Centrifugal Pump Data Sheet

Centrifugal Pump Data Sheet

Appendix 2 Centrifugal PumpData Sheet Date By NORD ENGINEERINGINC. CENTRIFUGAL No. A 02/10/97 UW HOUSTON,TEXAS PUMPS REVISION Issue For Bid Job #: ...

66KB Sizes 7 Downloads 441 Views

Appendix 2

Centrifugal PumpData Sheet Date By NORD ENGINEERINGINC. CENTRIFUGAL No. A 02/10/97 UW HOUSTON,TEXAS PUMPS

REVISION Issue For Bid

Job #: 97012-1 Spec #: 102.2 Date: 2/10/97 By: UW Rev: A Appv'd: KG

Client: SundChemical Inc Project: Auburn Plant Location: Florida Panhandle Service: Diesel Fuel Transfer Pumps

Equip No. P-101, P-102, P-103

Mfg: *

Type: Horizontal End Suction Pumps OPERATINGCONDITIONS.EACH PUMP

*

PERFORMANCE

Proposal Curve No.: NPSH Req'd (Water) Ft: No. of Stages: RPM: Design Eff: % BHP: Max BHP Rated Impeller: Erosion Caused by: No Erosion Max Head Rated Impeller: FT Corrosion Caused by: No Corrosion Min Continuous Flow: GPM Rotation Facing Coupling End: Water Cooling: Bearings: CONSTRUCTION& MATERIALS Stuffing Box: Pedestal: Case Mounting: Horizontal TappedOpenings: Vent, Drain Gland: Split: Radially Radial Bearings: Antifriction Total Water Required GPM Type: Overhung ThrustBearings: DoubleRow Base Plate: Fabricated Angular Contact Packing Cooling: Flushing: API Plan: Nozzles Size ANSI Rating Facing Position AUX PIPING BY MFG Suction 3" 150 # RF End Cooling Water ( )Tubing ( )Pipe Disch 2" 150 # RF Top Seal Flush (X) Tubing ( ) Pipe Impeller Diameter, Rated: * Max: * Type: Enclosed SHOP Coupling & Guard: Mfgr: * Driver Half Mounted by: Vendor TESTS REQUIREDWITNESSED ( ) Packing: Mfgr & Type: Size: No. of Rings: Factory (X) Mech Seal: Mfgr & Model: API Class Code: BSTFM NPSH () () MATERIALS Hydrostatic Test Pressure: PSIG Max Allow CaseWp: PSIG@ °F 316 SS Casing: Carbon Steel Impeller: iWeights, Pump: Base: 316 SS Shaft: 316 SS Shaft Sleeves: Motor: Column: NA Wear Ring Casing: 316 SS Wear Ring Imp: 316 SS Bearing Housing: CarbonSteel ThroatBushing: 316 SS MFG FINALDATA(AS BUILT) Carbon Steel Bearing H Cover: CarbonSteel GlandPlate: A-194-H4 Bolting, Studs: A-193-B7 Nuts: Outline Drawing No.: Pump Sect Drawing No.: MOTOR DRIVER Seal Diagram Drawing No.: Wear Ring Clearance: Mtd by: Pump Vendor Bearings: Antifriction Test Curve Number: Frame: * Full Load Amps: * HP: * RPM: * Area Classification: Class I, Div 2, Group D Mfr: * OPTIONS Insul Class: F SpaceHeater: 120 V Type: Induction Temp Rise: 40°C Volts/Phase/Hz: 460•3•60 Enclosure: TEFC Antifungal Tropicalized Insulation ( ) (X) Mechanical Seal ( ) Packing Internally Epoxy Coat Motor (X) ( )Installed (X) Installed Nonsparking (X) Coupling Guard: Enclosed(X)

Liquid: Rated Flow: Rated Disch Press.: Specific Gravity: Vapor Pressure at PT: Differential Pressure: Differential Head: Design Temperature:

Operating Temperature: 80 °F NPSH Available: * 8R Viscosity: 0.85 CS Code: ANSI B73.1

Diesel Fuel 220 GPM 50 PSIG 0.87 * PSIA 30 PSI 80 Ft 80 °F

,

.

.

.

.

.

.

.

.

.

.

.

.

.

.

,

,,

NOTES: 1. * Denotes information to be provided by vendor with the quotation. 2. Pump shall have a 316 SS nameplate permanently attached to the mounting plate.

160

,