Solar Energy, Vol. 26, pp. 461--463. 1981 Printed in Great Britain.
0038-092X/81/050461--03502.0010 Pergamon Press Ltd.
TECHNICAL NOTE Steady-state analysis of the convective loop ALVIN O. CONVERSE Thayer School of Engineering, Dartmouth College, Hanover, NH 03755, U.S.A.
(Received 27 May 1980; revison accepted 8 December 1980) I. INTRODUCTION Although restricted by the steady-state assumption, this analysis demonstrates the short-run importance of ground coupling in the performance of a convective loop building. The purpose of the analysis is to evaluate the ratio of the heat loss from the living space to the loss that would occur if the loop were omitted and the same amount of insulation were used in the shell of the building. It provides a partial answer to Shurcliff's question, "Why bother with the loop?"[1]. A fuller answer would obviously have to consider the loop's ability to accept insolation and store energy in the structure and ground; it would involve a transient analysis. The analysis presented here does, however, point out the importance of partial loop flows, such as between the sunspace and basement, and exposes a mechanism whereby the cool ground can assist in reducing losses from a warm house. 2. ANALYSIS Consider the schematic diagram presented in Fig. 1. The loop temperature, T4, is assumed to be constant through the loop whenever the loop is colder than the ground, thus neglectin;~ resistance to heat transfer within the loop itself when there is natural convection between the loop and basement. This, then, is a limiting-case analysis which provides an upper bound estimate of the loop contribution. The steady-state heat balance on the loop yields the following equations.
A3U3(T3- T4)
-
Heat flow into loop from living space walls
is evaluated in an iterative manner. First, eqn (t) is solved for T4 with 8 set equal to 1. If the resulting 7'4> T2, 8 is set = 0 and T4 is reevaluated from eqn (1). For the case when the loop is present, the heat loss from the living space is given by the following equation
Q, =
A3U3(T3
Loss from upper part of shell
3. RESULTS For the parameter values presented in Fig. 1, the ratio, QI/Q2, and T~ are presented as a function of R~ in Fig. 2. As R= is varied from 0 to 24, R2 is varied so that RI+R~=4.42(Wlm2-C) -~ (24(Btu/hr-ft 2- F) -~) for all the results presented in Fig. 2.
(l) (l)
Thus, the insulation thickness is held constant and the variation in Qt/Q2 is due entirely by the presence of the loop. When there is no insulation in the outer wall, R~ =0, the system acts as a no-loop upper shell with a hole into the basement from the outside. The ratio Q1/Q2 exceeds 1 because the basement is colder than it would be in a single wall building with no leak into the basement. As R~ increases, Qm/Q2 at first
~
TI • - 6 . 7 = C (2OIF) 1.0 RI
I
r4 R~
T4
///
t
T~,- 194°C (67"F1
0.75
L
I"
(1.64 Btu/h-ft2-F)
307m 2 (3300 f t 2 )
T4
] A 4 " l l | l t ~ (120O f t t') U4=0.47 W/nt2c (.083 Btulh-ft2F) Iuz-ga2 w ~ c A 2 • ~23m2
0.50
#
. 20 (6el u.
Ld a~
I0 (SO)
o.a
o
(2400 ft 2)
0
0
0!25
0180
0!75
t.O
0 (321
4 . 2 2 (W/m2C) "1 , {24 (Btu / h - f t 2 F ) -I )
RI//(R I 4- R2)
Fig. I. Schematic diagram of convective loop.
Fig. 2. Effect of loop placement on performance. 461
uJ a. tu
0.25
//
T 2 - 1 2 8 " C (55=F) R I -t- R 2 "
Loss from floor
where Ri = l/U, and R2 = I/U3.
~[A2U2(T2-T4)+A4U4(T3-T4)]=O
The switchin¢ function, 8, is used so that the loop is thermally coupled to the ground only when T4< 7"2, i.e. when natural convection would be expected because the upper chamber is colder than the lower chamber. In the computation algorithm, 8
(3)
T,)+ A4U4(T3- T2) (4)
Loss from upper part of shell
Heat flow into loop from ground and floor. Effective only when 6 = 1
(2)
Loss from floor
Q, =(A3 + A,)/2 [ R t ~ ] ( T 3 -
A,U,(T4-TO +
10 when T2>T4 when T2 ~< T4"
- 8) T2].
For the corresponding case when the loop is not present,
Heat loss from loop to ambient
8=
- ,~T4 - ( 1
- T,) + A,U,[T3
Technical Note
462
Table 1. The effect of loop position on performance (parameters are as given in Fig. 1) Heat Loss From: R1/(RI + R2)
Loop Temp. °C
0.02 0.104
1 8.4
0.187 0.27
Living Space Living Space, Q~ + Ground, Q~ W w
ql/q2 1.039 0.655
2332 1470
26746 10506
10.2
0.58
1303
6543
11.0
0.565
1268
4756
0.354
11.5
0.576
1293
3739
0.437
11.9
0.606
1360
3085
0.52
12L2
0.656
1472
2629
0.604
12.4
0.733
1645
2296
0.687
12.7
0.853
1914
2044
0.77
13.4
1.0
2243
2243
0.854
15.6
1.0
2243
2243
0.937
17.8
1.0
2243
2243
Table 2. The effect of ambient temperature on system performance. Ground temi)erature = 12.8°C(55°F) Ri = R2 = 2.11 (W/m e - °C)-I (12(Btu/hr- ft2°F)-~). Other parameters as shown in Fig. I Heat Loss from: Ambient Temp. °C
LoopTemp. Living Space, Q1 °C W
Living Space + Ground, Q3 W
QI/Q2
-28.9
10.7
1485
5745
-23.4
11.0
1427
4988
0.404 0.436
-17.8
11.3
1370
4231
~.477
-12.3
11.7
1313
3474
0.532
-6.7
12.0
1255
2717
0.608
-1.2
12.4
1198
1961
0.722
4.4
12.7
1140
1204
0.907
10.0
14.7
853
853
1.0
15.5
17.5
450
450
1.0
Table 3. The effect of increased ground temperature on system performance as a function of ambient temperature. Ground temperature=18.3°C (65°F), RI=R2=2.11(W/m2-°C)-~ (12)Btu/hr- ft 2 - °F)-I). Other parameters as shown in Fig. 1 Heat Loss From: Ambient Temp. °C
Loop Temp.
Livin~lSpace ,
°C
W
Living Space
+ Ground, OR W
ql/q2
-28.9
15.5
663
6444
0.187
-23.4
15.8
606
5688
0.193
-17.8
16.2
548
4931
0.201
-12.3
16.5
491
4174
0.211
-6.7 -1.2
16.8 17.2
434 376
3417 2660
0.225 0.248
4.4
17.5
319
1903
0.286
10.0
17.9
261
1146
0.367
15.5
18.2
204
389
0.659
decreases because the ground heats the loop causing T4 to increase as shown in Fig. 2, and the living space heat loss to decrease. As R1 increases still further, QI/Q~ increases because R2 is decreasing and T4, as shown in Fig. 2, is increasing very slowly. Finally, when RI is such that T~ = T2, the ground coupling ceases, and QJQ2 = 1, regardless of T4. The values of Q, that correspond to Fig. 2 are presented in
Table 1. Values for Q3 = Q~+ 8A2U2(T2- T4), the total heat loss rates from living space and ground, are also presented. Note that the reduction in the living space heat loss is "paid for" by increased heat loss from the ground. For example, when (RI/RI + R2)= 0.27, and Qi is at its minimum value, 1268 W, Q3 is 4756 W. Hence, the ground loss is 3488 W. However, at RJ(R~ +R~) =0.437, O~ is still low. 1360W. and
Technical Note yet Q3 is down to 3085 W, making the ground loss 1725, about half of the value obtained when QJQ2 is minimum. For the results presented in Tables 2 and 3, Rt is set = R2 = 2.11(W/m2-°C) -t, (12(Btu/hr-°F-ft2)-b. Note that the contribution of the loop is greater when the ambient temperature is lower. This makes the concept attractive in colder regions if the ground temperature can be maintained. The importance of ground temperature can be seen by comparing Tables 2 and 3. It is hoped that this rather restricted analysis provides some understanding of the importance of heat transfer from the ground to the upper portions of the shell. It is important to note that in this analysis the ground temperature is fixed. The ability of the ground surface to be recharged, either from above from solarheated air or from below, must, of course, be included in a more complete analysis.
463
Q3 rate of heat loss from living space plus ground, W Tj temperature /3/ heat transfer coefficient, W/m 2 - C
Subscripts i= 1 2 3 4 ./= I 2 3 4
outer shell ground-loop inner shell floor ambient ground living space loop
Greek ~$ a switch defined by eqn (2)
NOMENCLATURE A~ area across which heat flow, m2 Q~ rate of heat loss from living space with loop, W Q2 rate of heat loss from living space without loop, W
RE~..RENCF_~ 1. Shurcliff, W. A. Superinsulated Houses and Double-Envelop Houses. Shurcliff, Cambridge, Mass. (Mar. 1980).