Accepted Manuscript Assessing visitors' thermal comfort in historic museum buildings: Results from a PostOccupancy Evaluation on a case study Antonio Martinez-Molina, Paola Boarin, Isabel Tort-Ausina, José-Luis Vivancos PII:
S0360-1323(18)30069-6
DOI:
10.1016/j.buildenv.2018.02.003
Reference:
BAE 5287
To appear in:
Building and Environment
Received Date: 16 November 2017 Revised Date:
30 January 2018
Accepted Date: 4 February 2018
Please cite this article as: Martinez-Molina A, Boarin P, Tort-Ausina I, Vivancos José-Luis, Assessing visitors' thermal comfort in historic museum buildings: Results from a Post-Occupancy Evaluation on a case study, Building and Environment (2018), doi: 10.1016/j.buildenv.2018.02.003. This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please note that during the production process errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.
ACCEPTED MANUSCRIPT 1
ASSESSING VISITORS’ THERMAL COMFORT IN HISTORIC
2
MUSEUM BUILDINGS: RESULTS FROM A POST-OCCUPANCY
3
EVALUATION ON A CASE STUDY Antonio Martinez-Molinaa*, Paola Boarinb, Isabel Tort-Ausinac, José-Luis
4
Vivancosd
RI PT
5
6 7 8 9 10 11 12 13
a
14
Abstract: Adaptive reuse of historic buildings as museums is an effective strategy for
15
retaining heritage architectures while achieving environmental sustainability objectives.
16
Building adaptation, retrofitting and preserving optimal environments for artwork and
17
exhibit preservation are inherently complex, multifaceted tasks. However, indoor
18
microclimates do not only affect collections; occupants and visitors must also be
19
considered. The aim of this research is to explore whether artwork preservation
20
constraints in reused historic building affect patrons. The authors thereby promote a
21
more comprehensive approach, combining the objectives of exhibit conservation,
22
preservation of heritage buildings and adequate indoor conditions, particularly thermal
23
comfort. Data was gathered using the Post-Occupancy Evaluation process applied to a
24
case study where a combination of microclimate monitoring and questionnaire surveys
25
was carried out over a 12-month period. Results demonstrate that: i) the existing
26
microclimate did not always provide visitors with adequate thermal conditions, showing
27
dissatisfaction during the cooling season (July-September), with average TSV values
28
ranging from -1.03 to -1.13; ii) TSV and PMV values were significantly divergent
29
throughout the year, with TSV mainly included within the (-1, 0, +1) band and PMV
30
mainly within the (0, -2) band; and iii) questionnaires show that visitor choice of clothing
Universitat Politècnica de València, Camino de Vera s/n, 46022 Valencia, Spain. School of Architecture and Planning, Faculty of Creative Arts and Industries (CAI), University of Auckland, 26 Symonds Street, 1010 Auckland, New Zealand. c Department of Applied Physics, Universitat Politècnica de València, Camino de Vera s/n, 46022 Valencia, Spain. d Department of Engineering Projects, Universitat Politècnica de València, Camino de Vera s/n, 46022 Valencia, Spain. * Corresponding Author.
AC C
EP
TE D
M AN U
SC
b
1
ACCEPTED MANUSCRIPT is made according to outdoor conditions, with some gender-related variations in the clo
32
level (higher for women), not ensuring thermal comfort inside the museum during the
33
warm season. Results of this research highlight the limitations of Fanger’s model when
34
applied to such typology of buildings, emphasising the need for more research in this
35
field.
36
Keywords: Post-Occupancy Evaluation, Thermal Comfort, Indoor Environmental
37
Quality, Historic Buildings, Museum Buildings.
38
1. Introduction and background
SC
RI PT
31
The International Council of Museums (ICOM) defines a museum as a, “non-
40
profit, permanent institution in the service of society and its development, open to the
41
public, which acquires, conserves, researches, communicates and exhibits the tangible
42
and intangible heritage of humanity and its environment for the purposes of education,
43
study and enjoyment” [1]. Buildings not specifically designed for this purpose host a
44
significant portion of current culture-related activities, thereby serving as de facto
45
museums. This use poses additional challenges not only from the artworks’
46
preservation perspective, but also from the viewpoint of architecture conservation,
47
which is especially testing when heritage architecture is involved. Despite the added
48
complexity, adaptive reuse is an effective strategy for the conservation of cultural
49
heritage, as well as for the retention of redundant buildings, which can otherwise
50
become obsolete and deteriorate due to insufficient funds for their upgrading and
51
maintenance. As building adaptation could be an answer to functional obsolescence
52
caused by societal, economic and environmental changes [2], the reconversion of such
53
heritage into culture-related uses (e.g. museums, galleries, libraries, etc.) represents
54
an important asset for starting positive regeneration processes and has been
55
extensively investigated by scholars [3–6].
AC C
EP
TE D
M AN U
39
2
ACCEPTED MANUSCRIPT Although the retrofit of historic buildings has become a recurrent choice when
57
dealing with adaptive reuse for museum uses, the embedded heritage value could
58
represent an additional constraint in the process due to preservation requirements that
59
can limit the range of intervention from an architectural and technological point of view.
60
However, it is to be noted that traditional constructions could also contribute to reduce
61
indoor microclimate variability, particularly when thick walls and porous hygroscopic
62
materials are present, contributing to the indoor environment with a mitigation effect [7].
63
Additionally, authors working with historic architectures have recognised the positive
64
role played by traditional materials and constructions in passively controlled museums’
65
indoor environments [8,9]. The so-called ‘environmental metabolism’ of traditional
66
buildings is not only related to the physical characteristics of building materials, but
67
also to an architecture and layout, which promote the building’s self-control (through
68
elements such as under-roof cavities or other transitional spaces acting as buffers)
69
and, therefore, a more constant response to external climatic solicitations [10].
M AN U
SC
RI PT
56
The importance of a comprehensive assessment of indoor environmental
71
conditions for the purpose of artworks’ preservation has been overtaken by a focus on
72
energy performance, particularly when adapting a historic building such as a museum.
73
For instance, Lucchi developed a simplified method for assessing and comparing
74
“Environmental and Energy Quality” (EEQ) of museum buildings in order to support
75
decision-making processes through preliminary evaluations of the identification of
76
potential risks for future interventions [11]. The method defined “qualitative
77
performance indicators” that have an impact on EEQ, which were tested on 50 case
78
studies across eight European countries, evaluating both new and retrofitted buildings.
79
The research shows that, in general, the focus is more on a building’s environmental
80
performance than on the energy performance and reliance on active systems, which
81
emphasises the interest towards the building and conservation of collections. With the
82
aim of avoiding damage over time to collections and vulnerable objects exhibited in
83
museum buildings, Corgnati, Fabi and Filippi pointed out the importance of
AC C
EP
TE D
70
3
ACCEPTED MANUSCRIPT microclimate conditions and their medium/long-term monitoring, suggesting a
85
“Performance Index” to examine different parameters at the same time [12]. The
86
relevance of indoor microclimate conditions and the importance of environmental
87
monitoring in museum spaces has also been underscored by a number of guidelines
88
[13–17] and by a variety of case studies [8,18–20], demonstrating the complexity of the
89
subject. On the other hand, D’Agostino et al. argued that, since the monitoring of
90
indoor environmental conditions and related controlling systems is not common in
91
museum buildings, it is preferable to focus on a preventive strategy accounting for all
92
the Indoor Environmental Quality (IEQ) factors and “aimed to the microclimatic
93
assessment of museum environment, the quantification of factors responsible for the
94
degradation processes and the choice of most appropriate interventions to improve the
95
state of conservation” [21].
M AN U
SC
RI PT
84
The literature cited above highlights the importance of microclimate conditions for
97
museum facilities and the collections exhibited and conserved inside them. Monitoring
98
environmental conditions therefore becomes essential for defining preservation or
99
retrofit strategies, as well as activities for preventive conservation. In the first instance,
100
when performing such monitoring in historic environments on either a short-term basis
101
(few months) or as a part of a long-term, continuous campaign, particular care must be
102
given to the installation of sensors, for the avoidance of damage to historic surfaces
103
and to guarantee reliability of measurements over the entire period [22]. Positioning of
104
measuring equipment can also potentially affect data collection, as the choice
105
regarding the location of sensors can be complex when working with museums placed
106
in historic buildings. For instance, installation could be limited by the exhibition or room
107
layout, the presence of decorated, unstable or damaged surfaces, the presence of
108
factors interfering with the monitoring (such as windows) and the position of power and
109
sockets [23].
AC C
EP
TE D
96
110
The existing literature shows a plethora of research focused on microclimate and
111
environmental monitoring in historic buildings and, particularly, in museum facilities, 4
ACCEPTED MANUSCRIPT demonstrating the significant role of field investigations. In many cases, environmental
113
monitoring has been performed with the ultimate goals of risk assessment and/or
114
preventive conservation [24,25], as a base for short or long-term control over
115
significant variations of the different environmental factors involved [12,26,27], for
116
understanding causes of deterioration and defining remediation strategies [28], or for
117
assessing and optimising the building’s thermal and energy performance and
118
dimensioning HVAC systems accordingly [29,30]. The focus has only shifted to the
119
visitors after the preservation of the buildings themselves and the collections they
120
house was thoroughly addressed. Human presence and interaction has only been
121
marginally considered and visitors’ satisfaction in historic museum facilities is a field of
122
research not yet fully investigated. The challenge of building preservation,
123
safeguarding museum objects and, at the same time, accounting for human comfort
124
has often led to the heavy integration of HVAC systems, with an important impact on
125
architecture. In this regard, this paper attempts to promote a shift from the building and
126
collection perspective to the users’ perspective. This approach aligns well with the idea
127
of a “dynamic museum” [31] where the visitor is central to the process and the recipient
128
of the experiential activity. This view does not suggest that the building and its
129
collections are less important than users and visitors, but that a balance between the
130
two should be sought while defining effective strategies for conservation, retrofit and
131
adaptation of historic museum buildings. A similar goal was pursued by Pisello et al.
132
who performed a microclimate analysis that dealt with artwork preservation and
133
occupants’ comfort as contextual objectives [32]. Jeong and Lee investigated effects of
134
the physical environment of museums on visitors’ satisfaction [33]. They distributed
135
questionnaires and observed people’s behaviours in 30 museums located in Seoul and
136
its vicinities, collecting general information on visitors, actual circulation path through
137
the exhibition and individual perception of the museum environments, including thermal
138
comfort.
AC C
EP
TE D
M AN U
SC
RI PT
112
5
ACCEPTED MANUSCRIPT Although the recognised importance of thermal comfort assessment in historic
140
buildings is increasing [34], museum buildings are still not amongst the most
141
investigated uses [35] and literature on this regard is limited. This current gap is mainly
142
related to the many challenges connected to the contextual presence of heritage
143
values and pieces of art, whose importance tends to overcome the need to provide
144
visitors with a comfortable environment. However, some researchers have tried to
145
combine visitors’ thermal comfort evaluation with indoor microclimate monitoring in
146
museums, mainly in the attempt to reach a balance with conservation needs and
147
energy reduction by means of climate optimisation. This is the case of the investigation
148
conducted by Silva et al. [36], who, by highlighting the limited applicability of ISO 7730
149
[16] and ASHRAE 55 [37] for museum environments, defined a reduced thermal
150
sensation scale according to typical clothing ensembles documented by observing the
151
visitors. In fact, people visiting the museum were dressed according to the outdoor
152
climate and not for the indoor environment and, additionally, the length of their visit
153
indoors was limited. These considerations were used to assess Predicted Mean Vote
154
(PMV) and Predicted Percentage of Dissatisfied (PPD) for visitors and this information
155
was then used both to assess the current thermal comfort in the national museum
156
building in Portugal and to optimise the indoor operative temperature and relative
157
humidity [36]. The conflict between people's comfort and the preservation of works of
158
art was also considered by La Gennusa et al. [38]. In this study, a comparison between
159
indoor requirements relating to people's thermal comfort and those for preserving
160
artefacts was performed, introducing a new “simultaneousness index” (IS), defined as
161
“the ratio between the (possible) common area for people's comfort and preserving
162
works of art, and the whole area representing the conditions of comfort” [38]. With the
163
main aim of reducing the overall energy consumption of a museum building in the
164
Netherlands, Kramer et al. [39] introduced visitors’ thermal comfort as a parameter
165
affecting the definition of the optimum set-point strategy. They did this by implementing
166
an adaptive model derived from ASHRAE 55, remarking on the lack of guidelines on
AC C
EP
TE D
M AN U
SC
RI PT
139
6
ACCEPTED MANUSCRIPT thermal comfort specifically defined for museums and taking into consideration
168
people’s adaptability and expectations. Additionally, three relevant thermal comfort
169
studies in buildings were conducted by Mishra et al. [40,41] and by Kotopouleas and
170
Nikolopoulou [42], where authors also examined transitional thermal responses of
171
visitors and travellers.
RI PT
167
The aforementioned studies agree on the lack of research related to thermal
173
comfort evaluation in historic museum buildings and the consequential need to adapt
174
existing standards and guidelines for such conditions, rather than specifically
175
addressing this issue. This research attempts to contribute to this field by implementing
176
a Post-Occupancy Evaluation (POE) process that will enable the collection of
177
qualitative and quantitative data on heritage museum buildings. Although a shared
178
definition of POE does not exist (as it is actually a very flexible methodology), it is
179
intended as “the process of ascertaining the quality and standards of design and
180
construction” [43], or “the process of evaluating any type of buildings in a systematic
181
and rigorous approach after they have been built and occupied” [44]. POE is a very
182
useful method for collecting data on redundant buildings in order to inform their
183
improvement and enhancement. In the case of historic museum facilities, POE is often
184
implemented to assess thermal comfort or, more widely, the overall IEQ, mainly
185
through quantitative monitoring [32,45] and, only in very few studies, with the support
186
of qualitative investigations such as questionnaires [34,46].
187
2. Goals of the research and methodology
M AN U
TE D
EP
AC C
188
SC
172
This research paper aims at verifying the relationship between human thermal
189
comfort and indoor microclimate in historic buildings adaptively reused as museums,
190
thus contributing to the current disciplinary conversation regarding the achievement of
191
a balance between preservation issues and visitors’ satisfaction by promoting a shift
192
from a conservation-centric approach to an integrated approach which includes the
193
people’s perspective as well. 7
ACCEPTED MANUSCRIPT A case study building was used for this study, which is the Museu de la Història
195
de València (Valencia History Museum) in Spain. The research rationale was grounded
196
within the investigation on issues related to the thermal environment inside the historic
197
building, as some visitors claimed thermal discomfort during both summer and winter
198
seasons.
RI PT
194
The research implemented a POE methodology, combining quantitative
200
(measurement of indoor microclimate parameters) and qualitative (questionnaires to
201
visitors) investigations to assess and verify visitors’ satisfaction with the thermal
202
environment. Field measurements and thermal comfort questionnaires were carried out
203
throughout a full year to capture figures during both heating and cooling seasons. The
204
indoor thermal satisfaction questionnaires were thus handed to the visitors while the
205
indoor and environmental monitoring campaign was simultaneously ongoing. Collected
206
data were analysed in order to:
M AN U
SC
199
assess the visitors’ Thermal Sensation Vote (TSV);
208
compare the visitors’ TSV with the visitors’ Predicted Mean Vote (PMV) by using
209
Fanger’s model;
210
assess the visitors’ clothing insulation pattern in relation to indoor and outdoor
211
temperatures.
213
EP
3. Case study description
AC C
212
TE D
207
This research was carried out in a museum building in Valencia (39’28 N – 0’22
214
W), a city on the Mediterranean coast of Spain. According to the Köppen-Geiger
215
classification system [47], Valencia has a hot Mediterranean/dry-summer sub-tropical
216
climate (Csa-Mediterranean Climate). The evaluated building is approximately 8 km
217
away from the Mediterranean Coast and 30 m above the sea level. Monthly
218
temperatures range from a mean of 22ºC during the hottest month and a mean of 10ºC
219
during the coldest months. The annual mean temperature is 18.4ºC with low levels of
220
precipitation, mostly occurring in fall. 8
ACCEPTED MANUSCRIPT The building was built in 1850 as a main potable water reservoir for the city of
222
Valencia (9,000 m3 of water could be contained inside the construction) and was used
223
as such for over a century (Figure 1). In 1998, the local government began a process
224
of restoration and adaptation of the building in order to transform it into what today is
225
the Valencia History Museum. The museum is not listed but it is considered as a
226
‘building of cultural interest’.
227 228 229
AC C
EP
TE D
M AN U
SC
RI PT
221
Figure 1. Construction site photo (above) and original building plan (below). Source: Ministry of Development of Spain
230
The construction has a flat roof supported by a brick structure composed of 11
231
barrel vaults and a grid of 200 masonry columns. The building is developed on one
232
floor only with no openings in the side walls or in the roof, except for five auxiliary
233
metallic doors and the main entrance. The lack of fenestrations is derived by the
234
original use of the building as a cistern and has been preserved in the adaptive reuse 9
ACCEPTED MANUSCRIPT project as a distinctive quality of the historic construction. The building envelope is
236
composed of 95 cm thick uninsulated masonry external walls, an 18 cm thick air cavity
237
and an 18 cm thick external layer of brick veneer. The main façade of the museum has
238
a ceramic tile finishing underneath a waterfall, which falls from the roof to the side of
239
the building (Figure 2). The flat roof is composed of a 20 cm waterproof reinforced
240
concrete slab.
243
Figure 2. Internal (above) and external (below) building appearance. Source: Valencia History Museum
AC C
241 242
EP
TE D
M AN U
SC
RI PT
235
From the thermal perspective, the most important characteristic of this building is
244
its underground development for over 50% of the volume. Moreover, on top of the flat
245
roof there is a public green area with a small garden, a fountain and two basketball
246
courts. Table 1 summarises the thicknesses and thermal transmittance of the building
247
envelope. Because the building is partially underground and without any fenestrations,
248
natural ventilation does not exist and the building is therefore ventilated continuously
249
(24 hours a day, seven days a week) by means of a mechanical system of ceiling
250
ducting (Figure 3). 10
ACCEPTED MANUSCRIPT Most of the building’s central area (main cistern’s volume) is used for the
252
exhibition, although the perimeter area is used for small rooms such as storages,
253
toilets and other service rooms. Connected internally to the west side of the main
254
museum building is a newly added office where the administrative personnel work.
255
Museum opening hours are from 9:30am to 7:00pm, Tuesday through Saturday, and
256
9:30am to 3:00pm on Sundays.
257
RI PT
251
Table 1. Thickness and thermal transmittance of the building envelope and openings
2
M AN U
SC
Building Component Thickness [m] U-value [W/m K] External walls* 1.240 0.623 Flat roof 1.100 0.150 Ground slab 0.850 0.263 Side doors 0.160 3.124 Main door 0.020 5.207 *Weighted average value between the wall above the ground and the wall below the ground.
AC C
EP
TE D
258
259 260
Figure 3. Museum plan with data loggers’ locations (red spots) and HVAC units and ducting placement
261
and distribution (blue boxes and lines)
262
4. Environmental monitoring
263
To assess thermal aspects of the building’s Indoor Environmental Quality (IEQ),
264
a meticulous monitoring campaign was carried out by measuring indoor air 11
ACCEPTED MANUSCRIPT 265
temperature and relative humidity, as well as external environmental parameters
266
(Table 2). More detailed probabilistic results are shown later in Figure 7 which gives a
267
comprehensive overview of the indoor environmental conditions. Table 2. Indoor and outdoor average conditions during the survey period for the days analysed
RI PT
August 2015 September 2015 October 2015 November 2015 December 2015 January 2016 February 2016 March 2016 April 2016 May 2016 June 2016 July 2016
Outdoor Conditions Air Relative Solar Temperature Humidity [%] Radiation 2 [°C] [W/m ] 26.00 63.00 253 22.00 62.00 197 19.00 65.00 133 15.00 61.00 121 13.00 69.00 82 13.00 56.00 85 13.00 48.00 131 14.00 49.00 198 16.00 56.00 250 18.00 58.00 280 22.00 59.00 316 25.00 60.00 296
SC
Month
Indoor Conditions Air Relative Temperature Humidity [°C] [%] 22.44 64.23 22.15 64.28 21.97 63.75 21.74 55.65 21.28 51.81 21.34 46.74 21.48 43.51 21.77 41.89 22.12 49.39 21.81 56.85 22.21 63.74 22.21 67.53
M AN U
268
269
The monitoring period was a full calendar year, from August 2015 to July 2016,
271
and data were collected hourly. Internal monitoring was carried out with the use of a
272
network of data loggers evenly distributed throughout the building (Figure 3). Each
273
device was installed at a height of 1.10 m from the ground and at least 1 m away from
274
any external walls, thereby meeting the requirements of ASHRAE 55 [37] for standing
275
occupants (Figure 4). Regarding the external environment, data were collected from a
276
meteorological station located 3 km away from the building. Specifications of the
277
instruments for data gathering are presented in Table 3.
AC C
EP
TE D
270
278 12
ACCEPTED MANUSCRIPT 279
Figure 4. Data loggers placed inside the building (as per the red spots in Figure 3)
280
Table 3. Characteristics of monitoring devices
Brand & Model
Measuring Range
Precision
Response
Siemens-Symaro
-30ºC to 50ºC
±0.2 ºC
60 s
Siemens-Symaro
0% to 100% RH
±5%RH
60 s
Indoor Air Speed
Testo – 435-2 Hot Wire Probe
0m/s to 20m/s
0.03m/s
0.5 s
Vantage Pro2
-40ºC to 65ºC
-
2.5 s
Vantage Pro2
1% to 100% RH
±2%RH
2.5 s
Vantage Pro2
1 to 320Km/h
±1Km/h
2.5 s
±5% ±0.2mm
50 s -
Outdoor Air Temperature Outdoor Relative Humidity Outdoor Wind Speed & Direction Solar Radiation Rain
0 to 1800W/m -
SC
Vantage Pro2 Vantage Pro2
2
RI PT
Measured Physical Variable Indoor Air Temperature Indoor Relative Humidity
281
283
Valencia during the study are represented in Figure 5. Additionally, Figure 5 shows the
284
indoor and outdoor temperatures and solar radiation during the same period of time.
35
25 20 15
250 200 150
EP
Temperature (°C)
300
TE D
30
350
10
AC C
5
100 50 0 Jul-16
Jun-16
May-16
Apr-16
Mar-16
Feb-16
Jan-16
Dec-15
Nov-15
Oct-15
Sep-15
Aug-15
0
Solar Radiation
Minimum Temp.
Average Outdoor Temp.
Maximum Temp.
Average Outdoor RH
Minimum RH
Relative Humidity (%) & Solar Radiation (W/m2)
Temperature and Relative Humidity values (minimum, average and maximum) in
M AN U
282
Maximum RH
285 286
Figure 5. Solar radiation, outdoor temperature (T) and relative humidity (RH) values (minimum, average
287
and maximum) in Valencia during the study
288
5. Thermal comfort survey 13
ACCEPTED MANUSCRIPT To evaluate the subjective opinions on the occupants’ thermal comfort,
290
questionnaire surveys were designed following the parameters of ASHRAE 55 [37] and
291
Fanger’s Model [48]. Questionnaires were handed out to the visitors by the museum
292
staff who also provided a brief description of the study in order to clarify the purpose of
293
the questionnaire and to obtain more reliable answers.
294
RI PT
289
5.1. Questionnaire
The questionnaire was designed with the goal of extracting honest and reliable
296
responses with the following considerations in mind: brevity and simplicity. Indeed, it
297
was unlikely that visitors would have filled out the questionnaires if they were too long
298
to complete or too difficult to understand, and responses would not have reflected the
299
real experience. Additionally, the survey was translated into four languages: Spanish,
300
Valencian, English and Italian, as these are the main languages spoken by the visitors
301
of the museum. Questionnaires were offered to adults only (aged 18+ years), in order
302
to avoid problems related to the understanding of thermal comfort conditions, which
303
can be an issue for young people and children [34]. Visitors were given the
304
questionnaire at the entrance and had to return it at the end of their visit, in order to
305
capture their full experience inside the museum.
TE D
M AN U
SC
295
The filled questionnaires received were 440 out of 18,483 visitors within the
307
study period. However, before the study started, a trial period was set up during which
308
105 questionnaires were filled by the museum staff over a two-month span (June and
309
July 2015). This testing period was very useful for setting up the protocol and for fine-
310
tuning the questionnaire before distributing it to the visitors, thus minimising any
311
potential misunderstandings of the questions and ensuring trustworthy and sincere
312
answers. Questions aimed at obtaining as much information as possible about the
313
subjective thermal comfort opinion of each visitor during their visit indoors, in addition
314
to collecting the necessary data to calculate the Predicted Mean Vote (PMV) according
315
to Fanger’s method. The questionnaire included questions about:
AC C
EP
306
14
ACCEPTED MANUSCRIPT date and time of arrival to the museum and time of the answer to the questionnaire;
317
age (bands arranges as 18-30, 31-40, 41-50, 51-60 or +61), origin (from Spain or
318
from other country) and gender of the visitor (male or female);
319
indoor and outdoor Thermal Sensation Vote (TSV), according to ASHRAE 55’s
320
seven-point sensation scale (-3, -2, -1, 0, +1, +2, +3);
321
clothing insulation, with the most typical fourteen articles of clothing (based on
322
ASHRAE 55) included as choices in the answer options, to help fill the
323
questionnaire;
324
visitors’ domestic experience with HVAC units (whether he/she owned an HVAC unit
325
at home and whether he/she typically had used it before the visit);
326
visitors’ Metabolic Rate based on transportation method (walking, running, biking or
327
motorized transportation), and indoor air quality (very good, good, neutral, bad, very
328
bad) and humidity (very dry, dry, neutral, humid, very humid) through a series of
329
simplified questions;
330
visitor´s preference for the indoor temperature (much cooler, cooler, slightly cooler,
331
neither warmer nor cooler, slightly warmer or warmer much warmer);
332
visitors’ opinion about any other aspect regarding their thermal comfort that they
333
might wanted to highlight.
SC
M AN U
TE D
EP
335
5.2. Clothing Insulation and Metabolic Rate Clothing insulation (clo) and metabolic rate (met) are the two human factors in
AC C
334
RI PT
316
336
Fanger’s method; the other measurements collected during the monitoring campaign
337
were considered to be environmental aspects. A set of garments that are typically worn
338
in a mild climate was used to create the different options comprising in the survey
339
taker’s outfit (Table 4), according to ASHRAE 55. In an effort to streamline the survey
340
answers, the available garment selections were simplified and stripped down to the
341
basics. Afterwards, clothing insulation was calculated for each filled survey on the clo
342
values given by ASHRAE 55. 15
ACCEPTED MANUSCRIPT 343
Table 4. Garment Insulation Options Iclu [clo] included in the questionnaire, according to ASHRAE 55
Iclu [clo]
Garment item Underwear Panties T-shirt
0.03 0.08 Sweaters 0.25 0.36 0.44 0.12 0.19 0.25 0.34
SC
0.06 0.24 0.23
M AN U
Shirts and Blouses Sleeveless/scoop-neck blouse Short-sleeve dress shirt Long-sleeve dress shirt Long-sleeve sweatshirt Trousers Short shorts Straight trousers Skirt Footwear Shoes 0.02 Boots
RI PT
Long-sleeve (thin) Long-sleeve (thick) Blazer
344
0.02 0.10
Since the average visitor spend 1-2 hours per visitation, the authors followed
346
ASHRAE 55’s directions (Table 5) and did not take into account the method of
347
transportation to the museum. Instead, a 2.0 met rate (walking slowly throughout the
348
museum) was applied for the purpose of PMV calculations.
349
Table 5. Comparison between the standard activities (and metabolic rates) based on ASHRAE 55 and the
350
methods of transportation monitored in the case study during the survey
AC C
Walking Running Biking
Motorised Transport
351
Activity (according to ASHRAE 55)
EP
Activity (surveyed methods of transportation)
TE D
345
Walking (0.9 m/s, 3.2 Km/h, 2.0 mph) Calisthenics/Exercise Calisthenics/Exercise Driving Public transportation
Metabolic Rate (according to ASHRAE 55) 2
[W/m ]
[met]
115 175 - 235 175 - 235
2.0 3.0 - 4.0 3.0 - 4.0
60 - 115
1.0 - 2.0
6. Results of the research
352
This section presents the findings of the quantitative full-year monitoring
353
campaign and the results of the qualitative data gathered through questionnaires,
354
which were used to evaluate visitors’ opinions on indoor environmental conditions. The
355
recorded data were used to calculate and evaluate Fanger’s thermal comfort values
16
ACCEPTED MANUSCRIPT based on ASHRAE 55 [49] by using MATLAB, and following ISO 7730, Annex D [50].
357
In this research, indoor environmental conditions such as air temperature, air speed
358
and relative humidity data were measured [51]. Due to the building’s very high thermal
359
mass, radiant temperature was estimated based on the approximation that air
360
temperature is close enough to radiant temperature (Tair = Tradiant). Human factors
361
identified in Fanger’s method, such as metabolic rate and mechanical power, were also
362
estimated based on the answers to the questionnaires (according to ASHRAE 55 [49]).
363
Finally, clothing insulation was calculated for each answer based on visitors’ replies,
364
according to ISO 7730 [50].
SC
RI PT
356
Figure 6 summarises indoor and outdoor temperature and relative humidity
366
values monitored during the study, showing a mainly stable average indoor
367
temperature, possible thanks to the building’s high thermal mass, hypogeum space
368
and absence of windows. Figure 7 illustrates a histogram of operative temperatures
369
recorded in the museum, over the complete survey campaign. It shows that indoor
370
temperatures vary within a very narrow range of ~3 ºC. Figure 7 also illustrates the
371
cumulative probability distribution curve of the indoor operative temperatures. This
372
curve shows a more detailed distribution of temperatures and was obtained using the
373
cumulative values (temperatures in ºC) that are equal to or lower than the operative
374
temperature value at each particular plots on the curve.
EP
TE D
M AN U
365
80
AC C
30
Temperature (°C)
60
20
50
15
40 30
10
20 5
10
375
Average Outdoor RH Average Outdoor Temp.
Jul-16
Jun-16
May-16
Apr-16
Mar-16
Feb-16
Jan-16
Dec-15
Nov-15
Oct-15
Sep-15
0 Aug-15
0
Average Indoor RH Average Indoor Temp.
17
Relative Humidity (%)
70
25
ACCEPTED MANUSCRIPT Figure 6. Indoor and outdoor relative humidity and air temperature average values during the study in
377
Valencia
378 379
Figure 7. Histogram and cumulative probability distribution curve of the indoor operative temperatures
380
recorded in the museum.
6.1. Thermal Sensation Vote (TSV) values assessment
TE D
381
M AN U
SC
RI PT
376
Results show that there was a negative correlation between outdoor and indoor
383
temperature, and thermal sensation. As Figure 8 shows, the warmer the outdoor
384
temperatures, the colder the visitors felt inside the museum and vice versa. This
385
means that visitors felt discomfort inside the museum due to the temperature gap
386
during the summer and winter seasons. Although the same correlation existed between
387
indoor temperature values and thermal sensation, it should be noted that the real
388
indoor temperature values were practically always constant. This is due to the building
389
being mechanically ventilated 24/7, as thermal consistency is necessary for artwork
390
and artefact preservation. Hence, we can assume that the differences in the visitors’
391
answers were affected only by outdoor temperatures and, therefore, by the difference
392
between indoor and outdoor temperatures (thermal leap).
AC C
EP
382
18
ACCEPTED MANUSCRIPT 30.0 24.5 22.4
22.1
21.9 19.6
20.0
17.2
15.0 10.0 5.0 0.0 Indoor Temperature
-3, -2
Outdoor Temperature
-1, 0, +1
Indoor Temperature
Outdoor Temperature
+2, +3
Figure 8. TSV ranges against average indoor and outdoor temperatures
M AN U
393 394
Outdoor Temperature
SC
Indoor Temperature
RI PT
Temperature (°C)
25.0
To further support this consideration, there is a clear correlation between outdoor
396
and indoor temperatures and the visitors’ answers ranges (>1, 1 - -1, <-1). Figure 8
397
also proves the theory that the warmer the outdoor temperatures, the colder the visitors
398
feel. The difference between the visitors who felt neutral and hot is very limited and it is
399
therefore considered negligible. On the other hand, individuals who felt cold were more
400
affected by outdoor temperatures than the other two groups, following the tendency
401
previously presented.
TE D
395
Environmental temperatures and Thermal Sensation Votes (TSV) were evaluated
403
by using Pearson product moment correlation [40]. If p is smaller than the significance
404
level (default is 0.05), then the corresponding correlation in r is considered significant.
405
As such, TSV had a significant correlation with the indoor temperature (r= -0.34, p <
406
0.001). This correlation, although statistically significant, is quite weak. The plots for
407
TSV VS operative temperature for a whole period (1 year) are shown in Figure 9. It
408
may be observed that the correlation, although significant, is still quite weak.
AC C
EP
402
19
ACCEPTED MANUSCRIPT 3 2 y = -0.0899x + 1.4666 y = -0.7797x + 16.877
-1 -2 -3 0
5
10
15 20 Temperature (ºC)
Outdoor Temperature Linear (Outdoor Temperature)
RI PT
0
25
30
35
SC
TSV
1
Indoor Temperature Linear (Indoor Temperature)
Figure 9. Correlation between Thermal Sensation Vote (TSV) VS outdoor and average indoor temperatures.
412
The influence of gender in indoor thermal comfort opinions can be seen
413
seasonally in Figure 10. Generally, gender did not prove to be very influential on
414
thermal comfort perceptions, but there was a seasonal caveat. During summer months,
415
the answers within the middle range (-1, 0, +1) were different, with an 82% satisfaction
416
for males and only a 68% satisfaction for females across the band. Additionally, during
417
the same period, answers showed gender-based differences with 17% of males and
418
27% of females who reported feeling either cool or cold. Some gender variations were
419
noticeable in winter and spring, although values remained in the central comfort band:
420
a 15% gap was present in correspondence to the ‘neutral’ value in winter and in the
421
‘slightly cool’ in spring, with men feeling slightly warmer than women in winter and
422
women feeling slightly cooler than men in spring. During the remaining periods, values
423
by gender varied only slightly and thermal comfort ranges values were very similar. In
424
addition to providing a gender perspective, Figure 10 supports the earlier finding of a
425
negative correlation between warmer outdoor temperatures and visitors’ cooler thermal
426
sensations.
AC C
EP
TE D
M AN U
409 410 411
20
ACCEPTED MANUSCRIPT Male
Summer
Female
60% 49% 50%
50%
18% 15%
20% 11%10% 7%
9% 2%
2% 2% 1% 0%
10% 1%
-1
0
+1
+2
-3
60% 50%
42%
30%
21%
+3
Male
Female
25%
20%
11% 6% 0%2% 0%
+2
40%
30% 20%
+1
40%
32% 19%
0
54% 50%
M AN U
40%
-1
Spring
Female
57%
50%
-2
Male
Winter 60%
+3
SC
-2
12%13%
4% 0% 0% 0%
2%
0% -3
RI PT
18% 15%
0%
6%4%
10%
0% 0%
0%
4% 4% 0% 0%
14% 5%
5% 0% 0% 0%
0%
-3
-2Figure -110. Comparison 0 +1 +2 +3 male and female -3 TSV -2 values -1 by 0season +1 between
+2
+3
TE D
427 428
28% 25%
30%
23%
20%
10%
42% 40%
40%
30%
10%
Female
60% 50%
40%
Male
Fall
Figure 11 depicts the Thermal Sensation Votes of visitors. Data were
430
summarised monthly, using the average and the standard deviation values. Even
431
though the mean values showed that occupants felt comfortable almost the entire year
432
(a part from July, August and September when average values move below the -1
433
band), the standard deviation demonstrated a wider amplitude of values during the
434
cooling season (particularly June, August and September), with visitors feeling
435
uncomfortable (cool or cold), while, during the heating season (December, January and
436
February), visitors did report feeling comfortable.
AC C
EP
429
21
ACCEPTED MANUSCRIPT 3
2 1.32 0.76
TSV
0.51
0.41
0.03
0.02
0
1.18 0.27
0.00
0.00
-0.38
-0.50 -0.76
-1
-1.03
-1.06
-1.13
-1.14
-2.16
Jul-16
Jun-16
May-16
Mar-16
Feb-16
Jan-16
Dec-15
Nov-15
Oct-15
Sep-15
Aug-15
SC
-2.33
Apr-16
-2.07
Figure 11. Average and standard deviation of overall TSV values by month
M AN U
440
-0.73
-1.39
-3
439
-0.43
-0.45
-1.82
-2
437 438
-0.67 -1.11
-1.26
0.49
-0.20
-0.32 -0.64
0.87
0.74
0.67
0.48
RI PT
1
6.2. Comparison between Thermal Sensation Vote (TSV) values and Predicted Mean Vote (PMV) values
Figure 12 compares the calculated Predicted Mean Vote (PMV) average values
442
and measured Thermal Sensation Vote (TSV) average values, by month. While TSV
443
values were mainly concentrated in the neutral area (-1, 0, +1), PMV values were
444
mainly lower than TSV values and shifted towards the cooler bands, except for the
445
cooling session months (May-September) during which occupants reported to be
446
colder. According to Fanger’s model, visitors should feel uncomfortable due to the
447
HVAC system performance; however, since the results in this investigation exhibited
448
fairly stable TSV values in the comfort zone, Fanger’s model does not prove to be
449
reliable in this case.
AC C
EP
TE D
441
22
ACCEPTED MANUSCRIPT 3.00
0.79
0.41 0.00
0.27
-1.06
-0.73
-1.17
-1.13
SC
Jul-16
Jan-16
-1.03
Jun-16
-2.04 Feb-16
-1.99 Dec-15
Oct-15
Sep-15
Nov-15
-2.30 Aug-15
0.21 -0.17
RI PT
-1.28
-2.00 -3.00
-0.45
0.01
-0.54 -1.01
Average PMV
Average TSV
Figure 12. Comparison between PMV and TSV average values by month
M AN U
450 451
-0.20
May-16
-1.03 -1.00
0.00 -0.32
-0.38
0.00
Apr-16
1.00
Mar-16
TSV values
2.00
As argued by other researchers [36], visitor metabolic rate is a critical factor
453
when using Fanger’s model for museum buildings. In order to take as many factors as
454
possible into consideration, the transportation method employed by each visitor to
455
arrive at the museum was considered according to the options as directed in the
456
ASHRAE 55 [49] and listed in
TE D
452
Since the average visitor spend 1-2 hours per visitation, the authors followed
458
ASHRAE 55’s directions (Table 5) and did not take into account the method of
459
transportation to the museum. Instead, a 2.0 met rate (walking slowly throughout the
460
museum) was applied for the purpose of PMV calculations. Table 5. Since the average visiting time was between 1 and 2 hours, a fixed
AC C
461
EP
457
462
value for metabolic rate has been assigned for all visitors to calculate PMV values
463
(slowly walking 2.0 met). Therefore, PMV and TSV average values were calculated
464
and measured, respectively. As depicted in Figure 13, while TSV values remained
465
within the neutral range (-1, 0, +1) throughout the year, PMV values had diverse
466
results. TSV values lingered between 0 and -1, independent of the transportation
467
method, in accordance to Mishra et al.’s [40] results, while PMV values were quite
468
different. In particular, visitors who used motorised transportation had average PMV
23
ACCEPTED MANUSCRIPT 469
values of +2.1, whereas the PMV values for methods of transportation with higher
470
metabolic rates were as follows: biking +1.0, walking +1.3 and running +1.2.
3 2.1 1.3
1.0
1.2
1 0 -1
-0.4
-0.4
-0.2
Biking
Motorized transport
Walking
-3 PMV
TSV
SC
-2
RI PT
PMV & TSV values
2
-0.3
Running
Figure 13. PMV and TSV average values comparison between transportation methods for visitors staying
473
less than one hour.
474
M AN U
471 472
6.3. Clothing insulation assessment
In public buildings, such as museums, occupants do not have any control over
476
indoor temperature or natural ventilation, therefore adding or removing garments is the
477
only adaptive choice that is available to them. The type and amount of clothing worn is
478
thus a very important factor to consider while assessing subjective thermal comfort.
479
Figure 14 shows the average clothing levels and standard deviations for each month of
480
the monitoring campaign. It is very clear that during colder months, visitors’ clothing
481
level was much higher than during the warmer ones. Looking at the standard deviation,
482
values were very stable, reaching a gap between the highest and lowest values around
483
0.30 clo or even 0.40 clo. There was a slight reduction in this standard deviation
484
amplitude during the coldest months (January and February) which may have been
485
due to the very uncertain weather conditions.
AC C
EP
TE D
475
24
ACCEPTED MANUSCRIPT 1.00
0.95
0.90 0.84 0.78
0.70
0.77
0.69
0.58
0.56
0.58
0.57
0.38
0.61
0.42
0.40
0.27
0.18
0.46 0.32
Jul-16
May16
SC
Mar-16
Feb-16
Jan-16
Dec-15
Sep-15
Oct-15
Nov-15
0.00
Jun-16
0.17
0.10 Aug-15
0.58
0.51
0.47
0.25
486 487
0.83
0.70
0.35
0.30 0.20
0.88
0.69
0.48
0.47
0.40
0.73
0.66
0.58
0.50
0.73
0.91
RI PT
0.60
0.88
Apr-16
Clothing level
0.80
0.88
Figure 14. Average and standard deviation of clothing levels by month
Figure 15 displays the correlation between clothing levels and outdoor
489
temperature by gender. Outdoor temperatures are obviously very unstable. Clothing
490
levels, as expected, decreased when outdoor temperatures increased. Finally, male
491
and female choices were slightly different when considering the same outdoor
492
temperatures, with females choosing a slightly warmer clothing combination.
TE D
M AN U
488
1.4 1.2
y = -0.0238x + 1.0933
EP
y = -0.0264x + 1.1092
0.8 0.6
AC C
Clothing level
1
0.4 0.2 0
0
Male visitor
5
10
15 20 Outdoor Temperature (°C)
Female visitor
Linear (Male visitor)
25
30
35
Linear (Female visitor)
493 494
Figure 15. Correlation between clothing level and outdoor temperatures by gender for each survey answer.
25
ACCEPTED MANUSCRIPT 495
7. Discussion The case study investigated in this research offers an opportunity to understand
497
occupants’ satisfaction with a thermal environment in which their stay is limited to a
498
short amount of time (1-2 hours), but yet affects their overall experience. Being mainly
499
a hypogeum space with no windows, which is an important component of the building’s
500
heritage value that has been preserved and integrated in the adaptation project, the
501
building offers a peculiar environment for art collection and for visitors at the same
502
time. On one side, more stable conditions in terms of air temperature and relative
503
humidity offer the most suitable microclimate conditions for the preservation of
504
artefacts and the building itself; on the other, the few times that visitors reported
505
discomfort, this discomfort was generated by the gap between indoor and outdoor
506
temperatures. In order to guarantee indoor microclimate stability for conservation
507
purposes while providing the airflow rates suitable for its use, the building is equipped
508
with a mechanical system working on a 24/7 basis which generates more challenging
509
situations for human thermal comfort, mainly due to the temperature gap between the
510
inside and outside. Therefore, the negative thermal leap affects visitors’ satisfaction
511
with the thermal environment, while the positive gap does not, as participants did not
512
express any discomfort during the winter season.
EP
TE D
M AN U
SC
RI PT
496
Some minor fluctuations in the indoor air temperatures were, however, registered
514
during the field monitoring, mainly during the winter season (November-March), with a
515
drop of 1.2ºC (Figure 6). This demonstrates the effectiveness of the building’s thermal
516
masses (roof and walls), along with the hypogeum development of the building,
517
producing a positive effect in mitigating the heat transfer and in keeping the indoor
518
temperatures more stable, despite the combined effect of: i) the heat transfer through
519
the uninsulated extended flat roof surface; ii) the almost absence of winds cooling
520
down the roof’s surface; and iii) the unobstructed surrounding environment, with no
521
shadows from adjacent buildings. If the thermal mass is an effective hygrothermal
AC C
513
26
ACCEPTED MANUSCRIPT 522
barrier during the warm and hot seasons, it appears to affect the indoor environment
523
negatively in the cold season. An interesting point worth-discussing is the divergence between TSV and PMV,
525
as shown in Figure 14. The PMV values calculated according to Fanger’s model
526
suggest that visitors should have expressed satisfaction with the thermal environment
527
between May and November only, with a limit condition in August shifted towards the
528
warmer side of the central band (-1,0,+1), and feeling cool or cold for the rest of the
529
monitored period. In reality, visitors expressed a different opinion, as the average
530
calculated TSV sits within the central band for almost the entire year, with the
531
exception of the summer season, as discussed before. This worth-mentioning
532
difference points out the fact that the metabolic rate does not have a significant impact
533
on the visitors’ thermal comfort sensation in this building. The divergence between TSV
534
and PMV is clear when analysing the method of transportation utilised by the visitors to
535
arrive at the museum (even though PMV values were calculated with the same met
536
rate of 2.0 met) (Figure 13). Once again, PMV show values out of the neutral band,
537
while TSV values are within the neutral band. The most relevant result is related to the
538
use of motorised transportation, where metabolism levels are very low and, according
539
to PMV results, people should feel cool or cold in fall, winter and spring, and
540
comfortable in summer, a result in contrast with TSV values. Overall, results
541
demonstrate the limits of Fanger’s model when used in museum environments and in
542
mechanically controlled climates, as in the case study investigated in this research.
SC
M AN U
TE D
EP
AC C
543
RI PT
524
A possible direction for mitigating summer discomfort could be working with
544
indoor temperatures in summer, currently ranging between 22.21ºC and 22.44ºC, by
545
moving the set-point towards the upper threshold of the temperature range
546
recommended for artwork conservation (21ºC-24ºC), in order to reduce the
547
temperature gap between outdoors and indoors. This will have a positive effect not
548
only on visitors’ thermal comfort, but also on the museum’s management due to the
549
energy savings resulting from a lower pressure on the cooling system during the hot 27
ACCEPTED MANUSCRIPT season. However, moving forwards from Fanger’s model, considering seasonal
551
temperature variations in the set-up of optimal temperature conditions in indoor
552
environments would produce positive effects on occupants’ comfort, artwork
553
preservation and museum environments. In fact, the application of an adaptive
554
approach would account for the human response to fluctuations related to different
555
seasons [52], establishing a direct connection between outdoor and indoor thermal
556
conditions that would not necessarily affect the requirements for the preservation of art
557
and the built heritage in a negative way, as long as it is associated with the extension
558
of the temperature bandwidth, producing positive effects on overall energy savings as
559
well [39,53].
SC
RI PT
550
A final reflection should be made on the visitors’ participation in the survey. If
561
compared to the total amount of people visiting the museum during the research period
562
(18,483), those who accepted to undertake the questionnaire (440) were only 2.4%.
563
This means that the issue of visitors’ thermal comfort in museum buildings is still
564
understood as a secondary aspect and people do not engage with this enough.
565
Considering the scarcity of resources on this topic, more research needs to be done, in
566
order to contribute to the development of an integrated approach towards a combined
567
conservation and human comfort based adaptive reuse and building retrofit.
568
8. Conclusions
TE D
EP
AC C
569
M AN U
560
This paper investigated the relationship between human thermal comfort and
570
indoor microclimate in a historic building in Valencia, which has been adaptively reused
571
as the Valencia History Museum. The research implemented a Post-Occupancy
572
Evaluation methodology, performing a field monitoring on indoor microclimate
573
conditions and a questionnaire survey to visitors over a period of one year, in order to
574
assess the level of comfort perceived by the visitors during their stay inside the
575
heritage building.
576
The main results of the research are: 28
ACCEPTED MANUSCRIPT TSV assessment: visitors showed more dissatisfaction with the indoor thermal
578
environment during the cooling season (July-September), possibly because of the
579
gap between indoor and outdoor temperatures, with males and females generally in
580
agreement on this;
581
comparison between TSV and PMV: Fanger’s model for calculating PMV does not
582
prove to be representative of the real thermal environment as perceived by visitors
583
in this case study, as TSV and PMV values were significantly divergent across the
584
year, also in regard to metabolic rates;
585
clothing assessment: visitors choose a clothing combination according to outdoor
586
conditions; however, this choice does not appear to be successful during their visit
587
in the museum, mainly during the summer season, contributing to discomfort.
M AN U
SC
RI PT
577
The paper suggests that the conservation criteria of artworks should not be the
589
only parameters to be taken into account, rather, a more comprehensive approach
590
should be considered that also includes human thermal comfort. The resulting
591
integrated approach should assess the suitability of the indoor microclimate to foster
592
artwork preservation, heritage adaptation and indoor environmental quality for
593
occupants. Also, when retrofitting heritage buildings and adapting them to new uses,
594
this combination could have a significant impact on existing historic structures. Similar
595
to the role of structural monitoring for the upgrade of existing structures, environmental
596
monitoring should be performed in historic buildings to understand their indoor
597
microclimate and its variations compared to the external environment, in order to
598
inform the retrofit project. Monitoring techniques should be non-invasive and, possibly,
599
contactless, in order to avoid any damages to the existing materials and surfaces.
AC C
EP
TE D
588
600
Historically, the adaptation of heritage buildings into museums has been driven
601
by the goal of achieving optimal environmental conditions for artwork conservation.
602
This single objective has often resulted in the integration of very intrusive plant systems
603
in the building in order to provide the required hygro-thermal conditions, to the
604
detriment of existing materials and to the neglect of the cultural value of the building 29
ACCEPTED MANUSCRIPT itself. This approach has exacerbated the loss of materials in buildings originally
606
constructed for different uses and later adapted to museums, as adaptive reuse itself
607
can have high impacts on building fabrics due to compliance with mandatory
608
requirements (such as structural, mechanical, fire protection, etc.). On the contrary,
609
more recent approaches [54] promote a convergence between the conservation of the
610
building and the conservation of artefacts by taking fully advantage of both passive and
611
active systems, thus limiting the loss of materials and, consequently, of heritage value.
612
Ultimately, this approach will improve the level of sustainability of the overall
613
intervention, from an environmental (reduced energy consumption and improved indoor
614
environmental quality), social (reduced impact of heritage value as manifestation of a
615
social responsibility) and economic (reduced operation costs) point of view, in an
616
attempt of achieving a comprehensive, yet respectful adaptation process [55,56].
617
9. Acknowledgements
M AN U
SC
RI PT
605
This research would not have been possible without the co-operation of the
619
Valencia History Museum, Spain, and the valuable contribution of the director of the
620
museum, Javier Martí, staff and visitors.
TE D
618
This research has been supported by the Performance-Based Research Fund
622
(PBRF), year 2017, round 1 (Project n. A1707; Principal Investigator Dr Paola Boarin)
623
of the School of Architecture and Planning, The University of Auckland.
AC C
EP
621
624
The authors would like also to acknowledge Priscila Besen for her support in the
625
research and for the graphic elaborations related to the case study.
626
10. References
627 628 629 630 631 632 633 634 635
[1] [2] [3]
[4]
International Council of Museums (ICOM), ICOM Statutes, 2016. S. Wilkinson, H. Remøy, C. Langston, Sustainable building adaptation: innovations in decisionmaking, Chichester, England: Wiley-Blackwell, 2014. B. Plevoets, K. Van Cleempoel, W.I.T.T. on the B. Environment, Adaptive reuse as a strategy towards conservation of cultural heritage: A literature review, in: 12th Int. Conf. Struct. Repairs Maint. Herit. Archit. STREMAH 2011, Chianciano Terme, 2011: pp. 155–164. doi:10.2495/STR110131. D. Misirlisoy, K. Günçe, Assessment of the adaptive reuse of castles as museums: Case of Cyprus, Int. J. Sustain. Dev. Plan. 11 (2016) 147–159. doi:10.2495/SDP-V11-N2-147-159.
30
ACCEPTED MANUSCRIPT
[10]
[11] [12]
[13]
[14] [15] [16]
[17]
[18]
[19]
[20]
[21]
[22] [23]
[24]
[25]
[26]
[27]
[28]
RI PT
[9]
SC
[8]
M AN U
[7]
TE D
[6]
K. Günçe, D. Misirlisoy, Adaptive reuse of military establishments as museums: Conservation vs. museography, in: WIT Trans. Built Environ., 2014: pp. 125–136. doi:10.2495/DSHF140111. H. Barranha, J.V. Caldas, R.N.N.D. Silva, Translating heritage into museums: two architectural strategies inside Lisbon Castle, J. Cult. Herit. Manag. Sustain. Dev. 7 (2017). doi:10.1108/JCHMSD-05-2016-0033. D. Camuffo, R. Van Grieken, H.-J. Busse, G. Sturaro, A. Valentino, A. Bernardi, N. Blades, D. Shooter, K. Gysels, F. Deutsch, M. Wieser, O. Kim, U. Ulrych, Environmental monitoring in four European museums, Atmos. Environ. 35 (2001) 127–140. doi:10.1016/S1352-2310(01)00088-7. V. Zivkovíc, V. Džikíc, Return to basics—Environmental management for museum collections and historic houses, Energy Build. 95 (2015) 116–123. doi:10.1016/j.enbuild.2014.11.023. K. Fabbri, M. Pretelli, A. Professor, Heritage buildings and historic microclimate without HVAC technology: Malatestiana Library in Cesena, Italy, UNESCO Memory of the World, Energy Build. 76 (2014) 15–31. doi:10.1016/j.enbuild.2014.02.051. V. Belpoliti, G. Bizzarri, P. Boarin, M. Calzolari, P. Davoli, A parametric method to assess the energy performance of historical urban settlements. Evaluation of the current energy performance and simulation of retrofit strategies for an Italian case study, J. Cult. Herit. (2017) 1–13. doi:10.1016/j.culher.2017.08.009. E. Lucchi, Simplified assessment method for environmental and energy quality in museum buildings, Energy Build. 117 (2016) 216–229. doi:10.1016/j.enbuild.2016.02.037. S.P. Corgnati, V. Fabi, M. Filippi, A methodology for microclimatic quality evaluation in museums: application to a temporary exhibit, Build. Environ. 44 (n.d.) 1253–1260. doi:10.1016/j.buildenv.2008.09.012. D. Camuffo, Microclimate for cultural heritage: conservation and restoration of indoor and outdoor monuments, n.d. http://www.sciencedirect.com/science/book/9780444632968 (accessed May 12, 2017). M. Cassar, Environmental management: guidelines for museums and galleries, 1st ed., Routledge, 1994. AHRAE, Thermal Environmental Conditions for Human Occupancy. ANSI/ASHRAE Standard 552013, (2013). ISO, Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Standard 7730, (2005). EN 15251 Indoor environmental input parameters for design and assessment of energy performance of buildings- addressing indoor air quality, thermal environment, lighting and acoustics. CEN, Brussels., Brussels, 2007. K. Gysels, F. Delalieux, F. Deutsch, R. Van Grieken, D. Camuffo, A. Bernardi, G. Sturaro, H.-J. Busse, M. Wieser, Indoor environment and conservation in the Royal Museum of Fine Arts, Antwerp, Belgium, J. Cult. Herit. 5 (2004) 221–230. doi:10.1016/j.culher.2004.02.002. F. Sciurpi, C. Carletti, G. Cellai, L. Pierangioli, Environmental monitoring and microclimatic control strategies in “La Specola” museum of Florence, Energy Build. 95 (2015) 190–201. doi:10.1016/j.enbuild.2014.10.061. R.P. Kramer, Clever climate control for culture: energy efficient indoor climate control strategies for museums respecting collection preservation and thermal comfort of visitors, Eindhoven University of Technology, 2017. V. D’agostino, F.R. d’Ambrosio Alfano, B.I. Palella, G. Riccio, The museum environment: A protocol for evaluation of microclimatic conditions, Energy Build. 95 (2015). doi:10.1016/j.enbuild.2014.11.009. S. Raffler, S. Bichlmair, R. Kilian, Mounting of sensors on surfaces in historic buildings, Energy Build. 95 (2015) 92–97. doi:10.1016/j.enbuild.2014.11.054. J. Ferdyn-Grygierek, Monitoring of indoor air parameters in large museum exhibition halls with and without air-conditioning systems, Build. Environ. 107 (2016) 113–126. doi:10.1016/j.buildenv.2016.07.024. C. Dogan Sahin, T. Coskun, Z.D. Arsan, G. Gökçen Akkurt, Investigation of indoor microclimate of historic libraries for preventive conservation of manuscripts. Case Study: Tire Necip Pa a Library, ˙ Izmir-Turkey, Sustain. Cities Soc. 30 (2017) 66–78. doi:10.1016/j.scs.2016.11.002. M. Andretta, F. Coppola, L. Seccia, Investigation on the interaction between the outdoor environment and the indoor microclimate of a historical library, J. Cult. Herit. 17 (2016) 75–86. doi:10.1016/j.culher.2015.07.002. T. Hu, W. Jia, J. Cao, R. Huang, H. Li, S. Liu, T. Ma, Y. Zhu, Indoor air quality at five site museums of Yangtze River civilization, Atmos. Environ. 123 (2015) 449–454. doi:10.1016/j.atmosenv.2015.10.022. F.-J. García-Diego, M. Zarzo, Microclimate monitoring by multivariate statistical control: The renaissance frescoes of the Cathedral of Valencia (Spain), J. Cult. Herit. 11 (2010) 340–345. doi:10.1016/j.culher.2009.06.002. A. Caratelli, A.M. Siani, G.R. Casale, A. Paravicini, K. Hermann Fiore, D. Camuffo, Stucco panels of Room VI in the Galleria Borghese (Rome): Physical–chemical analysis and microclimate characterization, Energy Build. 61 (2013) 133–139. doi:10.1016/j.enbuild.2013.02.013.
EP
[5]
AC C
636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 691 692 693 694 695 696 697 698 699 700 701 702
31
ACCEPTED MANUSCRIPT
[34]
[35]
[36]
[37] [38]
[39]
[40]
[41]
[42] [43]
[44] [45]
[46]
[47] [48] [49]
[50]
[51] [52]
RI PT
[33]
SC
[32]
M AN U
[31]
TE D
[30]
S.P. Corgnati, M. Filippi, Assessment of thermo-hygrometric quality in museums: Method and infield application to the “Duccio di Buoninsegna” exhibition at Santa Maria della Scala (Siena, Italy), J. Cult. Herit. 11 (2010) 345–349. doi:10.1016/j.culher.2009.05.003. J. Ferdyn-Grygierek, Indoor environment quality in the museum building and its effect on heating and cooling demand, Energy Build. 85 (2014) 32–44. doi:10.1016/j.enbuild.2014.09.014. N.G. Kotler, Museum strategy and marketing: designing missions, building audiences, generating revenue and resources, San Francisco, Calif. : Jossey-Bass Publishers c1998., San Francisco, Calif., 1998. A.L. Pisello, V.L. Castaldo, C. Piselli, F. Cotana, Coupling artworks preservation constraints with visitors’ environmental satisfaction: Results from an indoor microclimate assessment procedure in a historical museum building in central Italy, Indoor Built Environ. 0 (2017) 1–24. doi:10.1177/1420326X17694422. J.-H. Jeong, K.-H. Lee, The physical environment in museums and its effects on visitors’ satisfaction, Build. Environ. 41 (2006) 963–969. doi:10.1016/j.buildenv.2005.04.004. A. Martínez-Molina, P. Boarin, I. Tort-Ausina, J.-L. Vivancos, Post-occupancy evaluation of a historic primary school in Spain: Comparing PMV, TSV and PD for teachers’ and pupils’ thermal comfort, Build. Environ. 117 (2017) 248–259. doi:10.1016/j.buildenv.2017.03.010. A. Martínez-Molina, I. Tort-Ausina, S. Cho, J.-L. Vivancos, Energy efficiency and thermal comfort in historic buildings: A review, Renew. Sustain. Energy Rev. 61 (2016) 70–85. doi:10.1016/j.rser.2016.03.018. H.E. Silva, F.M.A. Henriques, T.A.S. Henriques, G. Coelho, A sequential process to assess and optimize the indoor climate in museums, Build. Environ. 104 (2016) 21–34. doi:10.1016/j.buildenv.2016.04.023. ASHRAE, Thermal Environmental Conditions for Human Occupancy. ASHRAE Standard 55-2004, (2004). M. La Gennusa, G. Lascari, G. Rizzo, G. Scaccianoce, Conflicting needs of the thermal indoor environment of museums: In search of a practical compromise, J. Cult. Herit. 9 (2008) 125–134. doi:10.1016/j.culher.2007.08.003. R.P. Kramer, M.P.E. Maas, M.H.J. Martens, A.W.M. van Schijndel, H.L. Schellen, Energy conservation in museums using different setpoint strategies: A case study for a state-of-the-art museum using building simulations, Appl. Energy. 158 (2015) 446–458. doi:10.1016/j.apenergy.2015.08.044. A.K. Mishra, M.T.H. Derks, L. Kooi, M.G.L.C. Loomans, H.S.M. Kort, Analysing thermal comfort perception of students through the class hour, during heating season, in a university classroom, Build. Environ. 125 (2017) 464–474. doi:10.1016/j.buildenv.2017.09.016. A.K. Mishra, R.P. Kramer, M.G.L.C. Loomans, H.L. Schellen, Development of thermal discernment among visitors: Results from a field study in the Hermitage Amsterdam, Build. Environ. 105 (2016) 40–49. doi:10.1016/j.buildenv.2016.05.026. A. Kotopouleas, M. Nikolopoulou, Evaluation of comfort conditions in airport terminal buildings, Build. Environ. 130 (2018) 162–178. doi:10.1016/j.buildenv.2017.12.031. R. Hay, F. Samuel, K.J. Watson, S. Bradbury, Post-occupancy evaluation in architecture: experiences and perspectives from UK practice, Build. Res. Inf. 0 (2017) 1–13. doi:10.1080/09613218.2017.1314692. W. Preiser, H. Rabinowitz, E. White, Post-Occupancy Evaluation, Van Nostrand Reinhold, New York, 1988. A.L. Pisello, V.L. Castaldo, G. Pignatta, F. Cotana, Integrated numerical and experimental methodology for thermal-energy analysis and optimization of heritage museum buildings, Build. Serv. Engeneering Res. Technol. 37 (2016) 334–354. doi:10.1177/0143624415609910. J. Mundo-Hernández, M.C. Valerdi-Nochebuena, J. Sosa-Oliver, Post-occupancy evaluation of a restored industrial building: A contemporary art and design gallery in Mexico, Front. Archit. Res. 4 (2015) 330–340. doi:dx.doi.org/10.1016/j.foar.2015.09.003. Institute for Veterinary Public Health, World Maps of Köppen-Geiger Climate Classification, (2011). P Ole Fanger, Thermal Comfort: Analysis and applications in environmental engineering, McGrawHill. (1970). G. Paliaga, L.J. Schoen, P.F. Alspach, E. a Arens, R.M. Aynsley, R. Bean, J. Eddy, T.B. Hartman, D. Int-hout, M. a Humphreys, E.E. Khalil, M.P.O. Rourke, P. Simmonds, J.L. Stoops, S.C. Turner, K.W. Cooper, W.F. Walter, D.S. Abramson, C.S. Barnaby, S.J. Emmerich, J.M. Ferguson, R.L. Hall, R.M. Harrold, Thermal Environmental Conditions for Human Occupancy AHSRAE 55, ASHRAE. (2013). doi:ISSN 1041-2336. ISO, Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Standard ISO 7730, Geneva, 2005. ISO 7726 - Ergonomics of the thermal environment -- Instruments for measuring physical quantities, ISO, Geneva, 2012. R.J. de Dear, G.S. Brager, Indoor Environmental Quality (IEQ) Title Developing an adaptive model of thermal comfort and preference, ASHRAE Trans. 104 (1998) 1–18. https://escholarship.org/uc/item/4qq2p9c6 (accessed January 19, 2018).
EP
[29]
AC C
703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 738 739 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769
32
ACCEPTED MANUSCRIPT
RI PT
SC
[56]
M AN U
[55]
TE D
[54]
R. Kramer, L. Schellen, H. Schellen, Adaptive temperature limits for air-conditioned museums in temperate climates, Build. Res. Inf. (2017) 1–12. doi:10.1080/09613218.2017.1327561. M. Rota, S.P. Corgnati, L. Di Corato, The museum in historical buildings: Energy and systems. The project of the Fondazione Musei Senesi, Energy Build. 95 (2015) 138–143. doi:10.1016/j.enbuild.2014.11.008. Green Building Council Italia, GBC Historic Building. Sistema di verifica GBC Historic Building®, Green Building Council Italia, Rovereto, Italy, 2014. P. Boarin, Bridging the gap between environmental sustainability and heritage preservation: towards a certified sustainable conservation, adaptation and retrofitting of historic buildings, in: J. Zuo, L. Daniel, V. Soebarto (Eds.), Fifty Years Later Revisiting Role Archit. Sci. Des. Pract. 50th Int. Conf. Archit. Sci. Assoc. 2016, School of Architecture and Built Environment, The University of Adelaide, Adelaide, Australia, 2016: pp. 675–684. http://anzasca.net/wpcontent/uploads/2016/12/69-1120-675-684.pdf (accessed May 5, 2017).
EP
[53]
AC C
770 771 772 773 774 775 776 777 778 779 780 781 782 783
33
ACCEPTED MANUSCRIPT A Post-Occupancy Evaluation of a museum in a historic reused building is performed.
Quantitative monitoring and qualitative assessment are used for one year.
Customized questionnaires for visitors are developed to assess visitors' thermal comfort.
Artwork conservation, heritage adaptation and indoor environmental quality are considered.
AC C
EP
TE D
M AN U
SC