Behavior of one-way reinforced concrete slabs subjected to fire

Behavior of one-way reinforced concrete slabs subjected to fire

Alexandria Engineering Journal (2013) 52, 749–761 Alexandria University Alexandria Engineering Journal www.elsevier.com/locate/aej www.sciencedirect...

2MB Sizes 3 Downloads 159 Views

Alexandria Engineering Journal (2013) 52, 749–761

Alexandria University

Alexandria Engineering Journal www.elsevier.com/locate/aej www.sciencedirect.com

ORIGINAL ARTICLE

Behavior of one-way reinforced concrete slabs subjected to fire Said M. Allam *, Hazem M.F. Elbakry, Alaa G. Rabeai Structural Eng. Dept., Faculty of Engineering, Alexandria University, Alexandria, Egypt Received 21 August 2013; revised 16 September 2013; accepted 18 September 2013 Available online 17 October 2013

KEYWORDS Cooling; Fire resistance; Finite difference; Heat transfer; Slabs

Abstract A finite difference analysis was performed to investigate the behavior of one-way reinforced concrete slabs exposed to fire. The objective of the study was to investigate the fire resistance and the fire risk after extinguishing the fire. Firstly, the fire resistance was obtained using the ISO834 standard fire without cooling phase. Secondly, the ISO834 parametric fire with cooling phase was applied to study the effect of cooling time. Accordingly, the critical time for cooling was identified and the corresponding failure time was calculated. Moreover, the maximum risk time which is the time between the fire extinguishing and the collapse of slab was obtained. Sixteen oneway reinforced concrete slabs were considered to study the effect of important parameters namely: the concrete cover thickness; the plaster; and the live load ratio. Equations for heat transfer through the slab thickness were used in the fire resistance calculations. Studying the cooling time revealed that the slabs are still prone to collapse although they were cooled before their fire resistance. Moreover, increasing the concrete cover thickness and the presence of plaster led to an increase in the maximum risk time. However, the variation in the live load ratio has almost no effect on such time. ª 2013 Production and hosting by Elsevier B.V. on behalf of Faculty of Engineering, Alexandria University.

1. Introduction Structural fire performance engineering is a recent philosophy of design that has developed recently in structural engineering. Fire safety design can be achieved by active and passive fire protection systems. Active systems are generally self-activated * Corresponding author. Tel.: +20 1112244066. E-mail address: [email protected] (S.M. Allam). Peer review under responsibility of Faculty of Engineering, Alexandria University.

Production and hosting by Elsevier

once the fire is triggered. Such systems include fire detectors, smoke control systems, and sprinklers. However, passive systems are built into the structures such as building codes limitations, fire doors and windows and fire protection materials that prevent or delay the temperature rise in structural elements [1]. Many different fire exposures are used to study the reinforced concrete structure such as standard fire (without cooling phase), parametric and natural fires (with cooling phase) [1– 4]. The parametric and natural fires usually represent actual fires better than the standard fire. The behavior of reinforced concrete slabs under fire loading has been studied by researchers for many decades [5–9]. It is well known that when the temperature increases the slab fire resistance decreases. This is because when concrete is exposed to

1110-0168 ª 2013 Production and hosting by Elsevier B.V. on behalf of Faculty of Engineering, Alexandria University. http://dx.doi.org/10.1016/j.aej.2013.09.004

750 heat, chemical and physical reactions occur such as loss of moisture, dehydration of cement paste and decomposition of the aggregate. Such changes lead to high pore pressures caused by the water evaporation, internal microcracks and damages appear in concrete [10]. Also, the increase in the temperature leads to a decrease in the yield strength of the steel reinforcement. Concrete spalling under high temperatures is a major factor of reducing its fire resistance [11,12]. The spalling is caused by the build-up of pore pressure during heating. High strength concrete is believed to be more susceptible to this pressure build-up because of its low permeability compared to the normal strength concrete. Thus, high strength concrete is known to have less fire resistance than normal strength concrete [13,14]. The behavior of concrete slabs under fire is very sensitive to the stiffness and ends restrain condition. The fire resistance of one-way restrained slabs is generally higher than those for unrestrained slabs because compressive restraint in the surrounding structure decreased the slabs thermal expansion [15–17]. It is well known that the bottom concrete cover has significant influence on the fire resistance of the flexural member, but the lateral concrete cover has a less beneficial effect on the member fire resistance compared to the bottom concrete cover [18]. Codes of practice state that the temperature rise leads to strength degradation in both concrete and steel reinforcement based on the aggregate type and the grade of the steel [19,20]. However, such codes believed that the steel reinforcement temperature played the important role in strength degradation. The Eurocode2-2004 [19] gives profiles for temperature distributions through the slab thickness in the case of slabs or through the cross section in the case of beams and columns based on fire resistance class for the load-bearing criterion for 30, or 60, . . . minutes in standard fire exposure. It gives simple calculation methods for calculating the mechanical behavior namely 500 C isotherm and zone methods. The ACI committee 216 [20] gives fire resistance for the slab based on the relative slab bending capacity which is the ratio of the moment due to applied load to the moment capacity of the section where the cover thickness is based on the aggregate type. The ECP 203-2007 [21] gives the fire resistance for different structural elements, (slabs, beams, and columns) according to their dimensions and the concrete cover thickness. Most of research work found in the literature studied the behavior of reinforced concrete slabs and their fire resistance during exposure to fire. However little research work dealt with the influence of cooling time on the fire resistance of concrete slabs. Such studies considered only the time of cooling start on the fire resistance [5,7,10]. However, up to the knowledge of the authors there is no research work studied the risk of cooling time before the fire resistance. There is a critical time between the time of cooling start and the fire resistance. This critical time leads to failure of the concrete slab if cooled before its fire resistance. This is because the fire starts to decrease (cooled) while the concrete slab core temperature still increasing [22]. This paper presents a finite difference approach [23–25] for tracing the fire response of RC slabs under the standard and parametric ISO834 fire. Several parameters were considered such as concrete cover thickness, presence of plaster at exposed surface, and live load ratio. The scope of this study covers the behavior of simply-supported one way reinforced concrete slabs under fire. The model is verified against experimental and numerical data by comparing the predicted temperatures to the measured ones from Lie and Leir [23]. The model is

S.M. Allam et al. capable of predicting the fire resistance and the influence of cooling before the fire resistance (time). 2. The model The Finite difference method is considered in the current research to study the behavior of reinforced concrete simply supported one-way slabs under fire loading. The model considers the heat transfer through the slab thickness and both concrete and steel reinforcement strength degradation due to exposure to fire. The ISO834 standard fire without and with cooling phase is considered. The model considers three parameters namely: concrete cover, live load ratio, and the plaster thickness at the exposed surface to identify fire resistance. Also, the effect of cooling time before the fire resistance on the possibility of such slabs to collapse is studied and the corresponding failure time could be estimated. Moreover, the maximum risk time is determined. To perform such model the following assumptions are considered:  Plane sections before deformation remain plane after deformation (linear strain).  The concrete tensile strength is neglected.  The concrete slab is under static load.  The effect of spalling, expansion and shrinkage are neglected.  Slab edge restraint is neglected.

2.1. Heat transfer through concrete slab There are generally three modes of heat transfer namely conduction, convection and radiation. The surface of the element exposed to fire is subjected to heat transfer by conduction, convection and radiation. For concrete members, the convection is usually ignored when calculating the exposed surface temperature because convection is responsible for less than 10% of the heat transfer at the exposed surface of the concrete members [8]. On the other hand, convection is usually accounted for when calculating the unexposed surface temperature. The internal heat transfer through concrete members is typically calculated by conduction only [9]. To study the performance of reinforced concrete slab under fire, the distribution of temperature inside the slab has to be known. The assessment of the slab behavior under fire should start by applying the standard fire temperature on the exposed surface, after that prediction of the temperature through the slab is obtained. This prediction is performed using a heat transfer analysis. The heat transfer analysis was performed using finite difference method. In such analysis, the temperature distribution mainly depends on the thermal properties of materials such as thermal conductivity, emissivity, specific heat and convection heat transfer coefficient. 2.1.1. Fire temperature The fire temperature was calculated assuming that the slab was exposed to uniform fire from below (tension side). The fire temperature followed the ISO834 standard fire without cooling phase (phase 1) and the ISO834 parametric fire with cooling phase (phase 2). The time–temperature relationship for phase 1 and phase 2 could be described by the following expressions given by [11] and as shown in Fig. 1:

Behavior of one-way reinforced concrete slabs subjected to fire

751

Phase 1: temperature increasing stage only as: Tf ¼ Ta þ 345log10 ð8t þ 1Þ

ð1Þ

Phase 2: follows Eq. (1) up to the cooling point and after that follows the decreasing temperature stage as: Tf ¼ Th  10:417ðt  th Þ ðth 6 30Þ Tf ¼ Th  4:1673ð3  th =60Þðt  th Þ ð30 < th < 120Þ

ð2Þ ð3Þ

Tf ¼ Th  4:167ðt  th Þ ðth P 120Þ

ð4Þ

where t is the fire exposure time (min); th the time of maximum temperature or cooling phase time (min); Th the maximum temperature (C); Ta the initial temperature (C) and Tf is the fire temperature (C). 2.1.2. Calculation of temperature distribution through concrete slab The calculation of temperature distribution through the concrete slab thickness is calculated based on one dimensional heat transfer as given by Lie and Leir [23]. In such calculation, the cross section of slab is divided into layers. The thickness of each layer is Dx and the number of layers into which the slab is divided is M. Each layer is represented by a point Tm see Fig. 2. The temperature in each layer is assumed to be uniform and equal to that of the representative point. The bottom of the slab is exposed to the fire and the top of the slab can cool in ambient temperature. To calculate the temperature history, a heat transfer equation is written for each layer for the time jDt where j = 0, 1, 2 and Dt is the appropriate time increment. Using these equations, the temperature of each layer can be successively evaluated for any time t = (j + 1) Dt if the temperature at time jDt is known and moisture effect is neglected. To ensure that the error existing in the solution at any instant will not be amplified in subsequent calculations, stability criterion must be satisfied. For a given value of Dx, a limit is set for the maximum value of Dt. For fire-exposed slabs made of concrete the criterion is given as   qCpðminÞ Dx2 ð5Þ Dt 6 2ðkðmaxÞ þ Dxhmax Þ where Dt is the suitable time increment (min); qCp(min) the minimum volumetric specific heat (specific heat · density); Dx the Layer thickness (m); k(max) the maximum thermal conductivity of concrete; and hmax is the maximum value of the coefficient of heat transfer at the fire-exposed surface and is given by: hmax ¼ 4reðTfmax þ 273Þ3

ð6Þ

Figure 2

Heat transfer Model.

where Tfmax is the maximum fire temperature; e the emissivity of the concrete surface = 0.9; and r is the Stefan–Boltzman radiation constant = 5.669 · 108 W/m2 K4. 2.1.2.1. Exposed surface temperature. For calculating the exposed surface temperature at any time step, heat transfer by radiation and conduction was commonly considered. The increase in the exposed surface temperature is calculated from the sum of the temperature rise by radiation and the temperature dropped by conduction. The increase in the exposed surface temperature was calculated by the following equation: ! n Dt 4 4 jþ1 j T1 ¼ T1 þ 2½reef ðTjf þ 273Þ  ðTj1 þ 273Þ  qCjpð1Þ Dx  j  T  Tj2 j ðk1 þ kj2 Þ  1 Dx ð7Þ where T1 is the temperature at the exposed surface, Tf the fire temperature, ef the emissivity of the fire = 1.0, qCp(1) the volumetric specific heat of the exposed surface, and k1, k2 is the thermal conductivity of the exposed surface and above layer of concrete respectively. 2.1.2.2. Interior slab temperature. Heat was transferred through the slab by conduction between layers only. The increase in layer temperature is calculated from the sum of the temperature rise by conduction from previous layer and the temperature drop by conduction from the next layer. The increase in the interior layer temperature was calculated by the following equation: ! Dt jþ1 j Tm ¼ Tm þ ½ðTjm1  Tjm Þðkjm1 þ kjm Þ 2qCjpðmÞ Dx2  ðTjm  Tjmþ1 Þðkjm þ kjmþ1 Þ

Figure 1 phase.

Typical ISO834 fire curve with and without cooling

ð8Þ

2.1.2.3. Unexposed surface temperature. For calculating the unexposed surface temperature at any time steps, heat transfer by radiation, convection and conduction was considered. The increase in the unexposed surface temperature is calculated from the sum of the temperature rise by conduction and the temperature drop by air radiation and convection. The increase in the unexposed surface temperature was calculated by the following equation:

752

S.M. Allam et al.

!  Dt TjM1  TjM j jþ1 j j TM ¼ TM þ ðk  k Þ M1 M Dx qCjpðMÞ Dx 2½ðrehTjM þ 273i4  hTa þ 273i4 Þ þ ðchTjM  Ta i1:25 Þ

o

ð9Þ

where Ta is the ambient temperature and equal to 20 C and c is the convection heat transfer coefficient from horizontal slab surface to air. It generally equals to 2.49 Wm2 K1.25. 2.1.3. Steel temperature Steel reinforcement was not specifically considered in the thermal analysis because it does not significantly influence the temperature distribution [16]. Moreover, measurements at various locations during fire tests showed that the differences in the bar and sections are small [26]. Thus, the steel reinforcement temperature was considered equal to the concrete temperature at the location of the steel reinforcement bars [26]. 2.2. Verification of heat transfer model

experimental data obtained from Lie and Leir [23] as shown in Fig. 3. It was found that the numerical and experimental temperature distributions given by Lie and Leir [23] match well with the proposed model. 2.3. Material properties 2.3.1. Thermal properties The steel thermal properties were neglected, however, the steel reinforcement temperature was considered equal to the concrete temperature around the steel. Also, the concrete slab was assumed to be made of siliceous aggregate. The siliceous aggregate thermal properties were obtained from Eurocode22004 [19]. Such thermal properties are:  The concrete density was 2400 kg/m3.  The thermal conductivity was calculated using the following equations:

The numerical and experimental data given by Lie and Leir [23] were used to verify the accuracy of the heat transfer model. The slab thickness was 100 mm and the slab temperature distributions were considered as given from Eqs. (5)–(9). The aggregate used was of siliceous type and the slab was exposed to ASTM E119 fire. The ASTM E119 fire used is given by the following expressions:

T k ¼ 1:36  0:136 100  2 T þ 0:0057 W=mK for 20  C 6 T 6 1200  C 100

Tf ¼ Ta þ 0:555½1044 tanhð0:00023413tÞ 498:2 tanhð0:00027044tÞ þ 1286 tanhð0:002475tÞ For t < 7200 s

ð10Þ

Cp ¼ 900 J=kg K for 20 C 6 T 6 100  C

Tf ¼ 927 þ 0:011574t For t P 7200 s

ð11Þ

 The specific heat may be determined from the following:

Cp ¼ 900 þ

The high fire emissivity value was (e = 1). The concrete slab thermal properties were considered as given by Lie and Leir data [23]. The slab was divided into 4 layers. Using the stability criterion given by Eq. (5), it was found that the maximum time increment was 30 s to check the slab fire resistance up to three hours. The results were compared with numerical and

ð12Þ

T J=kg K for 100  C < T 6 200  C 100

Cp ¼ 1000 þ

T  200 J=kg K for 200  C < T 6 400  C 2

Cp ¼ 1100 J=kg K for 400  C < T 6 1200  C

ð13Þ ð14Þ ð15Þ ð16Þ

 The emissivity of the surface was 0.9.

2.3.2. Mechanical properties The concrete slab was assumed to have a characteristic compressive strength of 25 N/m2 and the reinforcing steel was assumed to have yield stress of 360 N/m2. The variation of concrete strength at elevated temperature was accounted for by considering a reduction factor for siliceous aggregate concrete kc which was given by Eurocode2-2004 [19] and defined as follows: kc ¼ 1 20  C 6 T 6 100  C kc ¼ 0:95  0:05

Figure 3 Temperature distributions through exposed surface, mid depth and unexposed surface.

T  200 100

100  C 6 T 6 200  C

ð17Þ ð18Þ

kc ¼ 0:75  0:2

T  400 200

200  C 6 T 6 400  C

ð19Þ

kc ¼ 0:15  0:6

T  800 400

400  C 6 T 6 800  C

ð20Þ

Behavior of one-way reinforced concrete slabs subjected to fire kc ¼ 0:08  0:07

T  900 100

kc ¼ 0:04  0:04

T  1000 100

900  C 6 T 6 1000  C

ð22Þ

kc ¼ 0:01  0:03

T  1100 100

1000  C 6 T 6 1100  C

ð23Þ

kc ¼ 0:1

1200  T 100

800  C 6 T 6 900  C

1100  C 6 T 6 1200  C

ð21Þ

ð24Þ

Also, Eurocode2-2004 [19] proposed a steel strength reduction factor with the temperature increase. The variation of the reduction factor for the tensile reinforcement with es,fi > 2% is defined as 



ks ¼ 1 20 C 6 T 6 400 C ks ¼ 0:78  0:22

T  500 200

T  600 ks ¼ 0:47  0:31 100

400  C 6 T 6 500  C 







500 C 6 T 6 600 C

T  700 ks ¼ 0:23  0:24 100

600 C 6 T 6 700 C

T  800 100

700  C 6 T 6 800 C

ks ¼ 0:11  0:12 ks ¼ 0:11

1200  T 400

753 and concrete according to Eurocode2-2004 [19]. The steel reinforcement temperature increases rapidly as the fire temperature increases because the steel is located at the lower part of slab section. The steel strength decreases with the increase in the temperature which lead to a decrease in the compression force. The compression block was divided into layers to study the variation in the stress block height with temperature. The concrete and steel strength reductions were calculated using the layer temperature shown in Fig. 4. The height of the stress block is calculated using the equilibrium equation between the compression force given by concrete and the tensile force given by steel reinforcement. The equation of equilibrium can be written as: C1 þ C2 þ C3 þ . . . þ Cn þ    þ CN ¼ Ts

ð25Þ

where

ð26Þ

Cn ¼

0:67fcu kcn 0:5DX 1:5

CN ¼

0:67fcu kcN a0 1:5

ð27Þ

Ts ¼ ð28Þ

A s ks f y 1:15

ð31Þ

ð32Þ

a ¼ ð0:5DXÞðN  1Þ þ a0 

ð29Þ

The moment capacity of the slab section is then calculated as:

800  C 6 T 6 1200  C

ð30Þ

2.4. Fire resistance of slabs The slab was designed according to the Egyptian code at ambient temperature with various concrete cover. The temperature distribution through concrete slab thickness obtained from the thermal analysis was used as an input to study the material properties at elevated temperatures. The temperature distribution was used to calculate the strength reduction in the steel

Figure 4

MþveðfireÞ ¼ Ts ðd  a=2Þ

ð33Þ

where kcn is the concrete strength reduction factor at nth layer, fcu the compressive strength, As the area of steel, ks the reinforcement steel strength reduction factor, fy the steel yield strength; Ts the tensile force, a the total height of compression stress block, and a0 is the part of last layer contribute to the compression stress block. For a given slab provided with flexural reinforcement and subjected to ISO834 Standard fire using heat transfer equations and both of Eqs. (31)-(33), the moment capacity degradation with time can be obtained as shown in Fig. 5. Once the

Heat transfer model and stress distribution.

754

S.M. Allam et al.

moment capacity of the slab subjected to fire degrades to a value equal to the applied moment, the slab fails and the time corresponding to this moment capacity is the fire resistance. 3. Slab geometry, loads, design and parametric study The study was conducted on sixteen simply supported one-way reinforced concrete slabs of span 3.0 m and thickness of 120 mm. The live load considered was 10 kN/m2 and 6 kN/m2 representing full live load (LL) and 60% of live load (0.6 LL), respectively. Four concrete cover thicknesses were considered namely; 15, 20, 25, 30 mm. According to the ECP 203-2007 design code and based on fcu = 25 N/mm2, fy = 360 N/mm2, and under full live load, the required areas of steel reinforcement were 850, 911.8, 972 and 1059.9 mm2 respectively. Also, the presence of 20 mm plaster thickness at the exposed surface was considered. Fig. 6 and Table 1 show the combinations of the studied parameters. Based on the stability criterion given by Eq. (5), it was found that dividing the slab thickness into a number of layers greater than 16 would be practically acceptable [22]. The suitable number of layers in the current parametric study was 22 layers which simplifies the calculation of temperature at the location of the steel reinforcement. The heat transfer through the concrete slab without plaster was calculated based on 120 mm slab thickness and the layer thickness was 5.5 mm. It is to be noted that the thermal properties of

plaster was considered similar to those of concrete material. Thus, the heat transfer through concrete slab with plaster was calculated based on 140 mm overall thickness and the layer thickness was 6.4 mm. Fig. 6 shows the slab layers for both cases. Moreover, the stability criterion given by Eq. (5) was used to find the suitable time increment. It was found that the suitable time increment is 5 s to check the fire resistance for eight hours for all concrete slab cases. 4. Fire resistance of slab (phase 1) Figs. 7 and 8 show the temperature distribution for exposed and unexposed surfaces of concrete slabs as well as steel temperature for different concrete cover thickness in the case of slabs without plastering and with plastering respectively. It is clear from the figures that the temperature on the exposed surface increased rapidly during the initial stages however temperature on the unexposed surface rises after the first hour. Figs. 9 and 10 show the relationships between moment capacity degradation and time in the case of slabs without plastering and with plastering respectively. Fig. 11 shows the variation of fire resistance with different concrete cover thickness. Fig. 12 shows the effect of the presence of plastering on temperature distribution of concrete slab surfaces. Figs. 13 and 14 show the effect of the presence of plastering on the moment capacity degradation for the cases of 30 mm and 15 mm concrete cover respectively. Fig. 15 shows the effect of the live load ratio on the moment capacity degradation for the cases of 30 mm and 15 mm concrete cover. Table 2 gives the calculated fire resistance for the sixteen studied slabs. 4.1. Effect of concrete cover thickness

Figure 5

Typical moment capacity degradation with time.

Figure 6

It was found that the concrete cover thickness mainly affect the temperature of the steel reinforcement. The steel reinforcement in a slab having 30 mm concrete cover was away from exposed surface than that in other slabs having less concrete cover thickness. Therefore, as the concrete cover thickness increased the steel reinforcement temperature decreased. Such concrete cover protected the steel reinforcement from rising temperature as shown in Figs. 7 and 8. Fig. 11 shows the variation

Concrete slab layers in case of with and without plaster.

Behavior of one-way reinforced concrete slabs subjected to fire Table 1

755

Study parameters.

Slab

Plaster (mm)

Live load ratio

Cover (mm)

S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 S14 S15 S16

None None None None None None None None 20 20 20 20 20 20 20 20

0.6L.L 0.6L.L 0.6L.L 0.6L.L L.L L.L L.L L.L 0.6L.L 0.6L.L 0.6L.L 0.6L.L L.L L.L L.L L.L

15 20 25 30 15 20 25 30 15 20 25 30 15 20 25 30

Figure 7 Temperature distribution for concrete slab surfaces and steel without plaster).

Figure 9 Moment capacity degradation for different concrete cover (without plaster).

increased. Furthermore, examining Table 2 along with Fig. 11, the following can be observed: (i) for slabs without plaster in the case of live load ratio 0.6, increasing the concrete cover thickness from 15 to 30 mm resulted in an increase in the fire resistance from 65.37 to 143.75 min which represents an increase of 120%. However for similar concrete slabs but subjected to full live load, increasing the concrete cover thickness from 15 to 30 mm resulted in an increase in the fire resistance from 51 to 113.25 min which represents an increase of 122%; (ii) for slabs having 20 mm plaster and in the case of live load ratio 0.6 it was observed that increasing the concrete cover thickness from 15 to 30 mm resulted in an increase in the fire resistance from 171.62 to 289.75 min which represents an increase of 69%. However for similar concrete slabs but subjected to full live load increasing the concrete cover thickness from 15 to 30 mm resulted in an increase in the fire resistance from 136 to 227.25 min which represents an increase of 67%. It can be concluded herein that the concrete cover thickness is one of the most important parameters that affects the fire resistance. Increasing the concrete cover thickness led to almost linear increase in the fire resistance. However, such increase in the fire resistance for slabs without plaster was greater than that in the case of slabs having 20 mm plaster. Moreover, the percentage of increase in the fire resistance as a result of increasing the concrete cover thickness is almost not influenced by the variation in the live load ratio. 4.2. Effect of plaster

Figure 8 Temperature distribution for concrete slab surfaces and steel (with plaster).

in the fire resistance for slabs having different concrete cover thicknesses. It is clear from the table and the figure that generally as the concrete cover thickness increased the fire resistance

The effect of the presence of plaster on the temperature distribution was studied by considering the case of no plaster and 20 mm thickness of plaster. It was observed from the temperature distribution through concrete slab that the exposed surface, unexposed surface and steel reinforcement temperature in case of 20 mm plaster thickness were lower than those of the slabs without plaster. This is because the plaster played a role similar to that of the concrete cover in protecting the steel reinforcement. Such effect was also sounded at the unexposed surface but with less significant difference, as shown in Figs. 7, 8 and 12. The presence of plaster increased the fire resistance of the concrete slab. Fig. 13 shows that the fire resistance of reinforced concrete slab for case of 0.6 live load, with concrete cover 30 mm and without plaster (slab S4) was 143.75 min,

756

S.M. Allam et al.

Figure 10

Moment capacity degradation for different concrete cover (with plaster).

Fire resistance (min)

350 300 250 200 150 100 50 0 10

15

20

25

30

35

Concrete cover thickness (mm) 0.6L.L-no plaster 0.6L.L-20mm plaster

full L.L-no plaster full L.L-20mm plaster

Figure 11 Variation of concrete slabs fire resistance with different concrete cover thickness.

Figure 13 Effect of presence of plastering on moment capacity degradation of slabs with 30 mm concrete cover.

Figure 12 Effect of presence of plastering on temperature distribution of concrete slab surfaces.

Figure 14 Effect of presence of plastering on the moment capacity degradation of slabs with 15 mm concrete cover.

however, for similar concrete slab but with 20 mm plaster (slab S12) the fire resistance was 289.70 min. Fig. 14 shows that the fire resistance of the reinforced concrete slab for case of 0.6 live

load, with concrete cover 15 mm and without plaster (slab S1) was 65.37 min However, for similar concrete slab but with 20 mm plaster (slab S9) the fire resistance was 171.62 min.

Behavior of one-way reinforced concrete slabs subjected to fire

Figure 15 Effect of live load ratio on the moment capacity degradation of slabs with concrete covet 15 and 30 mm.

Table 2 also shows the effect of plaster on the fire resistance of concrete slabs for different concrete cover values and live load ratios. For slabs subjected to 0.6 live load it was observed that the presence of plaster increased the fire resistance by 106 min which represents an increase of 162% in the case of 15 mm cover and by 146 min which represents an increase of 102% in the case of 30 mm cover. However, for slabs subjected to full live load, it was observed that the presence of plaster increased the fire resistance by 85 min which represents an increase of 167% in the case of 15 mm cover and by 114 min which represents an increase of 101% in the case of 30 mm cover. It can be concluded that the effect of the plaster is more pronounced for slabs with thin concrete cover than slabs with thick concrete cover. The reason for that is attributed to the ratio of the plaster thickness to the concrete cover thickness which varied from 133% in the case of 15 mm cover to 67% in the case of 30 mm cover. 4.3. Effect of live load ratio Two live load ratios were considered in this study namely; 0.6 and 1.0 representing 60% and 100% of the LL. Fig. 15 and Table 2 show the effect of live load ratio on the fire resistance of concrete slabs for different concrete cover values and plaster cases. It is clear from the table that the fire resistance of slabs having 30 mm concrete cover and without plaster was 143.75 Table 2

757 and 113.2 min under live load ratios of 0.6 and 1.0 respectively. However, the fire resistance of slabs with 15 mm concrete cover and without plaster was 65.37 and 51 min under live load ratios of 0.6 and 1.0 respectively. For slabs without plaster, it was observed that increasing the live load ratio from 0.6 to 1.0 decreased the fire resistance by 14 min which represents a decrease of 28% in the case of 15 mm cover and by 31 min which represents a decrease of 28% in the case of 30 mm cover. However, for slabs having 20 mm plaster, it was observed that increasing the live load ratio from 0.6 to 1.0 decreased the fire resistance by 36 min which represents a decrease of 27% in the case of 15 mm cover and by 62 min which represents a decrease of 27% in the case of 30 mm cover. Thus, increasing the live load ratio lead to a decrease in the fire resistance of the concrete slabs. It can be concluded that the live load ratio have a significant effect on the fire resistance of slabs. As the live load ratio increased, the fire resistance decreased and such decrease is almost constant regardless of the cover thickness value and the presence of plaster. 5. Study of cooling time (phase 2) The study of cooling phase aims to investigate the effect of starting cooling before the fire resistance with main objective to detect the critical time of cooling and the maximum risk time. Such critical time is the minimum time at which if the slab is cooled at that time or after and even such time is still less than the fire resistance of slab, there is still a possibility for such slab to fail. The maximum risk time is the time span between the critical time of cooling and the corresponding expected failure time. The importance of finding the maximum risk time is that such time is important for staying observant for possible impending failure after the start of the cooling phase. To achieve that, the ISO834 parametric fire with cooling phase was used (phase 2). To detect the critical time, three different starting times for cooling before fire resistance were used within a process of trial and error. To illustrate such process, slab S1 is considered as an example. The fire resistance of slab S1 is 65.37 min. Three arbitrary times of 2, 4 and 6 min before the fire resistance were considered. It means that cooling (decaying) starts at 63.37, 61.37 and 59.37 min. Using heat transfer equations the distributions of the temperature for

Fire resistance of studied slabs.

Slab

Plaster (mm)

Live load ratio

Cover (mm)

Fire resistance (min)

S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 S14 S15 S16

No No No No No No No No 20 20 20 20 20. 20 20 20

0.6L.L 0.6L.L 0.6L.L 0.6L.L L.L L.L L.L L.L 0.6L.L 0.6L.L 0.6L.L 0.6L.L L.L L.L L.L L.L

15 20 25 30 15 20 25 30 15 20 25 30 15 20 25 30

65.37 87.75 114.25 143.75 51.00 68.62 89.62 113.25 171.62 206.75 244.50 289.75 136.00 164.12 193.37 227.25

758

S.M. Allam et al. 5.1.2. Second step

concrete surfaces and steel were obtained at those times. Fig. 16 shows such distributions including mid-depth position of slab at 63.37 min. It is clear from the figure that, at a particular time; the temperature of the exposed surface became higher than the fire temperature. Also, it could be noted that as the fire temperature continued to drop, the mid-depth temperature became higher than the exposed surface temperature. Also, it is noted that the start of temperature drop, due to fire cooling phase, at any concrete depth was lagging behind the start of the fire cooling phase. It means that the maximum temperature inside the concrete slab did not take place at the same time of the maximum temperature of the fire. Using thermal analysis the strength degradation in the steel and concrete can be obtained. When the reinforced concrete slab exposed to fire with decay phase, the steel strength decreased with the increase in the temperature this lead to a decrease in the tension force and consequently the compression force. Therefore, the stress block height began to decrease with the increase in temperature but at a particular time increment in cooling phase stage the stress block height returned to increase. This lead to a decrease in the flexural strength of the slab section up to a certain time and then the flexural strength of slab started to increase again.

Using linear interpolation along with the applied moment corresponding to 0.6 LL which is 11.68 kN m, the critical time for cooling is obtained from the intersection which is 59.99 min as given in Fig. 18. Now such time is called the critical time for cooling the slab S1. Also, the critical net time is then defined as the difference between the critical time for cooling and fire resistance of the slab, i.e., the critical net time is 5.31 min. If the slab is cooled before such time it will not be collapsed however, if it is cooled after that time it will collapse. 5.1.3. Third step Now if the slab is cooled at the critical time 59.99 min the slab is predicted to collapse and the corresponding failure time can be calculated. The failure time corresponding to starting cooling of 63.3 and 61.3 min is 65.7 and 67.1 min as obtained from Fig. 17. Using linear extrapolation as shown in Fig. 19 the failure time corresponding to the critical time of cooling is obtained as 68.01 min. The maximum risk time is then calculated as the time span between the critical time for cooling and the expected failure time which is 8.02 min. 5.2. Effect of studied parameters on the maximum risk time

5.1. Critical time for cooling and maximum risk time

The maximum risk time is the maximum time span between the critical time of cooling and the collapse of slab. The concrete slabs are still prone to collapse even when, they were extinguished before their design fire resistance. For example; the fire resistance for slab S1 was 65.3 min, however, it was still subjected to failure if it was extinguished 5.3 min before its fire resistance (critical decay phase starting at 59.99 min), and the expected failure at 68.01 min. Table 3 gives the fire resistance, the critical time for cooling, critical net time, failure time corresponding to critical cooling time and the maximum risk time.

The following are the steps to find the critical time for cooling and the maximum risk time: 5.1.1. First step The moment capacity degradation under fire using decay phase starting at 63.3, 61.3 and 59.3 min was obtained as given in Fig. 17. It is shown from the figure that the applied moment corresponding to 0.6 LL is 11.68 kN m. It is clear from the figure that the concrete slab collapsed under fire with decay phase starting at 63.3 and 61.3 min, but the concrete slab did not collapse under fire with decay phase at 59.3 min. Also, the moment capacity of the section showed more degradation for a certain time after cooling time before ascending. This is attributed to the increase in the temperature inside the section just after cooling time. The minimum moment capacities of the section corresponding to time 61.3 and 59.3 min are 11.4 and 11.82 kN m respectively as given from Fig. 17.

5.2.1. Effect of concrete cover thickness on the maximum risk time Table 3 shows the variation of maximum risk time corresponding to different concrete cover thickness for all cases. It is clear from the table that, in general, as the concrete cover thickness increased the maximum risk time increased. Also, examining

1100 1000

temperature oC

900 800 700 600 500 400 300 200 100 0 0

50

100

150

200

250

300

350

400

450

500

550

time (min)

Figure 16

exposed surface

Mid depth (60mm)

ISO 834 fire

steel temperature

unexposed surface

Temperature distributions through concrete slab S1 at 63.3 min decay phase time.

Behavior of one-way reinforced concrete slabs subjected to fire

759

30

Moment capacity (KN.m)

28 26 24 22 20 18 16 14 12 10 8 6 0

10

20

30

40

50

60

70

80

90

100

110

time (min) moment with decay at 63.3min

moment with decay at 61.3min

moment with decay at 59.3min

Moment degradation of Slab S1 with cooling phase at 63.3, 61.3 and 59.3 min.

12 11.82

11.75

D.L+0.6L.L =11.68

11.5 59.99min

Minimum moment (KN.m)

Figure 17

moment with D.L+0.6L.L

11.25

11.4

11 59

59.5

60

60.5

61

61.5

decay phase time (min) min moment at 61.3 and 59.3min decay phase moment with D.L+0.6L.L

Figure 18

Finding the critical time (min).

Figure 19 Finding the failure time corresponding to critical time for cooling.

Table 3 the following can be detected: (i) for slabs without plaster and subjected to live load ratio of 0.6, it was observed that increasing the concrete cover thickness from 15 to 30 mm increased the maximum risk time from 8.02 to 26.86 min which represents an increase of 235%. However, for similar concrete slabs but subjected to full live load, increasing the concrete cover thickness from 15 to 30 mm increased the maximum risk time from 8.02 to 24.90 min which represents an increase of

210%; (ii) for slabs had 20 mm plaster and subjected to live load ratio of 0.6, it was observed that increasing the concrete cover thickness from 15 to 30 mm increased the maximum risk time from 32.05 to 45.2 min which represents an increase of 41%. However for similar concrete slabs but subjected to full live load, increasing the concrete cover thickness from 15 to 30 mm increased the maximum risk time from 31.8 to 48.72 min which represents an increase of 53%. It can be concluded herein that the concrete cover thickness had significant effect on the maximum risk time. Increasing the concrete cover thickness led to almost linear increase in the maximum risk time. However, such increase as a percentage of increase in the maximum risk time for slabs with no plaster was greater than that for slabs with 20 mm plaster. 5.2.2. Effect of plaster on the maximum risk time Table 3 shows the effect of the presence of the plaster on the maximum risk time of slabs. It is clear from the table that the presence of plaster increased the maximum risk time of the concrete slabs. The maximum risk time of reinforced concrete slab for the case of 0.6 live load, with concrete cover 30 mm and without plaster as given by slab S4, was 26.86 min, however, for similar concrete slab but, with 20 mm plaster as given by slab S12, the maximum risk time was 45.21 min. Table 3 shows also that the maximum risk time of the reinforced concrete slab for the case of 0.6 live load, with concrete cover 15 mm and without plaster as given by slab S1, was 8.02 min, however, for similar concrete slab but, with 20 mm plaster as given by slab S9, the maximum risk time was 32.05 min. Moreover, Table 3 shows the effect of plaster on the variation of maximum risk time of the concrete slabs for different concrete cover values and live load ratios. For slabs subjected to 0.6 live load, it was observed that the presence of the plaster increased the maximum risk time by 24.03 min which represents an increase of 300%, in the case of 15 mm cover and by 18.35 min which represents an increase of 68%, in the case of 30 mm cover. However, for slabs subjected to full live load, it was observed that the presence of plaster increased the maximum risk time by 23.78 min which represents an increase of 296%, in the case of 15 mm cover and by 23.82 min which represents an increase of 95%, in the case of 30 mm cover. It can be concluded that the presence of plaster

760

S.M. Allam et al.

Table 3

Results of cooling study.

Slab

Fire resistance (min)

Critical time for cooling (decaying)(min)

Critical net time (min)

Failure time corresponding to critical cooling time (min)

Maximum risk ime (min)

S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 S14 S15 S16

65.37 87.75 114.25 143.75 51.00 68.62 89.62 113.25 171.62 206.75 244.50 289.75 136.00 164.12 193.37 227.25

59.99 79.29 100.37 123.20 45.20 59.90 76.50 94.95 147.00 178.4 212.38 255.29 110.80 131.60 156.40 186.80

5.38 8.46 13.88 20.55 5.80 8.72 13.12 18.30 24.62 28.35 32.12 34.46 25.20 32.52 36.97 40.45

68.01 93.35 119.18 150.06 53.22 73.40 95.26 119.90 179.05 215.15 253.75 300.50 142.63 171.59 201.14 235.52

8.02 13.96 18.82 26.86 8.02 13.50 18.67 24.90 32.05 36.75 41.34 45.21 31.80 39.99 44.74 48.72

increased the maximum risk time, however, the effect of the plaster decreased with increasing the concrete cover thickness. 5.2.3. Effect of live load ratio on the maximum risk time Table 3 shows the effect of live load ratio on the maximum risk time of concrete slabs for different concrete cover values and plaster cases. It is clear from the table that the maximum risk time of slabs having 30 mm concrete cover and without plaster was 26.86 and 24.9 min as given by S4 and S8 under live load ratios of 0.6 and 1.0 respectively. However, the maximum risk time of slabs having 15 mm concrete cover and without plaster was 8.20 and 8.02 min as given by S1 and S5 under live load ratios of 0.6 and 1.0 respectively. Also, Table 3 shows that the maximum risk time of slabs having 30 mm concrete cover and having plaster was 45.21 and 48.72 min as given by S12 and S16 under live load ratios of 0.6 and 1.0 respectively. However, the maximum risk time of slabs having 15 mm concrete cover and with plaster was 32.05 and 31.8 min as given by S9 and S13 under live load ratios of 0.6 and 1.0 respectively. It can be concluded that the variation of live load ratio has almost no effect on the maximum risk time values. The variation of live load ratio from 0.6 to 1.0 gives almost the same maximum risk time. 6. Conclusions The behavior of one-way reinforced concrete slabs exposed to fire was investigated using a numerical finite difference analysis. Firstly, the fire resistance of slabs was obtained using the ISO834 standard fire without cooling phase. Secondly, the ISO834 parametric fire with cooling phase was applied to study the effect of cooling time. The critical time for cooling was identified and the corresponding expected failure time was calculated. The maximum risk time was obtained. Sixteen simply supported one-way reinforced concrete slab models were considered to study three different parameters namely: the concrete cover thickness; the presence of plaster at the exposed surface; and the live load ratio. Heat transfer equations through the concrete slab thickness were considered for the fire resistance calculations. From the current study, the following conclusions could be drawn:

 The steel reinforcement temperature played an important role in the strength degradation of the slabs. As the steel reinforcement temperature increased, the yield strength of the steel reinforcement decreased and accordingly the capacity of the section decreased.  The concrete cover thickness had a significant effect on the fire resistance. Increasing the concrete cover thickness led to almost a linear increase in the fire resistance. However, such increase in the fire resistance for slabs with no plaster was greater than that for slabs with 20 mm plaster. Increasing the concrete cover thickness from 15 to 30 mm resulted in an increase in the fire resistance with 120% in the case of no plaster and 69% in the case of plaster with thickness 20 mm as observed in the case of 0.6 live load. Moreover, the percentage of increase in the fire resistance with the increase in the concrete cover thickness is almost not affected by the variation in the live load ratio.  The presence of plaster significantly increased the fire resistance of slabs. This is because the plaster played a role similar to that of the concrete cover in protecting the steel reinforcement. However, the effect of the presence of the plaster is more pronounced for slabs with thin concrete cover compared to slabs with thick concrete cover. The presence of plaster increased the fire resistance by 162% in the case of 15 mm cover and by 102% in the case of 30 mm cover as observed in the case of 0.6 live load.  The live load ratio has a significant effect on the fire resistance of slabs. As the live load ratio increased, the fire resistance decreased and such decrease is almost constant in all cases with about 28%.  Slabs are still prone to collapse even if they were cooled before their fire resistance. As the fire temperature continued to drop, the mid depth temperature became higher than the exposed surface temperature. The start of temperature drop, due to fire cooling phase, at any concrete depth was lagging behind the start of the fire cooling phase. Accordingly, the maximum temperature inside the concrete slab did not take place at the same time of the maximum temperature of the fire.

Behavior of one-way reinforced concrete slabs subjected to fire  The concrete cover thickness had significant effect on the maximum risk time. Increasing the concrete cover thickness led to almost a linear increase in the maximum risk time. However, such increase in the maximum risk time for slabs with no plaster was greater than that for slabs with 20 mm plaster. Increasing the concrete cover thickness from 15 to 30 mm, in the case of no plaster, increased the maximum risk time from 8.02 to 26.86 min which represents an increase of 235%, however, in the case of plaster increased the maximum risk time from 32.05 to 45.2 min which represents an increase of 41% as observed in the case of 0.6 live load.  The presence of plaster significantly increased the maximum risk time. However, such increase is higher in the case of small concrete cover than that in the case of large concrete cover. The plaster increased the maximum risk time by 300%, in the case of 15 mm cover and by 68% in the case of 30 mm cover as observed in the case of 0.6 live load.  The variation in the live load ratio has almost no effect on the maximum risk time values. The variation in the live load ratio from 0.6 to 1.0 gives almost the same maximum risk time.

References [1] CIB W014 Fire Work Item 99-1. Rational fire safety engineering approach to fire resistance in buildings; 2001. [2] R. Feasey, A. Buchanan, Post-flashover fires for structural design, Fire Safety Journal 37 (2002) 83–105. [3] T.T. Lie, Fire temperature-time relations, National Research Council Canada, Appeared in the SFPE Handbook of Fire Protection Engineering, 1988, Section 3 Chapter 5, IRC PAPER NO. 1579, pp. 3-81–3-87. [4] O. Pettersson, S.E. Magnusson, J. Thor, Fire Engineering Design of Steel Structures, Swedish Institute of Steel Construction, Bulletin 52, 1976, Publication 50, pp. 1–232. [5] P.J. Moss, R.P. Dhakal, G. Wang, A.H. Buchanan, The fire behaviour of multi-bay, two-way reinforced concrete slabs, Engineering Structures 30 (2008) 3566–3573. [6] A. Huang, The behavior of reinforced concrete slabs in fire, Fire Safety Journal 45 (2010) 271–282. [7] A. Levesque, Fire Performance of Reinforced Concrete Slabs, Degree of Master of Science in Civil Engineering, May 2006. [8] C.G. Bailey, W.S. Toh, Small-scale concrete slab tests at ambient and elevated temperatures, Engineering Structures 29 (2007) 2775–2791. [9] C.G. Bailey, W.S. Toh, Behaviour of concrete floor slabs at ambient and elevated temperatures, Fire Safety Journal 42 (2007) 425–436.

761 [10] S. Bratina, M. Saje, I. Planinc, The effects of different strain contributions on the response of RC beams in fire, Engineering Structures 29 (2007) 418–430. [11] G.A. Khoury, Y. Anderberg, Concrete spalling review, Fire Safety Design – Report Submitted to Swedish National Road Administration, June 2000, pp. 1–60. [12] F. Ali, A. Nadjai, A. Abu-Tair, Explosive spalling of normal strength concrete slabs subjected to severe fire, Materials and Structures 44 (2011) 943–956. [13] E.G. Choi, Y.S. Shin, The structural behavior and simplified thermal analysis of normal-strength and high-strength concrete beams under fire, Engineering Structures 33 (2011) 1123–1132. [14] B. Wu, Z. Hong, G. Tang, C. Wang, Fire resistance of reinforced concrete columns with square cross section, Advanced Structural Engineering 10 (4) (2007) 353–369. [15] L. Lim, A. Buchanan, P. Moss, J. Franssen, Computer modeling of restrained reinforced concrete slabs in fire conditions, Journal of Structural Engineering, ASCE 130 (12) (2004) 1964–1971. [16] M.B. Dwaikat, V.K.R. Kodur, A numerical approach for modeling the fire induced restraint effects in reinforced concrete beams, Fire Safety Journal 43 (2008) 291–307. [17] M.B. Dwaikat, V.K.R. Kodur, Response of restrained concrete beams under design fire exposure, Journal of Structural Engineering ASCE 135 (11) (2009) 1408–1417. [18] X. Shi, T. Tan, K. Tan, Z. Guo, Influence of concrete cover on fire resistance of reinforced concrete flexural members, Journal of Structural Engineering, ASCE 130 (8) (2004) 1225–1232. [19] Eurocode 2: Design of Concrete Structures – Part 1 General rulesStructural fire design. The European Standard EN1992-1-2:2004. [20] ACI Committee 216, Guide for Determining the Fire Endurance of Concrete Elements (ACI 216), American Concrete Institute, Farmington Hills, Mich., USA, 1994. [21] The Egyptian Code for Design and Construction of Reinforced Concrete Structures, ECP 203–2007, Ministry of Housing, Egypt. [22] A.G. Rabeai, The Behavior of One-way Concrete Slabs Subjected to Fire Condition, Scientific Report – Master of Engineering in Structural Engineering, Structural Engineering Department, Alexandria University, Alexandria, Egypt (in preparation). [23] T.T. Lie, G. Leir, Factors affecting temperature of fire-exposed concrete slabs, National Research Council Canada – Reprinted from Fire and Materials 3 (2) (1979) 74–79. [24] T.T. Lie, T.D. Lin, Fire Performance of Reinforced Concrete Columns, National Research Council Canada Fire – Reprinted from Fire Safety; Science and Engineering, ASTM, STP 882, 1985, (DBR Paper No. 1352), pp. 176–205. [25] M.A. Sultan, T.T. Lie, J. Lin, Heat Transfer Analysis for FireExposed Concrete Slab-Beam Assemblies, National Research Council Canada, 1991 Internal, Report No. 605. [26] T.T. Lie, R.J. Irwin, Method to calculate the fire resistance of reinforced concrete columns with rectangular cross section, ACI Structural Journal 90 (1) (1993) 52–60.