Accepted Manuscript Developing a new frosting map to guide defrosting control for air-source heat pump units J.H. Zhu, Y.Y. Sun, W. Wang, S.M. Deng, Y.J. Ge, L.T. Li PII:
S1359-4311(15)00635-3
DOI:
10.1016/j.applthermaleng.2015.06.076
Reference:
ATE 6769
To appear in:
Applied Thermal Engineering
Received Date: 14 April 2015 Revised Date:
17 June 2015
Accepted Date: 28 June 2015
Please cite this article as: J.H. Zhu, Y.Y. Sun, W. Wang, S.M. Deng, Y.J. Ge, L.T. Li, Developing a new frosting map to guide defrosting control for air-source heat pump units, Applied Thermal Engineering (2015), doi: 10.1016/j.applthermaleng.2015.06.076. This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please note that during the production process errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.
ACCEPTED MANUSCRIPT 1
Developing a new frosting map to guide defrosting control
2
for air-source heat pump units
3
J.H. Zhua, Y.Y. Suna, W. Wanga,*, S.M. Dengb, Y.J. Gea, L.T. Lia Department of Building Environment and Facility Engineering, College of
RI PT
a
4
Architecture and Civil Engineering, Beijing University of Technology, No.100
6
Pingleyuan, Chaoyang District, Beijing 100124, China b
7
Department of Building Services Engineering, The Hong Kong Polytechnic
M AN U
University, Kowloon, Hong Kong SAR, China
8
9
SC
5
Abstract
10
The development of a new frosting map for air-source heat pumps (ASHPs) based on
12
a temperature-humidity chart is reported in this paper. Through a parametric analysis,
13
two boundary lines (a condensing line and a frosting line) were obtained, dividing the
14
map into three regions: a non-frosting region, a condensing region and a frosting
15
region. Using the simulation results from a generalized numerical model of frost
16
growth, the frosting region was further divided into three indicative zones
17
representing different frosting levels: a severe frosting zone, a moderate frosting zone
18
(I, II) and a mild frosting zone (I, II). Lab and field tests were conducted in order to
19
verify the correctness of the zoning and to obtain indicative defrosting intervals for
20
ASHPs operated at different zones. Based on the test results and using the developed
AC C
EP
TE D
11
*
Corresponding author. Tel.: +86 010 67391608-804; fax: +86 010 67391608-804 E-mail address:
[email protected] (W. Wang) 1
ACCEPTED MANUSCRIPT 1
map, reference defrosting intervals were suggested for different frosting zones, and
2
they can be used in conjunction with a conventional defrosting control method to
3
avoid potential mal-defrosting.
RI PT
4 5
Keywords: Air-source heat pump; Frosting map; Defrosting interval; Mal-defrost;
6
Field test
SC
7
M AN U
Nomenclature Frost mass, g
Q
Heating capacity, kW
RH
Air relative humidity, %
Ta
Air temperature, ºC
Td
Air dew point, ºC
Tdc
Defrosting interval, min
Tdis
Discharge temperature, ºC
EP
Freezing point of water, ºC
AC C
Tf
TE D
Mf
Tsuc
Suction temperature, ºC
Tw
Coil temperature of outdoor heat exchanger, ºC
Va
Air velocity, m s−1
W
Input electrical power, kW
∆T
Heat transfer temperature difference, ºC
8
2
ACCEPTED MANUSCRIPT 1
1 Introduction
2
Air-source heat pump (ASHP) technology is widely accepted for the merits of
4
energy-saving and environmental protection. It serves as a heating and cooling source
5
in many parts of the world [1,2]. However, for an ASHP unit, when its outdoor heat
6
exchanger surface temperature is below both air dew point and freezing point of water,
7
frost will form on the outdoor heat exchanger surface. The experimental results [3]
8
indicated that a frost layer on an outdoor heat exchanger surface can reduce its heat
9
flux by about 40 %. According to Sanders [4], the heating capacity of an ASHP unit
10
can be deteriorated by 35 % under frosting conditions. In the previous studies by
11
Wang et al. [5], the heating capacity of an ASHP unit was decreased by 29 % to 57 %
12
when its outdoor heat exchanger was covered by frost. Frosting not only increased the
13
heat transfer resistance and reduced coil’s efficiency [6], but could also lead to the
14
shutdown of an ASHP unit [7].
SC
M AN U
TE D
EP
15
RI PT
3
Therefore, periodic defrosting is necessary, although defrosting itself consumes
17
energy and causes an uncomfortable fluctuation of the indoor air temperature in a
18
heated space [8]. What is more, an improper defrosting-control scheme might result in
19
mal-defrosting [9]. Although various defrosting control methods have been developed,
20
such as temperature difference control [10], artificial neural network [11], fan power
21
sensing [12], photoelectric technology [13], etc., temperature-time (T-T) is the most
22
widely used defrosting control method. As reflected by its name, T-T control is based
AC C
16
3
ACCEPTED MANUSCRIPT on temperature and time and is adopted in most ASHP units due to its simplicity.
2
However, its reliability is questionable. Baxter and Mogers [14] found that, in a T-T
3
controlled ASHP unit, approximately 27 % of defrosting was carried out when no
4
frost was observed. According to the field test results [15], nearly 68 % of defrosting
5
was unnecessary in a heating season in Beijing, China. For a T-T controlled ASHP
6
unit, mal-defrost mainly resulted from the fact that one important parameter, air
7
humidity, was not taken into account. Both air temperature and humidity affect
8
frosting in an ASHP unit. Without knowing both parameters, it is hardly possible to
9
make a correct judgment on whether an ASHP unit is actually operating under frosting
10
conditions, nor is it possible to make a correct judgment as to the level of frosting.
11
Therefore, the use of T-T control can lead to mal-defrosting. To avoid mal-defrosting,
12
it is necessary to know how different combinations of ambient air temperature and
13
humidity affect frosting and its level.
SC
M AN U
TE D
14
RI PT
1
Limited studies related to developing a frosting map have been previously reported.
16
For example, Adachi et al. [16] proposed the ranges of outdoor air parameters within
17
which frosting may occur, as shown in Fig. 1 a). In Fig. 1 a), the shaded area is the
18
frosting region inside which, when an ASHP unit is operated, frosting on its outdoor
19
heat exchanger may occur. Frosting conditions were confined between Ta of −5 ºC
20
and 7 ºC and between RH of 60 % and 100 %. However, the level of frosting cannot
21
be specified by using this map. Furthermore, field test results [15] suggested that the
22
surface of the outdoor heat exchanger in an ASHP unit may also be frosted at Ta of
AC C
EP
15
4
ACCEPTED MANUSCRIPT 1
−0.6 ºC to 1.6 ºC and RH of 45 % to 52 %. But this is not covered in Fig. 1 a).
2 3
Fig. 1 Frosting maps developed in two previous studies
RI PT
4
Wang and Chen [17] also proposed a frosting map using simulation results, as shown
6
in Fig. 1 b). The map was divided into three regions, a non-frosting region (Region I),
7
a condensing region (Region II) and a frosting region (Region III). It was developed
8
at a specific air velocity (Va) of 2 m s−1, a level not considered by Adachi et al. [16].
9
Region III was further divided into five parts based on different frosting rates (Wm).
10
Therefore, this frosting map presented more details. However, although the frosting
11
rate was considered, as shown in Fig. 1 b), it cannot be directly used as a base for
12
defrosting control. Furthermore, it was not verified by experiments or field tests.
13
According to the field test results [15], the outdoor heat exchanger in an ASHP unit
14
may also be frosted in the non-frosting region. Therefore, the frosting map should be
15
further improved.
M AN U
TE D
EP
AC C
16
SC
5
17
In this paper, therefore, the development of a new frosting map for ASHPs with a
18
further zoning of the frosting region on a temperature-humidity chart, which can be
19
regarded as a further development to the frosting map developed by Wang and Chen
20
[17] shown in Fig. 1 b), is reported. Similar to the map developed by Wang and Chen
21
[17], the new map was also divided into three regions based on the
22
temperature-humidity chart: a non-frosting region, a condensing region and a frosting 5
ACCEPTED MANUSCRIPT region. By using a generalized numerical model for predicting frost growth on a cold
2
flat plate [18], the frosting region was further divided into three distinctive zones
3
representing different frosting levels, i.e., a severe frosting zone, a moderate frosting
4
zone (I, II) and a mild frosting zone (I, II). To verify the correctness of the zoning and
5
to obtain indicative defrosting intervals for ASHPs operating at different zones, lab
6
and field tests were conducted. Based on the tests results, reference defrosting
7
intervals for ASHP units operating at different frosting zones are proposed. The
8
potential uses of the new frosting map are also discussed.
M AN U
SC
RI PT
1
9 10
2 The developed new frosting map
11
A frosting map based on a temperature-humidity chart indicates frosting situations
13
and levels on the outdoor heat exchanger surface in an ASHP unit. The procedure to
14
develop the new frosting map is shown in Fig. 2, and is explained in this section.
17 18 19
EP
16
Fig. 2 The flow chart for developing the new frosting map
AC C
15
TE D
12
2.1 Assumptions
20
Frost formation and growth is a transient process featuring dynamic heat and mass
21
transfer. It is impacted by the following primary parameters: air temperature, air
22
relative humidity, air velocity, air cleanliness and the temperature and wettability of 6
ACCEPTED MANUSCRIPT 1
an outdoor heat exchanger surface [19]. When developing the new frosting map, the
2
following were assumed:
3
1) As air cleanliness and the wettability of the outdoor heat exchanger surface were not easily quantified, they were neglected;
RI PT
4
2) In practical application, air velocity at the outdoor heat exchanger surface in an
6
ASHP unit is between 1.5 m s−1 and 3.5 m s−1 [17]. In this study, Va was set as 2
7
m s−1;
9 10
3) The mass flow rate of the refrigerant was evenly distributed to each refrigerant
M AN U
8
SC
5
circuit;
4) A constant speed compressor was used.
11
2.2 Division of the frosting map through a parametric analysis
TE D
12 13
1) The range of the new frosting map
15
The range of the new frosting map needed to be determined. While air relative
16
humidity varied from 0 % to 100 %, the lower limit of the air temperature was set at
17
−15 ºC, a value widely accepted by manufacturers of ASHP units [20]. On the other
18
hand, heating may not be required in regions where the average temperature in
19
January is higher than 11.5 ºC [20], so this value was set as the upper limit of the air
20
temperature. Therefore, for the new frosting map to be developed for ASHP units, its
21
temperature range was set at −15 ºC to 11.5 ºC, and the relative humidity range was 0 %
22
to 100 %.
AC C
EP
14
7
ACCEPTED MANUSCRIPT 2) Physical phenomena of condensing and frosting
2
Non-frosting: If Tw > Td, both condensation and frost do not occur on the outdoor heat
3
exchanger surface.
4
Condensing: If Tw < Td and Tw > Tf, condensation occurs on the outdoor heat
5
exchanger surface.
6
Frosting: If Tw < Td and Tw < Tf, frost occurs on the outdoor heat exchanger surface.
7
There are two critical conditions for the above three physical phenomena. Tw = Td is
8
the critical condition for condensing. Tw < Td and Tw = Tf are the critical conditions for
9
frosting. Therefore, by comparing the values of Tw, Td and Tf, the frosting map can be
10
divided into three regions: a non-frosting region, a condensing region and a frosting
11
region.
M AN U
SC
RI PT
1
TE D
12
3) Determination of Tw and Td
14
Based on the above analysis, two crucial parameters, Tw and Td, need to be determined
15
first.
16
Tw can be estimated by the following correlation:
AC C
17
EP
13
= − ∆
(1)
18
where ∆T is the heat transfer temperature difference in an outdoor heat exchanger. The
19
value of ∆T is usually 11 ºC to 13 ºC [20], varying with the changes of Ta. To
20
determine a practical relationship between ∆T and Ta, a field test was conducted using
21
the test system described in Section 3.2 in this paper. The field test results are shown
22
in Fig. 3. 8
ACCEPTED MANUSCRIPT 1 2
Fig. 3 Heat transfer temperature difference with the change in air temperature
3
As shown in Fig. 3, ∆T decreased as a result of a decrease in Ta. Using the method of
5
linear regression, the following linear regression equation linking Ta and ∆T was
6
obtained, with the correlation coefficient R2 = 0.69:
∆ = + ∙ ( = 10.260; = 0.172)
SC
7
RI PT
4
(2)
Based on Equations (1) and (2), Tw can be calculated by using Ta.
9
Td can be calculated by using two air state parameters, Ta and RH. On the
10
temperature-humidity chart, the constant dewpoint curves can be obtained by
11
connecting the air state points, which have same values of Td.
M AN U
8
TE D
12
4) The condensing and frosting line
14
The condensing line is a boundary line used to judge whether condensation will occur
15
on the outdoor heat exchanger. According to the above analysis, the values of the two
16
parameters (Tw, Td) on any point of the frosting map can be determined. As shown in
17
Fig. 4, by connecting these points (Tw = Td) on the frosting map, the condensing line
18
was obtained. Below the condensing line, Tw is higher than Td, and there is no
19
condensation. Above the condensing line, Tw is lower than Td, and condensation will
20
occur on outdoor heat exchanger surface. If Tw is also lower than Tf, the outdoor heat
21
exchanger surface will be frosted.
AC C
EP
13
22 9
ACCEPTED MANUSCRIPT Fig. 4 The frosting map with three regions
1 2
The frosting line is a boundary line used to judge whether frost will occur on the
4
outdoor heat exchanger. Based on Equations (1) and (2), when Ta is 12 oC, Tw is equal
5
to Tf. If Ta is lower than 12 oC, Tw is lower than Tf, and frost will occur on the outdoor
6
heat exchanger surface. However, due to the temperature difference between the fins
7
and coils of an outdoor heat exchanger, the temperatures of most parts of the outdoor
8
heat exchanger would be higher than Tw. Based on the field test data, when Ta was
9
between 6 and 12 oC, frost and condensation occurred on the outdoor heat exchanger
10
surface at the same time, but condensation was dominant. Only when Ta was lower
11
than 6 oC, did frost occur on most parts of the outdoor heat exchanger. Therefore, the
12
frosting line was determined at 6 oC.
TE D
M AN U
SC
RI PT
3
13
5) The non-frosting, condensing and frosting region
15
Based on the two boundary lines, the frosting map was divided into three regions:
16
Condensing region (above the condensing line and on the right side of the frosting line). When an ASHP unit works in this region, condensation occurs on its outdoor heat exchanger surface.
20
22
AC C
19
21
Non-frosting region (under the condensing line). If an ASHP unit is operated in this region, its outdoor heat exchanger surface remains dry and no frost is formed.
17 18
EP
14
Frosting region (above the condensing line and on the left side of the frosting line). In this region, the ASHP unit works with frost on the outdoor heat 10
ACCEPTED MANUSCRIPT 1
exchanger surface.
2 3
2.3 Further division for the frosting region
RI PT
4
To specify frosting levels, the frosting region may be further divided based on
6
simulation results using a generalized numerical model for predicting frost growth on
7
a cold flat plate [18]. In this way, the frosting map may be used to predict frosting
8
levels of an ASHP unit operated under different temperature-humidity conditions. By
9
plotting curves of the constant frosting rate, the frosting region was, therefore, further
10
divided into three indicative zones representing different frosting levels, i.e., a severe
11
frosting zone, a moderate frosting zone and a mild frosting zone. In order to obtain a
12
more detailed frosting rate, the moderate frosting zone and the mild frosting zone
13
were both divided into two parts (I, II) reflecting different frosting levels. The division
14
of the frosting region is shown in Fig. 5.
17 18 19
M AN U
TE D
EP
16
Fig. 5 Indicative divisions in the frosting region
AC C
15
SC
5
3 Lab and field tests
20
To verify the correctness of the zoning of the frosting region and to obtain indicative
21
defrosting intervals for ASHPs operated at different zones, both lab tests and field
22
tests were carried out. 11
ACCEPTED MANUSCRIPT 1
3.1 Description of lab tests
2
In the severe frosting zone, three lab-based test cases (Cases 1–3) were carried out
4
using a lab-based test ASHP unit with a nominal heating capacity of 60 kW. This has
5
been previously described [21]. The reason for using a lab-based test instead of using
6
a field test was that, in Beijing, the outdoor weather conditions in winter were outside
7
the severe frosting zone. As a result, it was not possible to carry out field tests at the
8
severe frosting zone. The operating conditions of these test cases are listed in Table 1
9
and shown in Fig. 6, using the averaged tested air temperature and humidity.
M AN U
SC
RI PT
3
10 11
Table 1 Detailed operating conditions for all test cases
TE D
12
Fig. 6 Test conditions shown on the frosting region in the new frosting map for
14
Cases 1–15
16 17
3.2 Description of field tests
AC C
15
EP
13
18
A field test system was used to investigate the 12 cases (Cases 4–15) in the moderate
19
frosting zone (I, II) and the mild frosting zone (I, II). The operating conditions of
20
these test cases are also listed in Table 1 and shown in Fig. 6 using the averaged tested
21
air temperature and humidity. The field tests were carried out during two heating
22
seasons of 2012–2014 in an office building (test building) in Beijing, China. There 12
ACCEPTED MANUSCRIPT were 11 rooms with a total heating area of 185 m2. A commercial ASHP unit served as
2
both the heating and cooling sources for the test building. The nominal heating
3
capacity and input electric power were 28 kW and 8.66 kW respectively, based on
4
nominal conditions for provision of hot water to a floor radiant heating system. The
5
ASHP unit was equipped with two constant speed compressors. Reversed-cycle
6
defrosting was used. Fig. 7 shows the schematics of the test ASHP unit.
RI PT
1
SC
7
Fig. 7 Schematic of the field test ASHP unit and its associated space heating
M AN U
8
system
9 10
A measuring system was built to monitor and record the outdoor testing environment
12
and the operating parameters of the test ASHP unit. Table 2 presents detailed
13
information of the measuring system. Furthermore, photos of frost growth on the
14
outdoor heat exchanger surface of the test ASHP unit were taken.
TE D
11
EP
15
Table 2 Details of the measuring system for the ASHP unit used in field tests
AC C
16 17 18
Using the measuring system detailed in Table 2, the following parameters were
19
monitored.
20
pressure;
21 22
Air side: Outdoor heat exchanger inlet and outlet temperature, humidity and
Refrigerant side: Compressor suction and discharge temperatures and pressures, 13
ACCEPTED MANUSCRIPT 1
outdoor heat exchanger surface temperature (tube & fin), expansion valve inlet
2
and outlet temperatures;
Water side: Condenser inlet and outlet temperatures, water flow rate;
4
Others: Input electrical power to fan, compressor and water pump, frost mass, etc.
RI PT
3
5
All sensors and measuring devices were able to output a direct current signal of 4–20
7
mA or 0–10 V to a data acquisition system (DAS) for logging and recording. The
8
DAS collected and recorded all the measured data at an interval of 5 s.
M AN U
SC
6
9 10
4 Test results
11
The operating characteristics of both the lab test ASHP unit and the field test ASHP
13
unit at different frostings during laboratory and field tests are presented in this section.
14
TE D
12
Fig. 8 presents the results of lab-based test cases (Cases 1–3) in the severe frosting
16
zone. As shown in Fig. 8 a) and Fig. 8 b), in all three cases, as the frosting on the
17
outdoor heat exchanger proceeded, the operating performance of the test ASHP unit
18
deteriorated quickly. For example, in Case 1, the discharge temperature (Tdis) was
19
increased from 99.5 ºC at 10 min to 115.8 ºC at 26 min, and the suction temperature
20
(Tsuc) was decreased from −3.6 ºC at 10 min to −12.6 ºC at 26 min. The output heat
21
capacity (Q) of the test ASHP unit dropped by 30 %, and the COP decreased by 26 %
22
at 26 min, compared with the values at 10 min. For Cases 1–3, defrosting started at 26
AC C
EP
15
14
ACCEPTED MANUSCRIPT min, 27 min and 27 min respectively. Furthermore, as seen from the photos shown in
2
Fig. 8 c), over 90 % of the outdoor heat exchanger’s surface was covered by heavy
3
frost for each case at the start of defrosting. This suggested that, when an ASHP unit is
4
operated in the severe frosting zone, frost will quickly form on its outdoor heat
5
exchanger surface. Therefore, it can be recommended that the defrosting interval for
6
ASHP units operating in the severe frosting zone should be less than 30 min.
RI PT
1
SC
7
Fig. 8 Test results of Cases 1–3
M AN U
8 9
The full results for all the remaining cases are shown in Table 3. As shown in Fig. 9,
11
similar trends of the heating capacity and COP reductions to those in Cases 1–3 can
12
be observed. Furthermore, as shown in Table 3, defrosting was initiated when capacity
13
loss was at about 30 % and Mf was about 1320 g for all cases but was initiated at
14
different times, depending on the frosting zone in which the test ASHP unit was
15
operated. At moderate frosting zones I and II, defrosting was started at 45 min and
16
60–75 min, and, at mild frosting zones I and II, defrosting was started at 90–140 min
17
and 180–240 min respectively.
19
EP
AC C
18
TE D
10
Table 3 Results of four field tests (Cases 4–15)
20 21
Fig. 9 Results of selected field tests in moderate and mild frosting zones (Case 5,
22
8, 11, 14) 15
ACCEPTED MANUSCRIPT 1
5 Discussion
2
Based on the test results of Cases 1–15 and using the new frosting map, the reference
4
defrosting intervals for ASHP units operating at different frosting zones were
5
proposed, as shown in Table 4.
RI PT
3
6
Table 4 Reference defrosting intervals for ASHP units operating at different
8
frosting zones
M AN U
SC
7
9
These reference defrosting intervals can be used in conjunction with a conventional
11
time control or T-T control to avoid potential mal-defrosting. For example, when an
12
ASHP unit is operated at moderate frosting zone II, its reference defrosting interval is
13
45 to 90 minutes. Therefore, if its T-T control calls for defrosting in less than 45
14
minutes, possible mal-defrosting can be expected because the defrosting operation is
15
carried too early and the outdoor heat exchanger may only be covered with slight frost.
16
On the contrary, if the defrosting operation is carried out for more than 90 minutes,
17
possible mal-defrosting can be also expected. Because the outdoor heat exchanger
18
may be covered with heavily frost, the performance of the unit may seriously decrease.
19
This may even lead to the shutdown of the unit. In addition, the new frosting map can
20
be used to indicate if ASHP units may be appropriately applied in a specific area. For
21
example, it is not recommended to use ASHP units if most conditions for winter days
22
are in the severe frosting zone, even if it is not very cold, because frequent frosting
AC C
EP
TE D
10
16
ACCEPTED MANUSCRIPT 1
and defrosting will seriously decrease the performance of ASHP units.
2
Due to the difference in ∆T, appropriate modifications might have to be introduced
4
when the frosting map is used for other ASHP units. ∆T is an important parameter to
5
estimate Tw according to Ta. Different ∆Ts will result in different frosting maps.
6
Normally, ∆T is 11 ºC to 13 ºC when Ta is 7 ºC [20]. For the tested unit, ∆T was about
7
11.5 ºC when Ta was 7 ºC. For another unit, ∆T may be different, and Equation (2) (a
8
linear regression equation between ∆T and Ta described in Section 2.2) should first be
9
modified. In Equation (2), the main parameter is k1 as its value is much higher than
10
the value of ∙ . Therefore, to modify Equation (2), k2 should remain unchanged
11
while k1 should be altered according to the change of ∆T when Ta is 7 ºC. If ∆T is 13
12
ºC when Ta is 7 ºC, k1 should increase by about 1.5. Once Equation (2) is modified,
13
the frosting map can be correspondingly modified. In the frosting map, the frosting
14
line will move right for about 2 ºC, and the condensing line will move down for about
15
5 % RH. The above analysis shows that, for different ASHP units, the bigger ∆T is,
16
the lower Tw is and the bigger the range of the frosting region is. Nevertheless, if there
17
is only a slight difference in ∆T, the frosting map can be directly used.
19
SC
M AN U
TE D
EP
AC C
18
RI PT
3
6 Conclusions
20 21
In this paper, the development of a new frosting map for ASHP units is reported.
22
Through a parametric analysis, two boundary lines (a condensing line and frosting 17
ACCEPTED MANUSCRIPT line) were obtained, dividing the map into three regions: a non-frosting region, a
2
condensing region and a frosting region. Furthermore, the frosting region was divided
3
into three indicative zones representing different frosting levels: a severe frosting zone,
4
a moderate frosting zone (I, II) and a mild frosting zone (I, II). The operating
5
characteristics of the test ASHP unit at different frosting zones during laboratory and
6
field tests were presented. Based on the test results and using the new frosting map,
7
reference defrosting intervals were also suggested for ASHP units operating in
8
different frosting zones, and these intervals can be used in conjunction with a
9
conventional defrosting control method to avoid potential mal-defrosting.
10 11
Acknowledgements
TE D
12
M AN U
SC
RI PT
1
This work was supported partially by the National Natural Science Foundation of
14
China (Grant No. 51178015), National Twelfth Five-year Science & Technology
15
Support Plan (Grant No. 2011BAJ03B10), Beijing New-star Plan of Science and
16
Technology, and the science and technology plan project of Beijing Municipal
17
Education Commission (Grant No. KM 201410005022).
AC C
18
EP
13
19
20
21
18
ACCEPTED MANUSCRIPT
References [1]
W. Wang, Z.L. Ma, Y.Q. Jiang, Y. Yao, S. Xu, Z. Yang, Field test investigation of a double-stage coupled heat pumps heating system for cold regions, Int. J.
[2]
RI PT
Refrig. 28 (5) (2005) 672–679.
M. Mohanraj, S. Jayaraj, C. Muraleedharan, Applications of artificial neural networks for refrigeration, air-conditioning and heat pump systems-A review,
P.L.T. Brian, R.C. Reid, Y.T. Shah, Frost deposition on cold surfaces. Ind. Eng.
M AN U
[3]
SC
Renew. Sust. Energ. Rev. 16 (2) (2012) 1340–1358.
Chem. Fundam. 9 (3) (1970) 375–380. [4]
C.T. Sanders, Testing of air coolers operating under frosting conditions, in heat and mass transfer in refrigeration systems and in air-conditioning, Int. J. Refrig.
[5]
TE D
(1972) 383–396.
W. Wang, Y.C. Feng, J.H. Zhu, L.T. Li, Q.C. Guo, W.P. Lu, Performances of
EP
air source heat pump system for a kind of mal-defrost phenomenon appearing in moderate climate conditions, Appl. Energ. 112 (12) (2013) 1138–1145. [6]
R. Lazzarin, D. Nardotto, Study of Frost Growth on an Air Heat Pump Outside
AC C
1
Coil, Proceedings Congress "Sustainable Refrigeration and Heat Pump Technology", Stockholm, (2010).
[7]
S.N. Kondepudi, D.L. O’Neal, Effect of different fin configuration on the performance of finned-tube heat exchanger under frosting conditions, ASHRAE Trans. 96 (2) (1990) 439–444.
[8]
W.J. Hu, Y.Q. Jiang, M.L. Qu, L. Ni, Y. Yao, S.M. Deng, An experimental study 19
ACCEPTED MANUSCRIPT on the operating performance of a novel reverse-cycle hot gas defrosting method for air source heat pumps, Appl. Therm. Eng. 31 (2011) 363–369. [9]
W. Wang, J. Xiao, Q.C. Guo, W.P. Lu, Y.C. Feng, Field test investigation of
phenomena, Appl. Energ. 88 (12) (2011) 4470–4480.
RI PT
the characteristics for the air source heat pump under two typical mal-defrost
[10] T.R. Buick, J.T. Mcmullan, R. Morgan, R.B. Murry, Icedetection in heat pumps
SC
and coolers, Int. J. Energ. Res. 2 (1) (1978) 85–98.
M AN U
[11] D. Datta, S.A. Tassou, Implementation of a defrost on demand control strategy on a retail display cabinet, Proc. IIF-IIR–Commission D, 1 (2002) 218–226. [12] E.D. Muller, A new concept for defrosting refrigeration plants, Kalte, 28 (2) (1975) 52–54.
TE D
[13] J. Xiao, W. Wang, Y.H. Zhao, F.R. Zhang, An analysis of the feasibility and characteristics of photoelectric technique applied in defrost-control, Int. J. Refrig. 32 (6) (2009) 1350–1357.
EP
[14] V.D. Baxter, J.C. Mogers, Field-measured cycling, frosting and defrosting (2B)
AC C
losses for a high-efficiency air-source heat pump, ASHRAE Trans. 91 (1985) 537–554.
[15] Y.C. Feng, Mal-defrost accident research of air source heat pump. (MPhil Thesis), Beijing University of Technology, Beijing, (2013) [In Chinese].
[16] M. Adachi, S. Inoue, T. Aizawa, On the refrigeration cycle property of heat pump air conditioners operating with frost formation, Refrigeration, 50 (576) (1975) 818–820 [In Japanese]. 20
ACCEPTED MANUSCRIPT [17] J.F. Wang, G.M. Chen, Study of frosting characteristics of air source heat pumps during winter heating, Refrigeration, (1) (1997) 8–11 [In Chinese]. [18] W. Wang, Q.C. Guo, W.P. Lu, A generalized simple model for predicting frost
RI PT
growth on cold flat plate, Int. J. Refrig. 35 (2) (2012) 475–486. [19] C.M. Robinson, A.M. Jacobi, A study of frost formation on a plain fin. Air and
Refrigeration
Center,
Urbana-Champaign, IL, (2001) TR-188.
University
of
Illinois
at
SC
Conditioning
M AN U
[20] W. Wang, F.R. Zhang, Q.C. Guo, J. Xiao, Y.H. Zhao, Investigation of frost status for air source heat pump in different regions of China, J. Hunan Univ. 36 (12) (2009) 9–13 [In Chinese].
[21] W. Wang, J. Xiao, Y.C. Feng, Characteristics of an air source heat pump with
TE D
novel photoelectric sensors during periodic froste-defrost cycles, Appl. Therm.
AC C
1
EP
Eng. 50 (1) (2013) 177–186.
21
ACCEPTED MANUSCRIPT Figure captions Frosting maps developed in two previous studies
Figure 2
The flow chart for developing the new frosting map
Figure 3
Heat transfer temperature difference with the change in air temperature
Figure 4
The frosting map with three regions
Figure 5
Indicative divisions in the frosting region
Figure 6
Test conditions shown on the frosting region in the new frosting map for
M AN U
Cases 1–15 Figure 7
Schematic of the field test ASHP unit and its associated space heating system
Figure 8
RI PT
Figure 1
SC
1
Test results of Cases 1–3
Figure 9
TE D
Results of selected field tests in moderate and mild frosting zones (Case
AC C
2
EP
5, 8, 11, 14)
22
ACCEPTED MANUSCRIPT 100 90
70
RI PT
RH (%)
80
60 50
Frosting region 40 0
5
10
SC
-5
Ta (oC)
100
III
1.
90
W 80
1.2 5
=0
.6 3
88
2. 50
x1
x1 0 -5
x1
TE D
RH (%)
m
70
M AN U
a) The frosting map developed by Adachi et al. (1975)
0 -5
x
10 -
II
5
0 -5
kg
(m 2
s) - 1
I
Va = 2 m s-1
EP
60 -10
-5
0
5
10
o
Ta ( C)
1 2
AC C
b) The frosting map developed by Wang and Chen (1997) Fig. 1 Frosting maps developed in two previous studies
23
RI PT
ACCEPTED MANUSCRIPT
2
SC
1
Fig. 2 The flow chart for developing the new frosting map
AC C
EP
TE D
M AN U
3
24
ACCEPTED MANUSCRIPT 16 Experimental data Fitting line
14
o
△T ( C)
12 10
6 4 -10
-8
-6
-4
0
Ta (oC)
1
2
4
6
8
10
Fig. 3 Heat transfer temperature difference with the change in air temperature
SC
2
-2
RI PT
8
AC C
EP
TE D
M AN U
3
25
ACCEPTED MANUSCRIPT 100 2
A
3 B
a
70
4 C
5 D
b
RH (%)
60
7
e
region
8
F
d
9
G
10
H
f
12
J
13
K
i
50
Condensing line
11
I
g h
j
k
L l
14 M m
N n
40 30
15 O o
16 P p
17
18 19 Q 20 R 21 S q 22 T r 23 U s 24 V t 25 W u 26 X v w x Y Z 27 28 y z AA AB 29 30 aa ab ACAD 31 32 ac ad AE AF 33 34 35 ae af AGAH AI 36 37 ag ah 38 39 40 41 ai AJ aj AK 42 43 44 ak AL al AM amAN 45 46 47 an AO ao AP ap AQ 48 49 50 aq AR ar AS as AT 51 52 53 54 at AU au AV av AW awAX ax AY ay AZBA az ba BB bb
Non-frosting region
20 10 0 -15
Condensing
Frosting region
6 E
c
-12
-9
-6
-3
0 o
Ta ( C)
1 2
3
6
9
Fig. 4 The frosting map with three regions
AC C
EP
TE D
M AN U
3
26
0 -1 -2 -3 -4 -5 -6 -7 -8 -9 -10 -11 -12 -13 -14
1 A a
-15 -16 -17 -18 -19 -20 -21 -22 -23 -24 -25 -26 -27 -28
RI PT
80
Constant o dewpoint ( C)
Frosting line
11.5
SC
90 1
ACCEPTED MANUSCRIPT 100
80
ΙΙ
RH (%)
70 60
Severe frosting zone
Moderate frosting zone Ι
Mild frosting zone
Ι ΙΙ
50 40 30
Frosting region Condensing region Non-frosting region
20 10 -12
-9
-6
-3
0 o
Ta ( C)
1
6
9
Fig. 5 Indicative divisions in the frosting region
M AN U
2
3
SC
0 -15
RI PT
90
AC C
EP
TE D
3
27
11.5
ACCEPTED MANUSCRIPT 100 Averaged test conditions
C1 C2 C3 Severe frosting zone
90 Moderate frosting zone Ι
ΙΙ
C4 C7
70
Ι
60
C9
ΙΙ
C10
50
C13
C11 C15
C14
C12
40
-9
-6
-3
Ta ( C)
1
0
3
6
SC
-12
o
Fig. 6 Test conditions shown on the frosting region in the new frosting map for
M AN U
2
Cases 4-15 (Field test)
C6
C5 C8
Mild frosting zone
30 -15
Cases 1-3 (Lab-based test)
RI PT
RH (%)
80
Cases 1–15
3
AC C
EP
TE D
4
28
1
TE D
M AN U
SC
RI PT
ACCEPTED MANUSCRIPT
Fig. 7 Schematic of the field test ASHP unit and its associated space heating
3
system
AC C
4
EP
2
29
ACCEPTED MANUSCRIPT 120
C1
C2
C3
80 60
Tdis 20
Tsuc
10 0 -10 -20 0
10
20
30 0
10
20
60
C2
M AN U
C1
40
Q
30
W 20 10 0 0
6
10
TE D
Q & W (kW)
50
30
20
30 0
10
20
30 0
C3
10
20
Time (min)
EP
b) Variation of Q and W over time
AC C
5
20
a) Variation of Tdis and Tsuc over time
2
4
10
SC
Time (min)
1
3
30 0
RI PT
Tdis & Tsuc (oC)
100
26 min (Case 1)
27 min (Case 2)
27 min (Case 3)
7
c) Photos of the frosted outdoor coil
8
Fig. 8 Test results of Cases 1–3
9 30
30
ACCEPTED MANUSCRIPT 120 110
90 80
Tdis
C5 C8
20
C11
Tsuc
10 0 -10 -20 0
45 60
120
140
a) Variation of Tdis and Tsuc over time
2
12
Q & W (kW)
10 8
C5 C8
6
2 0 0
45 60
120
140
180
Q W
C14
240
Time (min)
3
6
C11
TE D
4
M AN U
14
EP
b) Variation of Q and W over time
AC C
5
240
SC
1
4
180
Time (min)
C14
RI PT
Tdis & Tsuc (oC)
100
45 min (Case 5)
60 min (Case 8)
140 min (Case 11)
240 min (Case 14)
7
c) Photos of the frosted outdoor coil
8
Fig. 9 Results of selected field tests in moderate and mild frosting zones (Case 5,
9
8, 11, 14) 31
ACCEPTED MANUSCRIPT Table captions Table 1
Detailed operating conditions for all test cases
Table 2
Details of the measuring system for the ASHP unit used in field tests
Table 3
Results of four field tests (Cases 4–15)
Table 4
Reference defrosting intervals for ASHP units operating at different
RI PT
1
frosting zones
AC C
EP
TE D
M AN U
SC
2
32
ACCEPTED MANUSCRIPT 1
Table 1 Detailed operating conditions for all test cases Ta (ºC)
RH (%)
Frosting
Case Avg.
Range
Avg.
zone
C1
−0.4 to 0.6
0.1
90.3 to 92.5
91.5
Severe
C2
0.5 to 0.9
0.7
91.2 to 92.4
92.0
Severe
C3
0.6 to 2.1
1.3
90.5 to 92.1
91.4
Severe
C4
−2.2 to −1.5
−2.0
73.6 to 75.7
74.5
Moderate I
C5
2.8 to 3.1
2.9
73.5 to 75.2
74.3
Moderate I
C6
4.2 to 5.3
4.8
68.1 to 69.2
68.7
Moderate I
C7
−6.0 to −5.1
−5.7
68.6 to 69.8
69.2
Moderate II
C8
3.9 to 4.5
−1.0
63.6 to 67.1
66.4
Moderate II
C9
5.0 to 5.6
5.2
58.8 to 62.7
60.7
Moderate II
C 11
−0.5 to 1.0
C 12
3.3 to 4.7
C 13
−3.0 to −1.5
C 14 C 15
SC
Laboratory
M AN U
TE D
−1.9 to 0.1
Field test
−1.2
54.6 to 58.3
56.8
Mild I
0.2
50.6 to 54.4
52.8
Mild I
3.8
50.2 to 55.3
52.1
Mild I
−2.2
47.8 to 49.9
49.2
Mild II
−1.9 to −0.8
−1.3
45.1 to 48.1
46.3
Mild II
0.1 to 1.1
0.5
47.5 to 49.8
48.5
Mild II
EP
C 10
RI PT
Range
AC C
2
Remark
33
ACCEPTED MANUSCRIPT Table 2 Details of the measuring system for the ASHP unit used in field tests Device
Number
Accuracy of reading
Full scale
Temperature sensor (PT1000)
18
Class A
−40 to 140 ºC
Humidity sensor
2
±3.5 %
0 to 99 %
Differential pressure sensor (air)
2
±3.0 %
Pressure sensor (refrigerant)
4
±0.4 %
Power sensor
3
±1.0 %
--
Flow-meter
1
±0.5 %
0.5 to 10 m3 h−1
1
--
15 Megapixels
1
--
14 Megapixels
1
±0.1 g
0 to 6000 g
RI PT
1
0 to 100 Pa 0 to 40 bar
Digital camera
AC C
EP
TE D
Electronic scale 2
SC
M AN U
Video camera
0 to 25 bar
34
ACCEPTED MANUSCRIPT Table 3 Results of four field tests (Cases 4–15)
Moderate II
Mild I
Mf (g)
Loss of Q (%)
Tdc (min)
C4
1393
30
45
C5
1386
30
45
C6
1381
29
45
C7
1375
30
70
C8
1362
30
60
C9
1406
31
75
C 10
1363
C 11
1361
C 12 C 13 C 14
Mild II
C 15
30
90
31
140
1365
31
120
1162
30
200
1192
30
240
1089
29
180
AC C
EP
TE D
2
RI PT
Moderate I
Case
SC
Frosting zone
M AN U
1
35
ACCEPTED MANUSCRIPT 1
Table 4 Reference defrosting intervals for ASHP units operating at different
2
frosting zones Reference defrosting intervals (min)
Severe frosting zone
Tdc ≤ 30 I
30 ≤ Tdc ≤ 45
II
45 ≤ Tdc ≤ 90
I
SC
RI PT
Frosting zones
Moderate frosting zone
90 ≤ Tdc ≤ 150
Mild frosting zone
150 ≤ Tdc ≤ 240
M AN U
II
AC C
EP
TE D
3
36
ACCEPTED MANUSCRIPT Highlights A new frosting map guiding defrosting control for ASHPs was reported. The map was divided into three regions, non-frosting, condensing, frosting
RI PT
region. Frosting region was divided into three zones, severe, moderate, mild frosting zone.
SC
Lab and field tests were carried out to verify the correctness of the zoning.
AC C
EP
TE D
M AN U
Reference defrosting intervals were proposed for different frosting zones.