email protected] (Karolina Petela) URL: www.itc.polsl.pl/kpetela (Karolina Petela)

Preprint submitted to Renewable Energy

July 13, 2017

ACCEPTED MANUSCRIPT

RI PT

Keywords: solar cooling, absorption chiller, solar thermal, COP, control strategy

1. Introduction

In times when the environmental policy is becoming more and more rigorous

SC

about the primary energy consumption, one cannot expect that the population's energy demand will decrease, facilitating the savings. On the contrary, accord5

ing to the prognoses, the energy demand will keep increasing. One of the main

M AN U

reasons for that are higher requirements towards provision of thermal comfort. Having access to central heating and domestic hot water is no longer a sign of full thermal comfort satisfaction - this change of societys attitude is also noticeable in moderate climate locations. More and more energy is being consumed 10

for the purposes of air conditioning systems. Currently 30% of energy demand is assigned to cooling end uses on the European Heat and Cold market. Ac-

TE D

cording to the estimates,the share of energy demand for the cooling purposes on the services market of EU27 countries is constantly increasing and will be equal to the heat demand share by 2030.What is more, the Chiller global market has 15

risen from 7 to 8 billion Euro since 2012. [1] The competitively low investment cost of a vapour compression chiller (up to

EP

5 times smaller than that of an absorption chiller [2]) is constantly driving the consumer market to this choice. However, since thermal driven chillers may be powered by heat deriving from solar energy, constant efforts should be undertaken to make these systems more attractive and more frequently installed.

AC C 20

Their diffusion would contribute to a higher share of renewable energy consumption in national and global balance and, consequently, to important savings of non-renewable energy resources. Solar chillers rely on an energy source with time-dependent availability and therefore are usually considered unreliable.

25

Hence, it is important to elaborate methods for reasonable solar thermal cooling plant management, to prove those systems are effective even in locations of poor

2

ACCEPTED MANUSCRIPT

solar resource. Engineering efforts should be made to obtain high values of solar

to the total energy demand for given conditions [3]. 30

RI PT

fraction, defined as the ratio between energy obtained from the solar collector

Today's literature provides a rich overview of methods investigated for the pur-

pose of solar cooling systems reliability improvement. Shirazi et al. (2016) [4] were evaluating an effect on the solar fraction with various configurations of

SC

components within a solar heating and cooling system. Energetic, economic and environmental analysis considered independent cases: one where the solar 35

absorption chiller is backed up by a gas fired heater, one where it is bypassed

M AN U

by a vapour compression chiller and two where the size of the absorption chiller is reduced but cooperates with an auxiliary compression chiller. The analyses showed that the highest primary energy saving is obtained within a system where absorption chiller cooperates with an auxiliary compression chiller. Nonetheless, 40

none of these systems was proven economically profitable, if there is no financial incentive available. On the other hand, Eicker et al. (2015) [5] found that undersizing of the absorption chiller system with respect to the building cooling

TE D

load may be recommendable to increase the machine operating hours. They also admit that solar thermal cooling systems are more viable in hot than in moder45

ate climates. Eicker et al. (2009)[6] discuss main control strategy ideas applied to solar absorption chillers cycles. In the literature, the consideration of driving

EP

temperature most often appears. The majority of physically installed systems are operated at a fixed value of generator temperature. A complex study has been presented by Eicker et al. (2012) [7]. Authors investigated different control strategies applied for absorption chillers equipped with wet, dry or geothermal

AC C

50

heat rejection system- varying the cooling agent temperature and generator inlet temperature, however with the assumption of On/Off controlled solar collector pumps. The generator inlet temperature was adjusted to the temperature in the hot water storage tank. The highest possible value of electrical COP=13 was

55

achieved for the case with geothermal heat rejection. The analysis presented by Syed et al. (2005) [8] concerns a lithium bromide/water chiller and assumes that the nominal outlet temperature from the flat plate collectors field is 90◦ C, 3

ACCEPTED MANUSCRIPT

leading to 80◦ C temperature level at the top of the storage tank, from which

60

RI PT

the absorption chiller is directly driven. Daily average COP was achieved on the level of 0.42. The authors do see a COP improvement potential by considering a lower temperature driven absorption LiBr-H2 O chiller and undersizing the cooling capacity. Li et al. (2014) [9] were trying to evaluate optimum oper-

ation temperatures that would maximize average monthly system efficiency of

65

SC

a double stage Lithium Bromide chiller in a subtropical city. They found that depending on month and meteorological conditions, a different optimal outlet

temperature from the collector results. Lecuona et al. (2009) [10] created an

M AN U

algorithm whose intention was to find an instantaneous optimum hot water temperature based on the phenomenon of inverse relationship between the COP of a single-effect LiBr-water chiller and collector efficiency increase. The authors 70

evaluated an equation for optimum hot water temperature and concluded that to reach the optimum temperature, mass flow rate control is required. The analysis prepared by Albers (2013) [11] presents a strategy of simultaneous control of hot and cooling water temperature leading to decrease of operation cost.

75

TE D

The researchers state that for the purpose of minimizing the specific costs, the control strategy for thermally driven chillers should be independent of solar or district heating. As a result, a 5% reduction of operating cost can be achieved. However, the authors do notice that the economic optimum temperatures (of

EP

hot water and cooling water) will not be the same as for the maximum primary energy savings. An analysis of a complex combined cooling, heating and power 80

plant is offered by Al-Sulaiman (2012) in [12] where an ORC cycle cooperates

AC C

with solar collector field and an absorption chiller; in the same study, it was observed that controlling the ORC pump inlet temperature could be profitable as well.

Taking current accomplishments on this research field under consideration, the

85

aim of the present work is to indicate the potential that weather-dependent adapting of the driving stream temperature may have on the amount of solar cooling power produced by an absorption chiller under specific climate conditions. The idea described in this research, is to find a generator driving temper4

ACCEPTED MANUSCRIPT

ature in every simulation step that may provide a theoretically lower COP but will produce a higher solar collector output. The study focuses on an evacu-

RI PT

90

ated tube collector driven ammonia-water chiller demanding substantial driving

temperatures. The system operates under relatively difficult meteorological conditions (Polish climate with limited radiation).

95

SC

2. Methodology 2.1. Theoretical chiller model

M AN U

For the purposes of this analysis, a design model of a single stage ammoniawater chiller was prepared. The detailed assumptions for the model are presented in subsection 2.4. Once the size of the heat exchangers is defined, an off-design simulation of the chiller operation under variable external conditions 100

is run. A simplified scheme of the cycle is presented in Fig. 1. Cooling water

19

17

5

Q gen

(1) GENERATOR

18

High pressure flow

14

4

EP

Intermediate pressure flow

6

15

(6) PREABSORBER

2

20 7

(7) PUMP

13

1 8

(4) SUBCOOLER

11

9 10

12

(5) EVAPORATOR

21

Qevap

22

Chilled water

AC C

Low pressure flow

3

Q cw

(3) CONDENSER/ ABSORBER

(2) RECTIFIER

16

TE D

(8) Solar collector

Figure 1: Simplified scheme of the single stage ammonia-water absorption chiller.

The components included in the model are: a heat generator (1) co-working

with a rectifier (2), a preabsorber (6), a common vessel for condenser and absorber (3), a circulation pump (7), a subcooler (4) and an evaporator (5). The system operates at 3 pressure levels therefore 3 throttling valves are considered. 5

ACCEPTED MANUSCRIPT

105

High, intermediate and low pressure flows are marked in the Fig. 1, respectively. Ammonia-water solution is warmed up in the generator (1) by the heat rate (

RI PT

Q˙ gen , kW) coming from the solar collector field (8). Incoming heat produces

ammonia vapour, which is subsequently purified in the rectifier (2). The almostpure ammonia vapour flows to condenser (3) where it is cooled down by external 110

cooling water and by the rich solution coming from the absorber (3), producing

SC

waste heat (Q˙ cw , kW). The rich solution is passing through the condenser, the rectifier and the preabsorber before it finally reaches the generator. The aim of this long path is to gradually increase its temperature, reducing the tempera-

115

M AN U

ture difference in the generator. At the same time, it enhances the condensation process of ammonia vapour. The pressure of the condensed ammonia is reduced by the intermediate throttling valve. The subcooler (4) reduces the temperature of the liquid, which is subsequently throttled to a lower evaporator (5) pressure and then evaporated. Low temperature evaporation process is responsible for providing the cooling power (Q˙ evap , kW). After being warmed in subcooler, the 120

ammonia vapour enters the preabsorber (6) where it is absorbed by the weak

TE D

NH3 -H2 O solution flowing from the generator. Rich solution is warmed to saturation conditions in the common condenser/absorber vessel. The design model of the chiller is based on the application of mass and energy conservation equations in accordance with the 1st law of thermodynamics. It is possible to describe every component by the use of balances 1 and 2

AC C

EP

125

n X

m ˙ iin =

i=1

n X

m ˙ iout

(1)

i=1

n n X X (m ˙ i hi )in + Q˙ i = (m ˙ i hi )out i=1

(2)

i=1

Where subscripts in and out denote the inlet or outlet of a stream from the

component, while m ˙ i , kg/s and hi , kJ/kg, are the mass flow rate and the specific 130

enthalpy of given stream, respectively. Q˙ i , kW is the heat transfer rate within

6

ACCEPTED MANUSCRIPT

every system component. Its negative value means a heat loss, while a positive

RI PT

appears as a heat gain from an external source (in case of generator: from warm heat transfer fluid from the collector, evaporator: from chilled water). For the

135

pump, the energy balance also covers mechanical power utilization, namely: Pn Pn ˙ i hi )in + Npump = i=1 (m ˙ i hi )out i=1 (m

Primary sizing of the components is done on the base of the Peclet equation

SC

(3). Knowing the heat exchanger logarithmic temperature difference ∆Tlg , the

value of overall heat loss coefficient multiplied by the heat exchanger size may

M AN U

be defined (U A, W/K). Q˙ i = (U A)∆Tlg

140

(3)

The final sizing depends on assumptions about the type of the heat exchanger. All devices: evaporator, subcooler and condenser/absorber were assumed to be shell and tube heat exchangers. Detailed heat transfer models accounting for conduction and convection effects between external and internal

145

TE D

streams were applied. 2.2. Solar collector model

(4) [3]:

EP

The solar collector model follows the 2nd order Bliss Equation given in Eq.

ηsc = η0 − a1

AC C

where

∆Tm ∆Tm 2 − a2 G G

∆Tm = THTF − Tamb

(4)

(5)

∆Tm is defined as a difference between the average heat transfer fluid (HTF)

temperature and the ambient temperature. G, W/m2 stays for total solar radia-

150

tion on a tilted surface, which is a sum of the beam and scattered radiation. The equation includes performance constants: optical efficiency (η0 ), linear heat loss

coefficient (a1 , W/(m2 K)) and quadratic heat loss coefficient (a2 , W/(m2 K 2 )).

7

ACCEPTED MANUSCRIPT

The value of the heat rate produced by a solar collector is defined by equations

RI PT

(6) and (7). Q˙ u = ηsc · A · G

(6)

Q˙ u = m ˙ HTF (h17 − h18 )

SC

155

(7)

2.3. Modelling tools

The design and off-design models of the solar cooling cycle were prepared

solution of equations [13].

M AN U

within Engineering Equation Solver (EES)– a software enabling the numerical

Thermodynamic properties of ammonia-water solution were provided by an ex160

ternal routine available in EES. The thermodynamic data are based on the mixture equation of state described by Ibrahim O.M and Klein S.A. in [14]. Additionally, the properties of assumed heat transfer fluid for given temperature are recovered from the EES properties library as well.

165

TE D

The varying values of the incoming solar radiation and ambient temperature, needed for the evaluation of the solar collector performance, are obtained with the help of TRNSYS software and its Meteonorm libraries [15]. 2.4. Modelling assumptions

EP

• Chiller type and its design point parameters Since an ammonia-water chiller is characterized by an average 10-15% lower solar fraction than H2 O-LiBr chiller [16] and it requires higher driving temper-

AC C

170

ature to generate the ammonia vapours, it can be treated as a more demanding solar cooling system and as such less attractive to potential installers. In order to prove ammonia-water solar chillers competitive, some efforts should be made enabling the increase of solar fraction - which is the motivation behind

175

the present study. The only electric energy consumption in solar absorption chillers is due to operation of the solution pump. The cooling effect results from evaporation of 8

ACCEPTED MANUSCRIPT

pressurized ammonia under low temperature (around 0◦ C, 4 bar). The elec-

180

RI PT

trically driven compressor in vapour compression chillers is replaced by a heat driven absorption compressor set including a thermally driven desorber (generator) and a water-cooled absorber. The analysed system is assumed to be operating under moderate climate conditions with meteorological source data obtained from the weather station in Cracow, Poland.

185

SC

Several assumptions had to be made to enable the design analysis. They are listed in Table 1 and include: assumption of nominal driving heat rate Q˙ gen , temperature of desorbed ammonia coming out from generator Tgen , the

M AN U

temperature difference with respect to isothermal evaporation ∆Tglide , minimal temperature difference in the Condenser/Absorber heat exchanger ∆T13-6 , subcooling level in the regenerative heat exchanger ∆Tsub , concentration of rectified 190

ammonia xrect , difference of concentrations between rich and poor solutions ∆x and pressure levels (pcond , pint , pevap ).

Table 1: Design point assumptions.

Value

Q˙ gen

25.5 kW

Tgen = T5

120◦ C

∆Tglide = T11 − T10

3K

∆T13−6 = T13 − T6

0.2 K

AC C

EP

TE D

System parameter

∆Tsub = T8 − T9

10 K

xrect = x6

0.995

∆x = x1 − x14

0.15

pcond

15.5 bar

pint

11.5 bar

pevap

4 bar

The absorption cycle interaction with external flows must also be considered. Table 2 summarizes the design assumptions connected with these flows. Chosen

9

ACCEPTED MANUSCRIPT

Table 2: External flows design assumptions.

Component

External flow parameter

Evaporator

T21

7◦ C

• Solar collector type

∆THTF = T17 − T18

10 K

∆Tpp cw = T7 − T19

5K

∆Tcw = T20 − T19

10 K

M AN U

195

10 K

SC

∆Tapp = T18 − Tgen

Absorber-Condenser

Value

12◦ C

T22 Generator

RI PT

temperature limitations correspond to those present in the literature [17].

As presented in Table 1, the design generator temperature equals 120◦ C. Hence, a solar collector with stagnation temperature much higher than 140◦ C had to be chosen. The collector should ensure positive values of thermal ef-

200

TE D

ficiency even while pursuing higher outlet temperatures. For the purpose of the analysis, it was decided to consider an enhanced vacuum tube solar collector. The constants: optical efficiency (η0 ), linear heat loss coefficient (a1 , W/(m2 K)) and quadratic heat loss coefficient (a2 , W/(m2 K 2 )) were adapted

EP

from the manufacturer performance data and are collected in Table 3. Table 3: Solar collectors efficiency parameters [18]

Value

AC C

Parameter

Optical efficiency

η0 ,-

0.82 2

Linear heat loss coefficient

a1 , W/(m K)

1.62

Quadratic heat loss coefficient

a2 , W/(m2 K 2 )

0.0068

It was assumed that the collector would be a non-tracking surface with 205

a slope equal to location latitude (51◦ for Cracow). The collector is South 10

ACCEPTED MANUSCRIPT

oriented, consequently, the surface azimuth angle equals 0◦ . Since the analysis

RI PT

covers a geographical location of inferior radiation conditions and the possibility of morning frost even during the cooling season, it has been decided that a

thermal oil will work as a heat transfer fluid in order to exclude the danger of 210

working fluid freezing. Thermal Syltherm800 was chosen.

SC

3. Absorption chiller base model results - design and off-design

Under design operating conditions described in Table 2, the chiller reaches a COP of 0.488 which means that it may produce almost 12.5 kW of cooling

215

M AN U

power. At the same time, the pump consumes 99 W of electric energy (0.4% of the heat input) and 38 kW of low-temperature waste heat is generated. For systems integrated with energy sources of variable and intermittent nature, like solar, it is of high importance to perform an off-design simulation, since they usually operate in part-load conditions. The off-design simulation assumes that some relevant operating parameters are time- and weather-dependent: the 220

driving heat rate, the mass flow rate and the temperatures of the cooling water

TE D

and of the chilled water. It is expected that together with the change of external flow parameters, the performance of the solar chiller will be a matter of change. The chart in Fig. 2 shows the change of COP in the function of generator driving temperature. Generator temperature was the only variable. Temperatures of the cooling water and chilled water for this case were maintained at the nominal

EP

225

state conditions, T19 =35◦ C and T21 /T22 =12/7◦ C. It is evident that the COP of the absorption chiller becomes higher if the gener-

AC C

ator temperature is increased. However, if a cooling system is driven by the heat source strictly dependent on the ambient conditions and the surface of the solar

230

thermal collectors is fixed, it becomes relevant to consider a control strategy enabling efficient operation at lower temperature level. 3.1. Interdependence of collector efficiency and COP Solar absorption chillers are usually driven at a fixed temperature level in order to achieve a high COP. One should, however, take into consideration, 11

ACCEPTED MANUSCRIPT

235

that together with the change of external meteorological conditions (ambient

RI PT

temperature and incoming solar radiation), the efficiency of solar collector may suffer from trying to obtain the highest temperature possible. It is evident while looking again at the chart presented in Fig.2. The collector efficiency curve has

240

20◦ C and incoming solar radiation of 1000 W/m2 .

1

SC

1

0.8

0.6

M AN U

COP

0.8

0.4

0.2 0

145 150 155 generator driving temperature T17; °C

0.4

0.2 0

160

TE D

140

0.6

solar collector efficiency 𝜂sc

been prepared using equation (4) with the assumption of ambient temperature

COP

solar collector efficiency 𝜂sc

Figure 2: COP curve of analysed chiller and solar collector efficiency curve.

EP

It is shown that, although the COP of the chiller increases with the growth of driving temperature, if the temperature difference between the outlet stream from the solar collector and the ambient is higher, the efficiency of the collector

AC C

will be falling down. This phenomenon of inverse dependence between those two

245

performance coefficients speaks for operating the chiller at a variable driving temperature, adapting to outer conditions.

4. Idea of control procedure To investigate the phenomenon presented in subsection 3.1., a control strategy procedure is proposed. Authors state that it is not always a priority to 12

ACCEPTED MANUSCRIPT

250

maintain the generator temperature achieving the highest coefficient of perfor-

RI PT

mance (COP) under given conditions. If the solar radiation conditions are poor, it may occur that it is difficult to produce enough heat at the desired higher

temperature level. Under these conditions, it may be profitable to produce more

low-temperature heat, and accept a lower COP estimated from the curve, lead255

ing on the whole to a higher cooling power production from the solar collector.

SC

Some simplifications were introduced to manage the control routine. The chiller

is cooled down constantly by the inflowing cooling water temperature of 35◦ C, and the evaporator delivers chilled water at the level of 12/7◦ C, to maintain

260

M AN U

consistency with the exemplary COP recovered from off-design simulation. Following Fig. 2, COP depends mainly on the generator temperature. Since the pump mechanical energy consumption constitutes only 0.4% of the heat input, its contribution is not taken under consideration.

The heat transfer temperature differences are kept constant according to relations presented in (8) and (9). Lecuona et al. (2009) [10] mention that those ∆T usually ranges from 5 to 15◦ C.

TE D

265

∆THTF = T17 − T18 = 10K

(8)

∆Tgen = T18 − Tgen = 10K

(9)

EP

∆THTF , K is the temperature increase of the heat transfer fluid inside the solar collector, while the ∆Tgen , K is the temperature difference between the fluid stream coming back to the collector (T18 , ◦ C) and the generator temper-

AC C

ature (Tgen = T5 , ◦ C). An example control routine for finding optimal working

270

parameters of solar collector has also been described in [19], where the solar collector outlet temperature has been adapted to ensure maximum exergy efficiency of collector. It is ideally assumed that the useful heat gain from the collector equals the heat rate to generator assigned to solar contribution Q˙ u =Q˙ gen . In an iterative

275

way, the procedure searches for the generation temperature at which the cooling

13

ACCEPTED MANUSCRIPT

power (Q˙ evap ) produced by the solar chiller is the highest, which at the same

is presented in Eq. (10). Tgen = f (max : Q˙ evap = COP · Q˙ u )

RI PT

means the highest possible solar fraction. The objective function of this routine

(10)

To maintain consistency with the before-mentioned considerations, the rou-

tine looks for the desired temperature in the range between 140◦ C (the lowest

SC

280

temperature for which off-design simulation has been done) and 161◦ C. The value of driving temperature is searched for raising values of the cooling power

M AN U

output; once the cooling power output begins to decrease, the optimal solution is refined by chord interpolation. The collector mass flow rate enabling heating 285

the heat transfer fluid to the desired temperature is defined on the base of equation (7) and, consequently, it should be processed and transferred as a setup control signal to remote-controlled variable speed pump.

TE D

5. Example application of the model - the study case The effect of the routine was tested in simulations performed with a 5290

minutes time step for 3 representative days of the cooling season. The overall solar radiation and ambient temperature data were processed to generate 3 average days statistically representative of specific months of the year. The analysis

EP

covers May, June and July, as months belonging to cooling season. Meteorological data for Cracow were used. Since the data recovered from Meteonorm library are hourly, a cubic interpolation was applied to simulate the operation

AC C

295

according to the smaller time step. The variable driving temperature study case is compared with the reference case operation.

The reference case follows an assumed standard operation routine. In this rou-

300

tine, the solar chiller is driven by the heat output of the solar collector at constant temperature level. During every time step of operation, a constant value of the solar collector outlet temperature is maintained (161◦ C). This value was 14

ACCEPTED MANUSCRIPT

chosen for the simulation purpose, as the driving temperature assuring high

305

RI PT

COP value (up to 0.9 according to Fig. 2). The analysed study case, on the other hand, assumes that the solar collector outlet temperature is optimized during every time step, according to the dis-

cussed objective function in Eq. (10). The chilled water and cooling water temperature remain the same for the reference and study case, so that the re-

310

the unit surface area of the solar collector.

SC

sults are comparable. The cooling power produced in both cases is referred to

The results are presented in graphical form in Figs. 3, 4 and 5 (May, June,

M AN U

and July). The upper charts show the amount of cooling power that could be produced from 1 m2 of solar collector at a fixed driving temperature and the increment of cooling power production that constant adjusting of collector 315

outlet temperature may bring. The bottom charts present the daily profiles of the outlet temperature and collector energy efficiency for both cases: with optimal adjustment of the outlet temperature (temp.var.) and for fixed value of

AC C

EP

TE D

it (temp.f ixed).

15

ACCEPTED MANUSCRIPT

140 600 500

100

400 300

60

200

40

100

20 0

0

10

11

variable ∆ 𝑄evap/mtemperature 2 (𝑡𝑒𝑚𝑝. 𝑣𝑎𝑟. )

160 150 140

13

14

15

hour fixed temperature 𝑄evap/m 2 (𝑡𝑒𝑚𝑝. 𝑓𝑖𝑥𝑒𝑑)

16

solar radiation G 0.6 0.5 0.4 0.3

130 120 110 100

9

TE D

driving temperature T17, °C

170

12

M AN U

9

B

SC

unit cooling power

80

10

11

12

AC C

EP

hour fixed temperature T17 coll. efficiency (temp. fixed) 𝜂sc

Figure 3:

solar radiation G, W/m2

RI PT

120

0.2 0.1

solar collector efficiency 𝜂sc

, W/m 2

A

0

13

14

15

16

variable temperature T17 coll. efficiency (temp. var.) 𝜂sc

Results of the simulation for a representative day of May; A: distribution of unit

cooling power production and its increase at variable driving temperature, solar radiation distribution; B: distribution of driving temperature and collector efficiency for both study cases.

16

ACCEPTED MANUSCRIPT

140 600 500

100

400 300

60

200

40

100

20 0

0

10

11

variable ∆ 𝑄evap/mtemperature 2 (𝑡𝑒𝑚𝑝. 𝑣𝑎𝑟. )

160 150 140

13

14

15

hour fixed temperature 𝑄evap/m 2 (𝑡𝑒𝑚𝑝. 𝑓𝑖𝑥𝑒𝑑)

16

solar radiation G 0.6 0.5 0.4 0.3

130 120 110 100

9

TE D

driving temperature T17, °C

170

12

M AN U

9

B

SC

unit cooling power

80

10

11

12 hour

AC C

EP

fixed temperature T17 coll. efficiency (temp. fixed) 𝜂sc

Figure 4:

solar radiation G, W/m2

RI PT

120

0.2 0.1

solar collector efficiency 𝜂sc

, W/m 2

A

0

13

14

15

16

variable temperature T17 coll. efficiency (temp. var.) 𝜂sc

Results of the simulation for a representative day of June; A: distribution of unit

cooling power production and its increase at variable driving temperature, solar radiation distribution; B: distribution of driving temperature and collector efficiency for both study cases.

17

ACCEPTED MANUSCRIPT

140 600 120 500

100

400 300

60

200

100

20

0

10

11

variable ∆ 𝑄evap/mtemperature 2 (𝑡𝑒𝑚𝑝. 𝑣𝑎𝑟. )

160 150 140

13

14

15

hour fixed temperature 𝑄evap/m 2 (𝑡𝑒𝑚𝑝. 𝑓𝑖𝑥𝑒𝑑)

16

solar radiation G 0.6 0.5 0.4 0.3

130 120 110 100

9

TE D

driving temperature T17, °C

170

12

10

11

12

0.1 0

13

14

15

16

variable temperature T17 coll. efficiency (temp. var.) 𝜂sc

AC C

EP

hour fixed temperature T17 coll. efficiency (temp. fixed) 𝜂sc

0.2

solar collector efficiency 𝜂sc

0 9

B

SC

40

M AN U

unit cooling power

80

solar radiation G, W/m2

RI PT

, W/m 2

A

Figure 5:

Results of the simulation for a representative day of July; A: distribution of unit

cooling power production and its increase at variable driving temperature, solar radiation distribution; B: distribution of driving temperature and collector efficiency for both study cases.

Incorporating the given control strategy may result in an increase of the 320

cooling power production related to solar collector utilization by up to 34 W 18

ACCEPTED MANUSCRIPT

per 1 m2 of collector. For specific conditions, it is possible to more than double

RI PT

the cooling power yield, which is happening around 10 a.m. and 3 p.m. for every of the representative days. The simulations show that under poor radiation

conditions it is profitable to operate close to the minimal driving temperature 325

allowing for ammonia vapour generation (here: 140◦ C). Optimal adaptation of driving temperature enables to obtain a positive value of cooling power around

SC

9 a.m. and 4 p.m. in May, June and July. According to the charts, it is

convenient to operate solar collectors at the highest outlet temperature level only when high radiation conditions are possible (during noon hours). During this time, the chosen temperature is close to the reference fixed of 161◦ C. As

M AN U

330

expected, a lower collector outlet temperature always leads to higher solar collector efficiency, as is visible in the bottom charts of Fig. 3, 4 and 5. In order to broaden the comparative analysis, a similar simulation study was performed for the case of parabolic trough concentrating collectors. The effi335

ciency parameters were: optical efficiency η0 =0.68, linear heat loss coefficient a1 =0.04 W/(m2 K) and quadratic heat loss coefficient a2 =0.0015 W/(m2 K2 )

TE D

[18]. It occurs that, although this type of collector is only able to utilize beam solar radiation, its efficiency is much less dependent on the change of outlet temperature in the range between 140-161◦ C. Thereby, the iterative procedure 340

produces an outlet temperature close to the fixed one (161◦ C) during the ma-

EP

jority of simulation hours of analogic representative days. According to the summary of results: it occurs that it is more profitable to operate the parabolic trough collectors on a reduced collector temperature (140◦ C) only in the late

AC C

afternoon hours (5 p.m.) in May, June or July. During the rest of the days 345

(8 a.m.-4 p.m.) the procedure chooses outlet temperatures within the narrow range between 160 and 161◦ C. In order to discuss the effect of applying the control strategy, an additional

indicator was considered, that is, the collector exergy efficiency indicator: coefficient of quality (COQ). The exergy of thermal radiation (or actually the change of exergy occurring with thermal radiation transfer) has been investigated in terms of fundamental research by several Authors. The sun emits its 19

ACCEPTED MANUSCRIPT

radiation at an equivalent very high temperature of nearly 6000 K. The exergy

RI PT

of solar radiation is lost due to transmission through space, and scattering by the atmosphere, to be finally utilized at respectively low temperatures. Petela

(2003) [20] stated that in order to derive a correct exergy formula it is wise to

interpret the characteristic exergy equation h − hamb − Tamb · (s − samb ). For solar thermal radiation the enthalpies would be substituted by the brightness

SC

values of radiation propagating within the given solid angle and the entropy of the radiation brightness would be considered. The same, the entropy should not be calculated as for the heat, but in accordance with Planck's formulae. The

M AN U

author managed to obtain a formula of maximum conversion efficiency of direct 1 Tamb 4 solar radiation (1 − 34 Tamb Ts + 3 ( Ts ) ). These considerations have been further

developed by Chu et al. (2009) [21], who provided formulas for the exergy of solar radiation covering the beam and diffuse components. The authors used spectral analysis for the wavelength range from 0.28 to 4 µm. According to their findings, the maximum conversion efficiency (exergy-to-energy ratio) for total solar radiation is about 0.92. All this considered, for the only purpose of the

TE D

qualitative evaluation of a collector flow rate control strategy, it is possible to apply a simplified approach. The input exergy rate is thus taken as the overall incoming solar radiation over the gross solar collector aperture area. Hence, the exergy efficiency of a solar collector is calculated only indicatively with the help

EP

of coefficient of quality presented in equation (11) [22]: COQ =

E˙ sc G·A

(11)

AC C

The rate of physical exergy (E˙ sc ) gained by the material stream of the heat

transfer fluid is given by equation (12): E˙ sc = m(h ˙ 17 − h18 − Tamb · (s17 − s18 ))

(12)

Values of specific enthalpy and entropy of the Syltherm heat transfer fluid were obtained using the EES software built-in libraries discussed in the Modelling Tools section.

350

Taking into consideration the radiation transmission exergy loss, the denomina20

ACCEPTED MANUSCRIPT

tor in Equation (11) would be lower; the attenuation factor would be variable

RI PT

with time, depending on the solar declination and on the length of the transmission path across the atmosphere; it would also be affected by meteorological conditions across the transmission path (mainly, by the presence of water 355

vapour); however, the qualitative daily trend of the collector exergy efficiency indicator should be marginally affected. The data presented in Fig. 6 provide

SC

the comparison of the collector COQ for the case of fixed and variable outlet

temperature (in this last case, temperature is adjusted to the environmental conditions searching numerically for the maximum COP conditions); the COP profiles are also shown for both study cases.

AC C

EP

TE D

M AN U

360

21

ACCEPTED MANUSCRIPT

1

0.25

0.9

0.2

RI PT

0.8 0.7

0.15

COQ

COP

0.6 0.5 0.4

0.1

0.3 0.2

0.05

SC

0.1 0

0

9

10

11

12

13

14

15

hour 1

0.25

0.9 0.8 0.7

COP

0.6 0.5 0.4 0.3 0.2

0.1 0

9

10

11

M AN U

b

16

12

13

14

15

0.2

0.15

0.1

COQ

a

0.05

0

16

1 0.9 0.8 0.7

0.2

0.15

0.5

EP

COP

0.6

0.25

COQ

c

TE D

hour

0.4

0.1

0.3 0.2

0.05

AC C

0.1 0

9

Figure 6:

0

10

11

COP (temp. fixed) COQ (temp. fixed)

12

13

14

hour

15

16

COP (temp. var.) COQ (temp. var.)

Solar collector COQ and COP value distribution for fixed and variable outlet

temperature on representative day of May, June, and July

22

ACCEPTED MANUSCRIPT

It is visible that, although the heat from a collector with constantly adjusted

RI PT

outlet temperature is produced at lower temperature level, the COQ is always higher than that for the reference case. It is shown that, as the input exergy rate A · G is equal for both cases, the increase of COQ derives from the higher value 365

of the collector output exergy rate. It results from the method of controlling the outlet temperature, which is done by a dynamic change of mass flow rate.

SC

Lower outlet collector temperatures are obtained at higher mass flow rate of heat transfer fluid (e.g. 0.0087 kg/sm2 at 11 a.m. in June). The reference case produces high outlet temperatures, for which lower mass flow rate are calculated, respectively (e.g. 0.0048 kg/sm2 at 11 a.m. in June).

M AN U

370

As discussed in section 5 and is shown in the Fig. 6, the COP value suffers from a lower temperature level heat driving stream. However, considering solar thermal energy as a free input, it is profitable to consume more of it and, consequently, to achieve higher solar fraction. 375

For the purpose of results generalization, a sensitivity analysis was performed. While considering the solar collector efficiency and COP value sep-

TE D

arately, relative increments with respect to the design point were obtained. Namely: if the values of solar radiation, ambient temperature or outlet solar collector temperature were increased by 1%, the solar collector efficiency value 380

would be changed by 0.5% or 0.1% or -0.8% of the original value, respectively.

EP

On the other hand, if the outlet solar collector temperature is increased by 1%, the COP would rise about 2.5% of the original value. This preliminary evaluation was followed by the sensitivity analysis on the re-

AC C

sults of the control procedure. The analysis indicates how the changing weather 385

conditions affect the decision on the optimal solar collector outlet temperature resulting from application of the proposed procedure. The results of the sensitivity analysis are presented in Fig. 7. Chart a on the left hand side reveals the breakthrough value of solar radiation valid for given ambient temperature (on x-axis) when the procedure no longer chooses the lowest driving temperature

390

(140◦ C) as optimal. Increasing the solar radiation beyond this value, the optimal temperatures get close to the reference 161◦ C. This phenomenon is visible 23

ACCEPTED MANUSCRIPT

in the plot on the right hand side. Plot b treats separately 5 cases for 5 different

RI PT

ambient temperatures. It shows the dynamics of optimal temperature choice in the function of increasing solar radiation. It covers the events when it is no 395

longer profitable to operate on the lowest driving temperature (140◦ C) and the chosen temperature is reaching 161◦ C. 162

161

600

580

160

560

159

540 520

M AN U

solar radiation G, W/m2

620

SC

b

640

collector outlet temperature T17, °C

a

158

0

5

10

15

20

25

30

ambient temperature Tamb , °C

500

Tamb:

550

5°C

600

650

700

solar radiation G, W/m2 10°C

15°C

20°C

750

800

25°C

Figure 7: Sensitivity analysis results: chart a solar radiation values at given ambient temperatures when optimal solar collector outlet temperature is close to 161◦ C; chart b distribution

TE D

of optimal solar collector outlet temperature close to 161◦ C in the function of changing radiation conditions for given ambient temperature.

The sensitivity analysis confirms that both ambient temperature and solar

EP

radiation values have an impact on the choice of the optimal temperature at the outlet from the solar collector.

6. Conclusions

AC C 400

A simplified theoretical method of controlling the solar collector outlet tem-

perature (which represents the chillers driving temperature) was proposed for a solar absorption chiller. Its purpose is to increase the cooling power production and thereby to increase the solar fraction of the cycle. The idea relies on the

405

physical phenomenon of the inverse trend referring to the solar collector outlet temperature - between the collector efficiency and the COP of the absorption 24

ACCEPTED MANUSCRIPT

cycle. An iterative procedure was set in an EES simulation software environ-

RI PT

ment, with the purpose of finding an optimal collector outlet temperature that is, a value maximizing the cooling effect - at every hour of average days of May, 410

June, and July in Cracow, Poland.

The results presented in current study show that incorporating a control strat-

egy adapting solar collector outlet temperature could bring a high profit to a

SC

system operating under moderate climate conditions. The highest increase in

cooling power production takes place during morning and late afternoon hours 415

when the solar radiation is low. During these times of the day, the cooling effect

M AN U

can be more than doubled.

Since none of the previous studies considered controlling a solar ammonia-water chiller (additionally: working under moderate climate conditions), it is not possible to compare the results directly. However, the main conclusions of the 420

analysis presented by Lecuona et al. (2009) [10] are consistent with the findings presented here: a lower generator operating temperature increases the maximum value of solar-induced COP; additionally, the system is more sensitive to

power is low. 425

TE D

temperature change at sunrise and sunset hours when the radiation and cooling

A future advanced analysis should include a transient effect of the system warming up in the morning hours. Moreover, transient effects were neglected when

EP

assuming that changing the mass flow rate of the heat transfer fluid results in an immediate change to the desired temperature. Further enhancements of the method should include: a routine application of maximum system exergy efficiency, transient modelling of heat transfer and the investigation of the dynamic

AC C

430

response to a change of mass flow rate.

Acknowledgements The present work is part of a Joint Ph.D. project, resulting from a long-

standing cooperation between Silesian University of Technology and the Uni435

versity of Florence.

25

ACCEPTED MANUSCRIPT

This research was supported by the statutory research funds of the Faculty

RI PT

of Power and Environmental Engineering of the Silesian University of Technology and by the Internationalization Plan funds of Department of Industrial Engineering (DIEF) of the University of Florence.

Exergy rate, W

m ˙

Mass flow rate, kg/s



Heat rate, W

A

Solar collector aperture area, m2

a1

Linear collector constant, W/(m2 K)

a2

Quadratic collector constant, W/(m2 K 2 )

COP

Coefficient of performance, -

SC



M AN U

445

Nomenclature

TE D

440

450

G

Total solar radiation, W/m2

h

Enthalpy, kJ/kg

p

EP

COQ Coefficient of quality, -

Entropy, J/(kgK)

AC C

s

Pressure, Pa

455

T

Temperature, ◦ C

UA

Overall heat loss coefficient multiplied by heat exchanger area, W/K

Greek Symbols ∆

Variation

η

Efficiency

26

ACCEPTED MANUSCRIPT

Subscripts

470

Optical

amb

Ambient

app

Approach

av

Average

cond

Condenser

cw

Cooling water

evap

Evaporator

ex

Exergy

gen

Generator/desorber

glide

Isothermal slip

HTF

Heat transfer fluid

in

Input to the system/component

int

Intermediate

lg

SC M AN U

Logarithmic

Medium

AC C

m

RI PT

0

TE D

465

Variable

EP

460

i

475

out

Output from the system/component

pp

Pinch point

rect

Rectifier

s

Sun

SC

Solar Collector 27

ACCEPTED MANUSCRIPT

sub

Subcooler

u

Useful gain

RI PT

480

References

[1] N. Pardo, K. Vatopoulos, A. Krook-Riekkola, J. Moya, A. Perez,

485

SC

Heat and cooling demand and market perspective, Tech. rep. (2012). doi:10.2790/56532. URL

https://pure.ltu.se/portal/files/42577403/ldna25381enn.

M AN U

pdf

[2] T. Otanicar, R. a. Taylor, P. E. Phelan, Prospects for solar cooling - An economic and environmental assessment, Solar Energy 86 (5) (2012) 1287– 490

1299. doi:10.1016/j.solener.2012.01.020.

URL http://dx.doi.org/10.1016/j.solener.2012.01.020 [3] W. Beckman, J. Duffie, Solar Engineering of Thermal Processes, John Wi-

TE D

ley and Sons, 1980.

[4] A. Shirazi, R. A. Taylor, S. D. White, G. L. Morrison, Transient simula495

tion and parametric study of solar-assisted heating and cooling absorption systems: An energetic, economic and environmental (3E) assessment, Re-

EP

newable Energy 86 (2016) 955–971. doi:10.1016/j.renene.2015.09.014. URL http://dx.doi.org/10.1016/j.renene.2015.09.014

AC C

[5] U. Eicker, D. Pietruschka, M. Haag, A. Schmitt, Systematic design and 500

analysis of solar thermal cooling systems in different climates, Renewable Energy 80 (2015) 827–836. doi:10.1016/j.renene.2015.02.019. URL

http://linkinghub.elsevier.com/retrieve/pii/

S0960148115001093

[6] U. Eicker, D. Pietruschka, Design and performance of solar powered ab505

sorption cooling systems in office buildings, Energy and Buildings 41 (1) (2009) 81–91. doi:10.1016/j.enbuild.2008.07.015. 28

ACCEPTED MANUSCRIPT

[7] U. Eicker, D. Pietruschka, R. Pesch, Heat rejection and primary energy

RI PT

efficiency of solar driven absorption cooling systems, International Journal of Refrigeration 35 (3) (2012) 729–738. doi:10.1016/j.ijrefrig.2012. 510

01.012.

URL http://dx.doi.org/10.1016/j.ijrefrig.2012.01.012

[8] A. Syed, M. Izquierdo, P. Rodr´ıguez, G. Maidment, J. Missenden,

SC

A. Lecuona, R. Tozer, A novel experimental investigation of a solar cooling

system in Madrid, International Journal of Refrigeration 28 (6) (2005) 859–871. doi:10.1016/j.ijrefrig.2005.01.007. URL

http://linkinghub.elsevier.com/retrieve/pii/

S0140700705000277

M AN U

515

[9] Z. Li, X. Ye, J. Liu, Optimal temperature of collector for solar double effect LiBr/H2O absorption cooling system in subtropical city based on 520

a year round meteorological data, Applied Thermal Engineering 69 (1-2) (2014) 19–28. doi:10.1016/j.applthermaleng.2014.04.039. URL

TE D

http://www.sciencedirect.com/science/article/pii/

S1359431114003032

[10] A. Lecuona, R. Ventas, M. Venegas, A. Zacar´ıas, R. Salgado, Optimum 525

hot water temperature for absorption solar cooling, Solar Energy 83 (2009)

EP

1806–1814. doi:10.1016/j.solener.2009.06.016. [11] J. Albers, A. Kuhn, S. Petersen, F. Ziegler, Control of absorption chillers

AC C

by insight: the characteristic equation, Test. [12] F. A. Al-Sulaiman, F. Hamdullahpur, I. Dincer, Performance assessment of

530

a novel system using parabolic trough solar collectors for combined cooling, heating, and power production, Renewable Energy 48 (2012) 161–172. doi: 10.1016/j.renene.2012.04.034.

URL http://dx.doi.org/10.1016/j.renene.2012.04.034

[13] EES-software, Product information (May 2016). 535

URL http://www.f-chart.com 29

ACCEPTED MANUSCRIPT

[14] O. Ibrahim, S. A. Klein, Thermodynamic properties of ammonia-water

RI PT

mixtures., ASHRAE Transactions 99 (0) (1993) 1495–1502. [15] TRNSYS-software, Meteonorm library available within the software package (May 2016). 540

URL http://www.trnsys.com

SC

[16] Z. F. Li, K. Sumathy, Technology development in the solar absorption air-

conditioning systems, Renewable and Sustainable Energy Reviews 4 (2000) 267–293. doi:10.1016/S1364-0321(99)00016-7.

545

M AN U

[17] D. Kong, J. Liu, L. Zhang, Z. Fang, G. Zheng, Theoretical and experimental analysis of a single stage ammonia-water absorption chiller performance, in: 2009 International Conference on Energy and Environment Technology, ICEET 2009, Vol. 1, 2009. doi:10.1109/ICEET.2009.121. [18] IEA, Solar collector data base available at (September 2016). URL http://www.iea-shc.org

[19] G. Manfrida, V. Gerard, Maximum Exergy Control of a Solar Thermal

TE D

550

Plant Equipped with Direct Steam Collectors, International Journal of Thermodynamics 11 (3) (2008) 143–149. [20] R. Petela, Exergy of undiluted thermal radiation, Solar Energy 74 (6)

555

EP

(2003) 469–488. doi:10.1016/S0038-092X(03)00226-3. [21] S. X. Chu, L. H. Liu, Analysis of terrestrial solar radiation exergy, Solar

AC C

Energy 83 (8) (2009) 1390–1404. doi:10.1016/j.solener.2009.03.011.

URL http://dx.doi.org/10.1016/j.solener.2009.03.011

[22] G. Manfrida, S. Kawambwa, Exergy control for a flat-plate Collector/Rankine Cycle Solar Power System, ASME Journal of Solar Energy

560

Engineering 113 (1991) 89–93. doi:10.1115/1.2929963.

30