Accepted Manuscript Energy saving evaluation of a novel energy system based on spray cooling for supercomputer center
Hua Chen, Wen-long Cheng, Wei-wei Zhang, Yu-hang Peng, Li-jia Jiang PII:
S0360-5442(17)31608-0
DOI:
10.1016/j.energy.2017.09.089
Reference:
EGY 11583
To appear in:
Energy
Received Date:
16 December 2016
Revised Date:
30 August 2017
Accepted Date:
19 September 2017
Please cite this article as: Hua Chen, Wen-long Cheng, Wei-wei Zhang, Yu-hang Peng, Li-jia Jiang, Energy saving evaluation of a novel energy system based on spray cooling for supercomputer center, Energy (2017), doi: 10.1016/j.energy.2017.09.089
This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please note that during the production process errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.
ACCEPTED MANUSCRIPT Highlights:
A novel energy system based on spray cooling for supercomputer center is proposed.
The system integrates spray cooling with waste heat driven absorption chiller.
Modeling of integrated energy system under different working conditions.
Inlet temperature strongly affects cooling capacity and optimum temperature exists.
The system can achieve energy saving of 49% and PUE within best practice scenario.
ACCEPTED MANUSCRIPT
1
Energy saving evaluation of a novel energy system based on
2
spray cooling for supercomputer center
3
Hua Chen, Wen-long Cheng, Wei-wei Zhang, Yu-hang Peng, Li-jia Jiang
4
Department of Thermal Science and Energy Engineering, University of Science and
5
Technology of China, Hefei, Anhui 230027, PR China
6 7
Abstract: To improve the energy efficiency of supercomputer center, a novel energy
8
system aimed at enhancing cooling efficiency while reusing waste heat is proposed.
9
The energy system integrates a plug-type spray cooling system with a two-stage
10
absorption chiller driven by spray cooling waste heat. Overall modeling of integrated
11
energy system is analyzed based on spray cooling model and absorption chiller
12
model. Energy saving evaluation is conducted based on Dawning 5000A
13
supercomputer in China. It is found that the novel energy system is much efficient
14
than the original energy system in all seasons. The energy saving effect is highly
15
affected by inlet temperature of spray cooling. With the increase of inlet temperature,
16
the spray cooling capacity decreases while the absorption cooling capacity increases.
17
Thus, an optimal inlet temperature of 55℃ is obtained at which the lowest cooling
18
power consumption, lowest power utilization effectiveness (PUE) and highest energy
19
saving efficiency (ESE) can be achieved. Taken Dawning 5000A supercomputer for
20
example, the system can achieve ESE as high as 49% and PUE within best practice
21
scenario of 1.44. At the optimal design, cooling power consumption only accounts for
22
16%. Power consumption devoted to running the IT equipment is improved from 60%
23
to 67%.
24
Keywords: Energy saving; Supercomputer; Spray cooling; Multi-nozzle array;
25
Absorption chiller; Energy efficiency.
Corresponding author. Tel./Fax: +86 551 63600305. E-mail address:
[email protected] 1
ACCEPTED MANUSCRIPT 26 27
Nomenclature
28
C
specific heat, kJ/(kg K)
29
COP
coefficient of performance
30
CLF
cooling load factor
31
CPP
cost payback period, year
32
G
mass flux of spray droplets, kg/(m2s)
33
h
enthalpies, kJ/kg
34
HEG
heat exchanger in generator
35
HEE
heat exchanger in evaporator
36
HP
high pressure
37
HPA
high pressure absorber
38
HPG
high pressure generator
39
HPHE
high pressure solution heat exchanger
40
LP
low pressure
41
LPA
low pressure absorber
42
LPG
low pressure generator
43
LPHE
low pressure solution heat exchanger
44
m
mass flow rate, kg/s
45
Nu
Nusselt number
46
Pr
Prantle number
47
PUE
power usage effectiveness
48
Q
heat flow, kW
49
Re
Reynolds number
50
T
temperature, oC
51
We
Webber number
52
W
53
x
power consumption, kW mass concentration of LiBr solution 2
ACCEPTED MANUSCRIPT 54 55
Greek letters
56
λ
57
ρ
density, kg/m3
58
dimensionless temperature
heat conductivity, W/(m K)
59 60
Subscrips
61
A
62
ac
air conditioner
63
chw
chilled water
64
cool
cooling system
65
cw
cooling water
66
C
condenser
67
drop
droplet
68
E
evaporator
69
film
water film on heating surface
70
IT
IT equipment
71
in
inlet
72
out
outlet
73
S
strong solution
74
sc
spray cooling
75
sat
saturation
76
tower cooling tower
77
W
weak solution
78
wc
water-cooled cabinet
absorber
79 80 81
1. Introduction The increasing demand for high-performance computing has resulted in a 3
ACCEPTED MANUSCRIPT 82
dramatic increase of energy consumption as well as high heat flux dissipation density
83
in supercomputer center. It was estimated that data centers are responsible for nearly
84
2% of the worldwide total electricity usage [1]. In 2009, China's data center consumed
85
around 36 billion kWh, which accounts for 1% of China’s total electricity
86
consumption. In 2011, electricity consumption of China's data center has increased to
87
50 billion kWh [2]. Almost 40% of this energy consumption is spent to operate the
88
cooling systems [3], resulting in a significant energy waste and making it very
89
important to minimize the energy consumption of the cooling system. Consequently, a
90
more rational energy management and a more efficient cooling method are in urgent
91
requirement.
92
Generally, liquid cooling can provide higher cooling performance than air
93
cooling [4,5]. Single phase liquid cooling such as forced convection [6], microchannel
94
[7], jet impingement [8] and spray cooling [9-11] has become an unavoidable and
95
effective alternative to dissipate high heat flux density of electronic components.
96
Compared with other liquid cooling methods, spray cooling has numerous advantages
97
such as high heat flux removal capacity, low coolant mass flux, low temperature
98
difference, and so on [9-11]. Electronic components showed higher reliability and
99
lower temperature after using spray cooling technology. At present, spray cooling has
100
been applied in the Cray X1 supercomputer successfully [12]. Shedd et al. [13,14]
101
conducted experiments to cool a large area of 70mm×70mm and studied the cooling
102
characteristics of various nozzle array arrangements. Cheng et al. [15] established
103
integrated spray cooling system in a compact spray chamber to study the cooling
104
performance of larger area surface. Zhang et al. [16,17] designed a novel plug-chip
105
spray cooling enclosure to cool the integrated electronic system and studied the
106
effects of inclination angle and flow rate on spray cooling performance.
107
Usually, spray cooling system operates at two modes: open-loop and closed-
108
loop. In open-loop operation, cooling water is supplied continually and the waste
109
water is discharged directly, which not only leads to a huge requirement of water 4
ACCEPTED MANUSCRIPT 110
consumption but also results in a significant amount of energy waste. In closed-loop
111
operation, cooling water is recirculated in the system, thus the above problems can be
112
avoided. However, in order to cool the recycle water, additional cooling devices such
113
as cooling towers and condensers are needed, which will lead to unnecessary energy
114
consumption and result in low energy efficiency.
115
To solve above problems, absorption chiller is adopted in this paper to reuse and
116
cool the recycle water of spray cooling system. Many researchers have proved the
117
economic potential and energy efficiency of waste heat driven absorption chiller [18-
118
20]. Regarding to the maximum allowable junction temperature of electronic
119
components, which is no more than 85℃ in most cases [21], the highest spray
120
cooling outlet water temperature is no more than 85℃. Since NH3/H2O absorption
121
system requires generator temperature in the range of 95 to 170℃ [22], NH3/H2O
122
working pair is not applicable here. However, this low temperature waste heat is
123
suitable for LiBr/H2O system, which operates at generator temperature in the range of
124
70 to 95℃ [22]. Thus, to better reuse this low temperature waste heat, two-stage
125
LiBr/H2O absorption chiller was proposed [23-25]. Sumathy et al. [23] found that
126
two-stage chiller could achieve slightly higher COP than single-stage system with a
127
cost reduction of about 50% at low heat source temperature of 80℃. What’s more,
128
usable temperature drop is much larger than the single-stage system. Many studies
129
have focused on two-stage absorption chiller [23-27], and most of them were applied
130
in solar collector. However, the application in data center is rare to be seen.
131
In summary, spray cooling is an efficient and powerful cooling method among
132
the existing technologies. However, the additional chillers for treating the recycle
133
water will lead to unnecessary energy consumption. Hence, in order to further
134
improve the energy efficiency of supercomputer center, a novel energy system based
135
on spray cooling system integrated with waste heat reusing absorption chiller is
136
proposed in this paper. To evaluate the energy saving effect of novel energy system,
137
power consumption and cooling arrangement of Dawning 5000A supercomputer is 5
ACCEPTED MANUSCRIPT 138
used to offer data reference. Overall modeling of novel energy system under different
139
working conditions is conducted. The effect of inlet temperature on energy saving
140
efficiency, power usage effectiveness and cooling load factor is analyzed.
141 142
2.
Integrated energy system design
143
The primary objective of this study is to improve the energy efficiency of
144
supercomputer by reducing the power consumption of cooling facilities. To achieve
145
this objective, a novel energy system based on plug-type spray cooling system
146
integrated with two-stage absorption chiller which is driven by the waste heat
147
discharged from spray cooling is proposed. For comparison, the actual operational
148
results of the original energy system in Dawning 5000A supercomputer are collected
149
from reference [28-31]. Dawning 5000A supercomputer in China is one of the top
150
supercomputer in Asia [28,29]. The details of rack numbers and cooling methods in
151
Dawning 5000A supercomputer are summarized in Table 1. There are 65 racks in the
152
Dawning 5000A system, including 42 compute racks, 10 I/O and communication
153
racks and 13 storage racks. The maximum heat load of one compute rack is 23 kW.
154
The maximum heat load of I/O and communication racks and storage racks are 45 kW
155
and 70 kW, receptivity. In total, the maximum power load of Dawning 5000A is 1081
156
kW, and the rated power load is about 800 kW. The power consumption of different
157
subsystem, including IT equipment, power supply loss, cooling system and other
158
equipment are summarized in Table 2.
159
The cooling method of original energy system in Dawning 5000A supercomputer
160
is using water-cooled cabinets supplement with air conditioners [30,31]. The water-
161
cooled cabinets are used to cool compute racks and the air conditioners are used to
162
cool the remaining racks. The water-cooled cabinet is an enclosed cabinet with a
163
closed air circulation system and a heat exchanger in it. Each compute rack is placed
164
in one water-cooled cabinet. The cooling mechanism of water-cooled cabinet is using
165
chilled water to reduce the air temperature in the enclosed cabinet and then the 6
ACCEPTED MANUSCRIPT 166
electronic components in the compute rack is cooled by air convection heat transfer.
167
Similarly, the remaining racks are cooled by air conditioners through air convection
168
heat transfer. However, the poor thermal properties of air would result in a low heat
169
transfer of air convection, a large temperature rise of air flow and a large temperature
170
gradient within the rack [3]. What’s more, the temperature of some locations can
171
reach quite a high value due to localized hot spots. Thus, the supply temperature of
172
the original system should be unnecessarily low to maintain the maximum local
173
temperature of the electronic components within the temperature limit. This will lead
174
to unnecessary energy consumption and result in low energy efficiency.
175
To improve the energy efficiency of supercomputer, the advantages of novel
176
energy system against the original energy system are summarized as follows:
177
(1) The application of plug-type spray cooling system in replacement of water-cooled
178
cabinet enables an appreciable reduction of water consumption and cooling power
179
consumption. Firstly, spray cooling could achieve high heat flux removal capacity
180
with low coolant mass flux and low temperature differences. The cold plates of
181
spray cooling system are directly mounted on the heating surface of electronic
182
components. They are in direct contact with the heating devices which could offer
183
superior performance compared to air convection. Secondly, spray cooling is able
184
to provide high cooling capacity at relatively high inlet water temperature, which
185
eliminates the use of chilled water, thus reducing the power consumption. Finally,
186
cold pates are mounted separately on different heating devices, which could
187
achieve a thermal control at individual cold plate levels. This will eliminate the
188
unnecessary overcooling in some locations and reduce the power consumption.
189
(2) The reuse of waste heat produced by spray cooling system not only improves the
190
energy utilization efficiency, but also eliminates the need of additional cooling
191
devices to cool the recycle coolant in spray cooling cycle, which in turn reduces
192
the system energy requirement.
193
(3) The integration of absorption chiller driven by spray cooling waste heat could 7
ACCEPTED MANUSCRIPT 194
produce extra cooling capacity. Thus it could replace or supplement the air
195
conditioning system and further reduce the heat load of air conditioner.
196 197
2.1 Integrated energy system description
198
As shown in Fig. 1, the novel energy system is composed of a plug-type spray
199
cooling system and a waste heat reusing absorption chiller. The former spray cooling
200
system is utilized to replace the water-cooled cabinet and cool computer racks. The
201
latter absorption chiller is used to not only reuse and cool the recycle water in spray
202
cooling system but also partially eliminate the heat load of the air conditioner. The
203
whole cooling process contains four main parts: spray cooling cycle to cool computer
204
rack, heat exchanger in generator (HEG) to reuse waste heat, absorption cooling cycle
205
driven by waste heat, heat exchanger in evaporator (HEE) to supplement air
206
conditioner.
207
Spray cooling system is applied in cooling computer racks by installing many
208
cold plates at the heating surface of each electronic component. The cold plates are
209
cooled by cold water sprayed out by nozzles. After spray cooling process, the cold
210
water becomes hot waste water. Then, the hot water is circulated to HEG to drive the
211
absorption chiller. After heat exchanging process, the cooled water return to spray
212
cooling system and continue to cool computer racks. In absorption cooling cycle,
213
water is used as refrigerant and lithium bromide is used as absorbent. Water vapor
214
generated in generator flows to the condenser and provides cooling effect in the
215
evaporator. The cooling capacity is taken away by chilled water through HEE.
216
Finally, the chilled water is circulated to the air conditioning facilities to supplement
217
air conditioner. Through using spray cooling in computer racks along with using
218
chilled water produced by absorption chiller, the heat load of air conditioner could be
219
reduced a lot or even be totally eliminated, resulting in considerable energy savings.
220 221
2.2 Plug-type spray cooling system 8
ACCEPTED MANUSCRIPT 222
As shown in Fig. 2, the plug-type spray cooling system is composed of many
223
plug-type spray chambers (only three are illustrated in Fig. 2 to simplify the cooling
224
system), a cooling water tank, a liquid pump, liquid delivery and return pipes, valves
225
and other accessories. The plug-type spray chamber is designed to install on different
226
electronic components easily and quickly. It is comprised of cold plate, plug pins,
227
multi-nozzle array and liquid distribution chamber. Cold plates of spray chambers
228
could be mounted easily and quickly on the heating surface of electronic components
229
through plug pins. Heat flux generated in electronic components are removed via cold
230
plates. To achieve this purpose, the cold plate is mounted as close as possible on the
231
heating surface and is made by high thermal conductivity copper. Each spray chamber
232
is connected to the cooling water tank through liquid delivery pipe. The spray flow
233
rate could be adjusted by the flow control value according to different cooling
234
requirements. The multi-nozzle array is composed of numerous small pressure-swirl
235
nozzles assembled uniformly in a thin plate. The spray chamber is mainly designed to
236
distribute water evenly on to the cold plate. In order to make the flow of each nozzle
237
even and to discharge waste water conveniently, the water inlet is arranged at the top
238
of spray chamber and the water outlet is arranged at the bottom of spray chamber
239
respectively.
240
During cooling process, working fluid stored in cooling water tank is pumped
241
into the liquid delivery pipe and evenly distributed to the inlet of each spray chamber.
242
In each spray chamber, water is sprayed out by multi-nozzle array and atomized into
243
tiny droplets with high velocity. Then, the high velocity droplets impinge on the cold
244
plate, remove large amount of heat and become hot waste water. Finally, the hot
245
waste water accumulates at the bottom of spray chamber and is discharged into liquid
246
return pipes through the water outlet. In order to reuse this low-grade heat of waste
247
water, the main liquid return pipe is connected to the generator of absorption chiller.
248
The hot waste water is reused as the heat source of the generator to drive the
249
absorption chiller. After heat exchange process in generator, the cooled water is 9
ACCEPTED MANUSCRIPT 250
recirculated to the cooling water tank and completes the full cooling cycle.
251 252
2.3 Two-stage absorption chiller
253
Two-stage LiBr/H2O absorption chiller is very efficient to reuse and cool the
254
recycle water of spray cooling system. As shown in Fig. 3, it is comprised of a
255
refrigerant cycle and two stages of solution cycles, namely, a high pressure (HP) stage
256
and a low pressure (LP) stage. The HP stage consists of a HP generator, a HP solution
257
heat exchanger (HPHE) and a HP absorber. Similarity, the LP stage consists of a LP
258
generator, a LP solution heat exchanger (LPHE) and a LP absorber.
259
In solution cycles, water is used as refrigerant and lithium bromide is used as the
260
absorbent. Waste water from the spray cooling system is supplied as the heat source
261
for HP and LP generators to generate water vapor from the weak solution. After the
262
evaporation of water, the remaining LiBr/H2O strong solution is precooled in the
263
solution heat exchanger before flowing back to the absorber. The water vapor
264
generated in HP generator flows to the condenser and provides cooling effect in the
265
evaporator. However, the water vapor generated in LP generator is circulated to the
266
HP absorber, absorbed by the strong solution coming from HP generator and does not
267
provide cooling effect. Then the weak solution in HP absorber is reformed and
268
pumped back to HP generator.
269
In refrigerant cycle, water vapor generated in HP generator is condensed in the
270
condenser and the condensation latent heat is removed by cooling tower. Then, the
271
condensate water coming from condenser is circulated to the evaporator through an
272
expansion valve. In the evaporator, the water evaporates and provides cooling effect
273
which is taken away by chilled water. Finally, the water vapor is recycled to the LP
274
absorber and is absorbed by the strong solution coming from the LP generator. Thus,
275
the entire closed cooling cycle is completed.
276
10
ACCEPTED MANUSCRIPT 277
3. Thermodynamic analysis of integrated energy system
278
3.1 Performance analysis of spray cooling
279
Restricted by temperature limits of electronic components, water spray cooling is
280
dominated by single-phase heat transfer. In this non-boiling regime, spray cooling
281
system performs with high operation stability and uniform heat flux distribution
282
although with limited heat dissipation capability. This heat transfer mode is suitable
283
for the thermal control of electronic components in supercomputer center which is
284
very sensitive to temperature. In order to apply this effective spray cooling system in
285
supercomputer center, experimental results and mathematical model of our previous
286
works [15-17,33-35] are adopted and briefly summarized in Appendix A and B
287
respectively. Based on these researches, spray cooling performance is analyzed.
288
To evaluate the cooling performance of spray cooling system, equivalent COP
289
(Coefficient of performance) of spray cooling (COPsc) is defined as the ratio of spray
290
cooling heat removal capacity (Qspray) to total electrical power of spray cooling system
291
(Wspray) as follows:
292
COPsc Qspray Wspray
293
A higher COPsc means higher cooling capacities with lower operating costs. Qspray can
294
be calculated based on our previous model presented in reference [33-35]. It is highly
295
dependent on working conditions, especially required thermal control temperature,
296
inlet water temperature and spray flow rate. Wspray is mainly composed of power to
297
run the water pump and power to cool recycle coolant in spray cooling cycle. In novel
298
integrated energy system, the power to cool recycle coolant is eliminated by reusing
299
the spray cooling waste heat to drive an absorption chiller. So the Wspray is equal to the
300
pump power and can be estimated based on our previous experimental results
301
presented in Appendix A.
(1)
302
For comparison, the equivalent COP of water-cooled cabinet in original
303
Dawning 5000A supercomputer (COPwc) is calculated as the ratio of water-cooled
304
cabinet cooling capacity to total power consumption of water-cooled cabinet as 11
ACCEPTED MANUSCRIPT 305
follows:
306
COPwc Qwc Wwc
(2)
307 308
3.2 Mathematical model of two-stage absorption chiller
309
To analyze the cooling performance of absorption chiller, a mathematical model
310
is established based on conservation and balance equations. The basic cycle process
311
and P-T-X diagram are shown in Fig. 4. The two-stage absorption chiller is mainly
312
composed of two generators, two absorbers, a condenser and an evaporator. To
313
simplify the model, two solution heat exchangers and pumps between generator and
314
absorber are not considered. The following assumptions are made to establish the
315
mathematical model:
316
(1) The system is in steady state. Refrigerant in generator and absorber is in
317 318 319
equilibrium state. (2) The outlet conditions of LiBr aqueous solution and refrigerant at each component are in saturation states.
320
(3) The outlet temperatures of HPG and LPG are 5℃ lower than the heat source inlet
321
temperatures. The outlet temperatures of HPA and LABS are 4℃ higher than the
322
cooling water temperature.
323 324
(4) The heat loss and pressure drop in all components are negligible. Based on above assumptions, the mass and energy equations of each component
325
are obtained as follows:
326
m
327
x
328
Q mout hout min hin
329
The energy equations of heat exchangers in each component are obtained as follows:
330
Q mC (Tin Tout )
331
The state equations of LiBr aqueous solution and saturation water are obtained as
in
in
mout
(3)
min xout mout
(4) (5)
(6)
12
ACCEPTED MANUSCRIPT 332
follows:
333
f LiBr P, T , x 0
(7)
334
f LiBr h, T , x 0
(8)
335
f water P, T 0
(9)
336
f water h, T 0
(10)
337
where, m, x, p, T, h are the mass flow rates, mass concentrations, pressures,
338
temperatures and enthalpies of working fluids, respectively. The enthalpies can be
339
calculated by the corresponding temperature, concentration, and pressure according to
340
correlations given in literatures [36,37].
341
Thermal COP (COPthernal) is defined as the ratio between heat flow in evaporator
342
and heat flow in generator. It is used to evaluate the utilization efficiency of heat
343
source as follows:
344
COPthermal QE () QLPG QHPG
345
Electrical COP (COPelectric) is defined as the ratio between the cooling capacity and
346
the power consumption of absorption chiller. It is used to evaluate the energy
347
efficiency of absorption cooling system. The power consumptions of absorption
348
chiller is composed of solution pump power consumption and cooling tower power
349
consumption. The power consumption of solution pump is negligible compares to
350
other components[38]. However, the electric fan and water pump equipped in cooling
351
tower cannot be neglected. So the COPelectric can be calculated as follows:
352
COPelectric QE Wtower
353
where, Wtower can be calculated according to the COP of cooling tower [39]. The
354
cooling demand of cooling tower (Qtower) is calculated by the sum of heat flow in
355
absorber and condenser.
356
Qtower QC QA
(11)
(12)
(13)
357 13
ACCEPTED MANUSCRIPT 358
3.3 Comprehensive performance analysis
359
Overall simulation of novel integrated energy system is conducted based on
360
spray cooling model and absorption chiller model. The spray cooling inlet
361
temperature has a great effect on the cooling capacity and outlet temperature of spray
362
cooling system. The outlet water of spray cooling system is reused to drive the
363
absorption chiller, so the spray cooling characteristics will influence the absorption
364
cooling performance. As the water cooled by absorption chiller is recirculated to
365
spray cooling system, the absorption chiller will in turn influence the spray cooling
366
performance.
367
In this study, the focus is to minimize the power consumption of cooling system
368
(Wcool) and increase the energy efficiency of Dawning 5000A supercomputer. To
369
better present the energy efficiency improvement of the novel system, the evaluation
370
indicators such as energy saving efficiency (ESE), power usage effectiveness (PUE)
371
and cooling load factor (CLF) are introduced.
372
In order to understand the energy saving effect of novel energy system, energy
373
saving efficiency (ESE) is defined as the ratio between power consumption of novel
374
energy system and original energy system as follows:
375
ESE 1
Wcool of new cooling system Wcool of original cooling system
(14)
376
The most widely accepted evaluation standard is PUE. It is defined as the ratio
377
between total power consumption of supercomputer and the power required to run IT
378
equipment. PUE is used to evaluate the energy efficiency of a supercomputer and can
379
be calculated as follows:
380
PUE
381
where, Wtotal is composed of IT equipment power consumption (WIT), power supply
382
loss of power distribution unit (Wloss), power used to operate the cooling system
383
(Wcool) and power consumption of other assistant equipments (Welse).
Total electrical power consumption Wtotal IT equipment power consumption WIT
14
(15)
ACCEPTED MANUSCRIPT 384
Wtotal WIT Wloss Wcool Welse
385
PUE represents the fraction of total electrical power consumption that devoted to
386
running IT equipment. Lower PUE value means higher energy efficiency because it
387
means more energy consumed in supercomputer is actually devoted to computing IT
388
equipment. According to the reports of Environmental Protection Agency [40],
389
current data centers have an average PUE of 2.0. By using alternative efficiency
390
scenario assumptions, lower PUE value could be achieved bellow 1.7 in the Improved
391
Operation Scenario and bellow 1.5 in the Best Practice Scenario. To achieve lower
392
PUE, efforts should be made to maximize the power devoted to IT equipment such as
393
using more efficient microprocessors, servers and storage devices, and to minimize
394
the power consumption of ancillary infrastructures such as using more efficient power
395
distribution systems and cooling systems.
396
(16)
Cooling Load Factor (CLF) is defined as the ratio between power used to operate
397
the cooling system and power required to run IT equipment as follows:
398
CLF
399
CLF represents the power consumption devoted to cool one unit IT load. Thus, the
400
lower the CLF is, the more efficient is the cooling system.
Cooling system power consumption Wcool IT equipment power consumption WIT
(17)
401
In the novel integrated energy system, Wcool is mainly composed of power
402
consumption caused by spray cooling system (Wsc), air conditioner (Wac), and cooling
403
tower in absorption chiller (Wtower).
404
Wcool Wsc Wac Wtower
405
where, Wsc can be calculated based on the heat removal requirement of spray cooling
406
system in supercomputer (Qsc) and the equivalent COP of spray cooling system
407
(COPsc) as follows:
408
Wsc Qsc COPsc
409
where, Qsc is equal to the heat load of computer racks because the spray cooling
(18)
(19)
15
ACCEPTED MANUSCRIPT 410
system is used to replace the water-cooled cabinet and cool computer racks. The heat
411
loads of Dawning 5000A supercomputer are summarized in Table 1. COPsc is
412
calculated based on our previous experimental and numerical results as explained in
413
section 3.1.
414
In novel integrated cooling system, Wac is much lower than that in original
415
energy system, since the total heat load of air conditioner is reduced by the
416
supplemental absorption chiller. So Wac can be calculated as follows:
417
Wac (Qac Qev ) COPac
418
(20)
Wtower is the power consumption of cooling tower in absorption chiller. It can be
419
calculated according to the COP of cooling tower [38] as follows:
420
Wtower Qtower COPtower
421
where, the cooling demand of cooling tower (Qtower) is calculated by Eq.13. It is the
422
sum of heat flow in absorber and condenser as analyzed in section 3.2.
(21)
423 424
4. Results and discussion
425
4.1 Spray cooling performance
426
As inlet water temperature is the key parameter which affects spray cooling
427
performance, the effect of inlet water temperature on spray cooling outlet water
428
temperature, heat removal capacity and COPsc is studied. Regarding to the
429
temperature limits (85℃ in most cases) of electronic components, the thermal control
430
temperature (maximum temperature on the heating surface) of spray cooling system is
431
set at 85℃ and a lower thermal control temperature of 80℃ is also simulated for
432
comparison. The inlet water temperature is in the range of 40 to 80℃. Through
433
simulation, the outlet water temperature range of 75-83.5℃ is obtained at thermal
434
control temperature of 85℃ as shown in Fig. 5. This temperature range is suitable for
435
LiBr/H2O absorption chiller, which operates at generator temperature in the range of
436
70 to 95℃[22]. The heat removal capacity results at different thermal control
437
temperatures are also shown in Fig. 5. It is found that the inlet water temperature has a 16
ACCEPTED MANUSCRIPT 438
great influence on spray cooling heat transfer performance. With the increase of inlet
439
water temperature, the outlet water temperature increases almost proportionally and
440
finally approaches close to the thermal control temperature. However, the heat
441
removal capacity decreases proportionally with the increase of inlet water
442
temperature. Since the inlet water temperature is equivalent to the outlet temperature
443
of HEG in absorption chiller, the cooling performance of spray cooling system is
444
highly dependant on the performance of absorption chiller. Meanwhile, the outlet
445
water of spray cooling system is the heat source of absorption chiller. Thus, the
446
performance of spray cooling system will influence the cooling performance of
447
absorption chiller as well. Moreover, higher thermal control temperature results in
448
higher heat removal capacity and higher outlet water temperature, which is beneficial
449
to not only the spray cooling system but also the absorption chiller.
450
Fig. 6 shows the effect of inlet water temperature on COPsc results under
451
different thermal control temperatures. It is found that the COPsc decreases sharply
452
with the increase of inlet water temperature. This is because the increase of inlet water
453
temperature will greatly decrease the cooling capacity of spray cooling, however the
454
power consumption is almost independent of inlet water temperature. For comparison,
455
the COPwc of original cooling system is calculated by Eq.2 and the COPwc value of
456
4.8 is marked in Fig.6. At thermal control temperature of 85℃, all the COPsc results
457
are larger than COPwc. At thermal control temperature of 80℃, the COPsc are larger
458
than COPwc when the inlet temperature is lower than 75℃.This indicates that the
459
spray cooling system is always superior to the original water-cooled cabinets when
460
thermal control temperature is larger than 85℃. The comparison of COP results
461
shows that the plug-type spray cooling system is much more efficient than the water-
462
cooled cabinet system at appropriate conditions.
463 464 465
4.2 Absorption chiller performance The waste heat temperature is a key parameter affecting the absorption chiller 17
ACCEPTED MANUSCRIPT 466
performance since it is the heat source temperature of generator. It should be noted
467
that the waste heat temperature is equivalent to the outlet water temperature of spray
468
cooling. According to the spray cooling analysis in section 4.1, the temperature range
469
of waste heat is 75-83.5℃. To study the effect of waste heat temperature on
470
absorption chiller performance, the simulation parameters are set according to
471
reference [41,42] as listed in Table 3. The cooling capacity, power consumption and
472
COP results are shown in Fig. 7 and 8.
473
Fig. 7 shows the effect of waste heat temperature on cooling capacity and power
474
consumption. It is found that the two-stage LiBr absorption chiller cannot be operated
475
when the waste heat temperature is lower than 63℃. Thus, to ensure the effective
476
operation of absorption chiller, the outlet water temperature of spray cooling system
477
should be higher than 63℃. With the increase of waste heat temperature, the cooling
478
capacity increases rapidly at first, and then increase slowly. But when the waste heat
479
temperature is larger than 80℃, the increase of cooling capacity becomes very small.
480
Since the higher waste heat temperature (corresponds to a higher outlet temperature of
481
spray cooling system) results in lower spray cooling capacity, waste heat with
482
temperature larger than 80℃ is not beneficial to the overall cooling system. The
483
cooling capacity is as high as 80kW when the waste heat temperature reaches 80℃
484
and the corresponding power consumption is about 38kW. This amount of cooling
485
capacity is able to eliminate the heat load of air conditioners in storage racks.
486
Fig.8 shows the effect of waste heat temperature on thermal COP and electrical
487
COP of absorption chiller. The same variation trend of COP results with cooling
488
capacity is also shown in the figure. With the increase of waste heat temperature, both
489
the thermal COP and electrical COP increase rapidly at first. But when the waste heat
490
temperature exceeds 80℃, the thermal COP and electrical COP reach 0.33 and 2.1
491
respectively and almost no longer increase. This indicates that the absorption chiller
492
experiences better cooling performance with a higher waste heat temperature, since
493
more cooling capacity can be achieved under this condition. In conclusion, to obtain 18
ACCEPTED MANUSCRIPT 494
high COP values, it is necessary to operate the generator at higher temperature.
495
However, the further increase of waste heat temperature will decrease the cooling
496
performance of spray cooling system. Thus, the best temperature range of waste heat
497
is between 75-80℃ taking into consideration the optimization of overall integrated
498
cooling system. Regarding to the waste heat temperature range of 75-83.5℃, the
499
cooling capacity, thermal COP and electrical COP of absorption chiller is about
500
80kW, 0.33 and 2.1 respectively. This proves that the performance of absorption
501
chiller is excellent in our novel energy system.
502 503
4.3 Comprehensive performance of integrated energy system
504
In order to better present the energy efficiency improvement of our novel
505
integrated energy system, a comparison study between the original energy system and
506
novel energy system is conducted. In the simulation, the configurations of spray
507
cooling system such as water temperature, flow rate and cold plate number are listed
508
in Table 4. As the spray cooling inlet water temperature has a great effect on the novel
509
integrated energy system, the comprehensive performance of the novel system is
510
evaluated as a function of the spray cooling inlet water temperature under different
511
working conditions.
512
Fig. 9 shows the effect of spray cooling inlet water temperature on cooling
513
system power consumption (Wcool) and energy saving efficiency (ESE) in winter.
514
With the increase of spray cooling inlet temperature, Wcool decreases a lot at first,
515
reaches the lowest value of 155kW at inlet temperature of 55℃, and then increases
516
rapidly. This indicates that an optimal inlet temperature exists at which the lowest
517
Wcool is obtained. Fig. 9 also shows that the ESE increases with the increase of inlet
518
temperature at first, and then decrease when the inlet temperature exceeds 55℃. The
519
maximum ESE of 49% is obtained at inlet temperature of 55℃. This non-
520
monotone effect is caused by the interaction between spray cooling system and
521
absorption chiller. As explained in section 4.1 and 4.2, with the increase of inlet water 19
ACCEPTED MANUSCRIPT 522
temperature, the outlet water temperature of spray cooling system increases but
523
cooling capacity decreases. Since the outlet water of spray cooling system is the heat
524
source of absorption chiller, the cooling capacity of absorption chiller increases
525
sharply with the increase of inlet water temperature at first. As the increase effect of
526
absorption chiller is stronger than the decrease effect of spray cooling system at lower
527
temperatures, the ESE increases at first. With the further increase of inlet water
528
temperature, the spray cooling capacity continues increasing but the cooling capacity
529
of absorption chiller almost no longer increase. So the ESE begins to decrease.
530
Fig. 10 shows the effect of spray cooling inlet water temperature on power usage
531
effectiveness (PUE) and cooling load factor (CLF) in winter. Similar to Fig. 9, the
532
PUE and CLF values of novel system decrease at first, and then increase with the
533
increase of inlet temperature. The lowest PUE and CLF values of 1.44 and 0.22 are
534
obtained at inlet temperature of 55℃. For comparison, PUE and CLF values of the
535
original supercomputer system (PUEoriginal, CLForiginal) in winter are also marked in the
536
figure. It is found that no matter how the inlet temperature increase, the PUE and CLF
537
values of novel system are always much lower than the original system. All the PUE
538
and CLF results of novel system are better than the original system with inlet
539
temperature range from 40 to 70℃. According to reference [40], PUEoriginal value of
540
1.66 is in the degree of Improved Operation Scenario. However, the novel system
541
could achieve PUE of 1.44 within best practice scenario under appropriate conditions.
542
According to above analysis, the comparison results between original energy
543
system and novel energy system at optimal design are listed in Table 5. It is surprising
544
that although the PUE of original system has been low enough, the novel system
545
could further reduce the PUE to a level of Best Practice Scenario [40]. What’s more,
546
by using the novel system, total power consumption devoted to operate IT equipment
547
is improved from 60% to 69%, which means a high level of energy efficiency. Power
548
consumption of cooling facilities is reduced from 27% to 16%, which means a high
549
level of energy saving. To further prove the reliability and energy efficiency of the 20
ACCEPTED MANUSCRIPT 550
novel energy system, we have conducted another case study at thermal control
551
temperature of 80℃. The power consumption and energy efficiency results at this
552
case are also listed in Table 5. Although a lower and stricter thermal control
553
temperature will increase the power consumption of cooling system, the ESE is still as
554
high as 40%. This proves the energy saving effect of the novel energy system.
555
In order to evaluate the energy efficiency of novel system at different working
556
conditions, the performance comparison of different seasons during one year is
557
conducted between novel system and original system. The performance variation of
558
original system is listed in Table 2. According to above analysis, the performance of
559
novel system at the optimal inlet temperature over four seasons is shown in Fig. 11-
560
12. Fig. 11 illustrates the comparison of Wcool between novel and original systems in
561
different seasons. It is found that Wcool is lowest in winter and highest in summer. For
562
both systems, the power consumption in summer is about 30% higher than that in
563
winter. In summer, due to high ambient temperature, the power consumption of
564
cooling system is much higher than that in other seasons. Compared with original
565
system, novel system could reduce power consumption of about 49% in winter, 49%
566
in spring and autumn, and 48% in summer. This indicates that the energy saving
567
effect of novel system is remarkable in all seasons. Fig. 12 shows the comparison of
568
PUE between novel and original systems in different seasons. For both systems, PUE
569
value in summer is very close to that in other seasons. In addition, compared with
570
original system, novel system could reduce PUE below 1.5 to best practice scenario in
571
all seasons. This proves that the novel cooling system is superior to original system all
572
the year round.
573 574
4.4 Simple economic analysis of integrated energy system
575
A simple economic analysis is performed on the novel energy system to provide
576
more insights into the application potential of the novel system. The initial investment
577
cost and operation cost of novel energy system and original energy system are listed 21
ACCEPTED MANUSCRIPT 578
in Table 6. In economic analysis, the total cooling capacity of both system is 1081kW.
579
For novel system, the cooling capacity of spray cooling system, absorption chiller and
580
air conditioners are 966 kW, 80kW and 35kW, respectively. For original system, the
581
cooling capacity of water-cooled cabinets and air conditioners are 966 kW and
582
115kW respectively. For novel energy system, the largest cost is the multi-nozzle
583
array in spray cooling system. The multi-nozzle arrays are still specialty product at
584
present. They are customized and fabricated commercially, so the price is quite high.
585
As the maximum cooling load of spray cooling system is as high as 966kW, the
586
demand of multi-nozzle arrays, cold plates, water tanks, pumps, pipes and other
587
additional components is increased dramatically. Thus, the cost is increased
588
substantially. The absorption chiller used in this paper is more complex than
589
commercial air conditioner, so its price is consequently much higher. Various
590
additional costs are also listed in Table 6. It is found that the total cost of the novel
591
system is 325,690 dollars, while the total cost of original system is 101,200 dollars.
592
Although the novel system costs 3 times of the original system, a large amount of
593
power consumption savings caused by novel system could lower the operation cost
594
greatly. The cost payback period (CPP) can be calculated as follows:
595
CPP
596
Through analysis, a payback period of 1.5 years can be achieved, which proves the
597
application potential of the novel energy system.
Total cost of novel system-Total cost of original system Operation cost of original system- Operation cost of novel system
(22)
598 599
5. Conclusions
600
In order to improve the energy efficiency of supercomputer center, a novel
601
energy system based on spray cooling was proposed in this paper. The novel system
602
was composed of a plug-type spray cooling system and a waste heat reusing
603
absorption chiller. Overall simulation of the novel energy system was conducted
604
based on spray cooling model and absorption chiller model. Energy saving evaluation 22
ACCEPTED MANUSCRIPT 605
was compared with the original energy system of Dawning 5000A supercomputer
606
system. The energy saving efficiency (ESE), power usage effectiveness (PUE) and
607
cooling load factor (CLF) under different working conditions were analyzed. The key
608
findings can be summarized as follows:
609
(1) Overall simulation results showed that the novel energy system is superior to
610
original energy system of dawning 5000A supercomputer in all seasons. The
611
novel system could achieve ESE as high as 49% and PUE within best practice
612
scenario of 1.44.
613
(2) The energy saving effect is strongly affected by inlet water temperature of spray
614
cooling. With the increase of inlet water temperature, the spray cooling capacity
615
decreases while the absorption cooling capacity increases.
616
(3) There exists an optimal inlet temperature (e.g. 55℃ at thermal control
617
temperature of 85℃), at which the lowest cooling power consumption, PUE, CLF
618
and highest ESE can be achieved. At the optimal design, cooling power
619
consumption of novel energy system only accounts for 16% in the total power
620
consumption. Power consumption that devoted to running the IT equipment is
621
improved from 60% to 69%.
622
(4) Plug-type spray cooling system is much more efficient than water-cooled cabinet
623
adopted in Dawning 5000A supercomputer. The spray cooling capacity increases
624
with the increase of inlet water temperature and thermal control temperature.
625
Maximum COP value of 18 is achieved at inlet temperature of 40℃ and thermal
626
control temperature of 85℃.
627
(5) Two-stage LiBr/H2O absorption chiller could make good use of low temperature
628
waste heat discharged by spray cooling system. The cooling capacity, thermal
629
COP and electrical COP increase with the increase of waste heat temperature,
630
reach maximum value of 80kW, 0.33 and 2.1 respectively, and no longer increase
631
when waste heat temperature is higher than 75℃.
632 23
ACCEPTED MANUSCRIPT 633 634
Conflicts of interest There are no conflicts of interest to declare.
635 636 637 638
Acknowledgement The authors would like to thank the National Science Foundation of China (Grant No. 51376169) for the financial support.
639 640
References
641
[1] Demetriou D W, Kamath V, Mahaney H. A Holistic Evaluation of Data Center
642
Water Cooling Total Cost of Ownership. J Electron Packaging 2016, 138(1): 010912.
643
[2] Sun W C, Huang Y. Data center energy consumption model analysis and research.
644
Shanghai Energy Conserv 2014 (1): 29-32.Chinese
645
[3] Li Z, Kandlikar S G. Current status and future trends in data-center cooling
646
technologies. Heat Transfer Eng 2015, 36(6): 523-538.
647
[4] Zimmermann S, Meijer I, Tiwari M K, et al. Aquasar: A hot water cooled data
648
center with direct energy reuse. Energy 2012, 43(1): 237-245.
649
[5] Ellsworth M J, Iyengar M K. Energy efficiency analyses and comparison of air
650
and water cooled high performance servers. Proceedings of IPACK, SHTC and ICES,
651
San Francisco, 2009: 907-914.
652
[6] Daungthongsuk W, Wongwises S. A critical review of convective heat transfer of
653
nanofluids. Renew Sust Energy Rev 2007, 11(5): 797-817.
654
[7] Rezania A, Rosendahl L A. Thermal effect of a thermoelectric generator on
655
parallel microchannel heat sink. Energy 2012, 37(1): 220-227.
656
[8] Hosain M L, Fdhila R B, Daneryd A. Heat transfer by liquid jets impinging on a
657
hot flat surface. Appl Energy 2016, 164: 934-943.
658
[9] Kandlikar S G, Bapat A V. Evaluation of jet impingement, spray and
659
microchannel chip cooling options for high heat flux removal. Heat Transfer Eng
660
2007, 28(11): 911-923.
661
[10] Kim J. Spray cooling heat transfer: the state of the art. Int J Heat Fluid Fl 2007, 24
ACCEPTED MANUSCRIPT 662
28(4): 753-767.
663
[11] Silk E A, Golliher E L, Selvam R P. Spray cooling heat transfer: technology
664
overview and assessment of future challenges for micro-gravity application. Energy
665
Convers Manage 2008, 49(3): 453-468.
666
[12] Shedd T A. Next generation spray cooling: high heat flux management in
667
compact spaces. Heat Transfer Eng 2007, 28(2): 87-92.
668
[13] Pautsch A G, Shedd T A. Spray impingement cooling with single-and multiple-
669
nozzle arrays. Part I: Heat transfer data using FC-72. Int J Heat Mass Transfer 2005,
670
48(15): 3167-3175.
671
[14] Shedd T A, Pautsch A G. Spray impingement cooling with single-and multiple-
672
nozzle arrays. Part II: Visualization and empirical models. Int J Heat Mass Transfer
673
2005, 48(15): 3176-3184.
674
[15] Cheng W L, Zhang W W, Jiang L J, et al. Experimental investigation of large
675
area spray cooling with compact chamber in the non-boiling regime. Appl Therm Eng
676
2015, 80: 160-167.
677
[16] Zhang W W, Cheng W L, Shao S D, et al. Integrated thermal control and system
678
assessment in plug-chip spray cooling enclosure. Appl Therm Eng 2016, 108: 104-
679
114.
680
[17] Cheng W L, Zhang W W, Shao S D, et al. Effects of inclination angle on plug-
681
chip spray cooling in integrated enclosure. Appl Therm Eng 2015, 91: 202-209.
682
[18] Wang F J, Chiou J S, Wu P C. Economic feasibility of waste heat to power
683
conversion. Appl Energy 2007, 84(4): 442-454.
684
[19] Haywood A, Sherbeck J, Phelan P, et al. Thermodynamic feasibility of
685
harvesting data center waste heat to drive an absorption chiller. Energy Convers
686
Manage 2012, 58: 26-34.
687
[20] Javani N, Dincer I, Naterer G F. Thermodynamic analysis of waste heat recovery
688
for cooling systems in hybrid and electric vehicles. Energy 2012, 46(1): 109-116.
689
[21] Capozzoli A, Primiceri G. Cooling Systems in Data Centers: State of Art and 25
ACCEPTED MANUSCRIPT 690
Emerging Technologies. Energy Procedia 2015, 83: 484-493.
691
[22] Florides G A, Kalogirou S A, Tassou S A, et al. Modelling and simulation of an
692
absorption solar cooling system for Cyprus. Sol energy 2002, 72(1): 43-51.
693
[23] Sumathy K, Huang Z C, Li Z F. Solar absorption cooling with low grade heat
694
source-a strategy of development in South China. Sol energy 2002, 72(2): 155-165.
695
[24] Du S, Wang R Z, Lin P, et al. Experimental studies on an air-cooled two-stage
696
NH3-H2O solar absorption air-conditioning prototype. Energy 2012, 45(1): 581-587.
697
[25] Lin P, Wang R Z, Xia Z Z. Numerical investigation of a two-stage air-cooled
698
absorption refrigeration system for solar cooling: cycle analysis and absorption
699
cooling performances. Renew Energy 2011, 36(5): 1401-1412.
700
[26] Siddiqui M A. Economic analysis of two stage dual fluid absorption cycle for
701
optimizing generator temperatures. Energy Convers Manage 2001, 42(4): 407-437.
702
[27] Kim D S, Ferreira C A I. Air-cooled LiBr-water absorption chillers for solar air
703
conditioning in extremely hot weathers. Energy Convers Manage 2009, 50(4): 1018-
704
1025.
705
[28] Sun N, Kahaner D, Chen D. High-performance computing in China: research and
706
applications. Int J High Perform C 2010, 24(4): 363-409.
707
[29] Zhang Y, Sun J, Yuan G, et al. Perspectives of China’s HPC system
708
development: a view from the 2009 China HPC TOP100 list. Front Comput Sci China
709
2010, 4(4): 437-444.
710
[30] Chen Y J, Zhang Y Q, Huang K Z, et al. Energy Efficiency Analysis of Shanghai
711
Supercomputing Center. Elec Appl 2010, 29(18):18-21. Chinese
712
[31] Zhang Y Q, Chen Y Q, Huang K Z, et al. Analysis of energy efficiency
713
improvement of supercomputing center in Shanghai. Sci times 2010 (12): 299-303.
714
Chinese
715
[32] Figueredo G R, Bourouis M, Coronas A. Thermodynamic modelling of a two-
716
stage absorption chiller driven at two-temperature levels. Appl Therm Eng 2008,
717
28(2): 211-217. 26
ACCEPTED MANUSCRIPT 718
[33] Cheng W L, Han F Y, Liu Q N, et al. Experimental and theoretical investigation
719
of surface temperature non-uniformity of spray cooling. Energy 2011, 36(1): 249-257.
720
[34] Cheng W L, Han F Y, Liu Q N, et al. Spray characteristics and spray cooling
721
heat transfer in the non-boiling regime. Energy 2011, 36(5): 3399-3405.
722
[35] Zhao R, Cheng W, Liu Q, et al. Study on heat transfer performance of spray
723
cooling: model and analysis. Heat mass transfer 2010, 46(8-9): 821-829.
724
[36] Patek J, Klomfar J. A computationally effective formulation of the
725
thermodynamic properties of LiBr-H2O solutions from 273 to 500K over full
726
composition range. Int J Refrig 2006, 29(4): 566-578.
727
[37] Chua H T, Toh H K, Malek A, et al. Improved thermodynamic property fields of
728
LiBr-H2O solution. Int J Refrig 2000, 23(6): 412-429.
729
[38] Kilic M, Kaynakli O. Second law-based thermodynamic analysis of water-
730
lithium bromide absorption refrigeration system. Energy 2007, 32(8): 1505-1512.
731
[39] Hasan A, Siren K. Theoretical and computational analysis of closed wet cooling
732
towers and its applications in cooling of buildings. Energy Build 2002, 34(5): 477-
733
486.
734
[40] Brown R. Report to congress on server and data center energy efficiency: Public
735
law 109-431. Berkeley Lab 2008.
736
[41] Ma W B, Deng S M. Theoretical analysis of low-temperature hot source driven
737
two-stage LiBr/H2O absorption refrigeration system. Int J refrig 1996, 19(2): 141-146.
738
[42] Ma W B, Xia W H, Yu C B. Industrial application of the two-stage LiBr/H2O
739
absorption chiller. Refrigeration 1998, 4: 40-43. Chinese
740 741
Appendix A. Experimental results spray cooling
742
As schematized in Fig. A1, spray cooling experimental studies were conducted
743
by our previous studies [15,34]. The single-nozzle experiment and multi-nozzles
744
experiment were conducted by the works in Ref [34] and Ref [15] respectively. For
745
single nozzle spray cooling, the heat transfer correlation in non-boiling regime is as 27
ACCEPTED MANUSCRIPT 746
follows [34]:
747
Nu 0.036 Re1.04We0.28 Pr 0.51 3.02 1.53
748
Tsurf Tinlet Tsat is the dimensionless temperature. Further details on where, =()
749
dimensional analysis and correlation derivation were reported previously [34]. In this
750
correlation, Nusselt number is range from 200 to 600, Prandtl number is from 2.1 to
751
6.8 and dimensionless temperature is from 0.08 to 0.7. The correlation agrees well
752
with experimental result and the deviation is within 7%.
(A.1)
753
The heat removal capacity and heat transfer coefficient results of non-boiling
754
spray cooling were also obtained by our previous work [15,34]. Fig. A2 (a) shows the
755
single-nozzle results of Ref [34] and Fig. A2(b) shows the multi-nozzle results of Ref
756
[15]. It was found that the heat removal capacity is as high as 250W/cm2 for single
757
nozzle and as high as 80W/cm2 for multi-nozzles. This proved the high heat removal
758
potential of spray cooling. The heat removal capacity increases proportionally with
759
the increase of temperature difference (difference of surface temperature and water
760
inlet temperature) for both single and multi-nozzles. What’s more, the heat removal
761
capacity increases with the increase of spray flow rate. Compared with single-nozzle
762
spray cooling, the multi-nozzle spray cooling shows a smaller heat removal capacity
763
due to its larger surface area.
764 765
Appendix B. Mathematical model of spray cooling
766
The mathematical model of spray cooling heat transfer was fully described in our
767
previous work [33,35]. In single-phase regime, spray cooling heat transfer is
768
dominated by liquid film convection and droplets impingement. Spray cooling
769
process can be simplified as below: high-pressure working fluid is atomized through
770
nozzle and becomes tiny droplets with high velocity. The spray droplets impact on
771
heating surface continuously and form a liquid film on the heating surface. The liquid
772
film washes the surface and cools the surface by convection. The droplet impaction
773
heat transfer (Qdrop) consists two parts: heat transfer induced by droplets crossing the 28
ACCEPTED MANUSCRIPT 774
liquid film (Qdrop,1) and heat transfer induced by the droplets hitting on the heating
775
surface (Qdrop,2). In this model, the droplets are assumed to be spherical particles and
776
the film is assumed to be viscous liquid. Then heat transfer between droplets and film
777
is as follows:
778
Q drop,1 film lfilm Nudrop Adrop (Tdrop Tfilm )
779
The heat transfer of droplet hitting the surface can be empirically evaluated using an
780
effectiveness parameter (), which is defined as the ratio of the actual heat transfer to
781
the maximum possible heat transfer. The relationship between and droplet Weber
782
number was concluded in Ref [33,35]. Then heat transfer of droplet hitting the surface
783
is as follows:
784
Q drop,2 G[C p ,l (Tw Tdrop )]
785
In order to obtain film-surface convective heat transfer, the film formation and film
786
motion are modeled based on dynamics fundamentals. The mass conservation and
787
momentum conservation equations of the film are as follows:
788
(B.1)
(B.2)
du d(lfilm ) lfilm film,i m in / Afilm d dxi d(ufilm,i lfilm ) d
ufilm,i lfilm
dufilm,i dxi
(B.3)
m in uin,i / Afilm
789
The film thickness and film velocity can be determined by these equations. Then the
790
film-surface heat transfer (Qfilm) can be expressed by an empirical correlation as
791
follows:
792
Q film liq lfilm Nufilm Afilm (Tw Tfilm )
793
Thus, the equation governing energy conservation in non-boiling spray cooling is
794
given as follows:
795
Q heating =Q drop +Q film
(B.4)
(B.5)
796
The initial droplet parameters such as mean diameter, velocity and mass flux
797
were measured by the Phase-Doppler Anemometer (PDA), and analyzed in our
798
previous work [34]. Based on Eq. (B1-B5), the spray cooling performance in non29
ACCEPTED MANUSCRIPT 799
boiling regime can be calculated through simulation procedure. The model is
800
validated by the experimental results provided in Ref [35], and a favorable
801
comparison is demonstrated with a deviation below 10%.
30
ACCEPTED MANUSCRIPT Figure captions Fig.1. Schematic diagram of integrated energy system in supercomputer Fig.2. Schematic diagram of plug-type spray cooling system Fig.3. Schematic diagram of two-stage absorption chiller Fig.4. Basic cycle process and P-T-X diagram of two-stage absorption chiller Fig.5. Effect of inlet water temperature on outlet water temperature and spray cooling heat removal capacity. Fig.6. Effect of spray cooling inlet water temperature on COPsc Fig.7. Effect of waste heat temperature on cooling capacity and power consumption of absorption chiller Fig.8. Effect of waste heat temperature on thermal COP and electrical COP of absorption chiller Fig.9. Effect of spray cooling inlet water temperature on Wcool and ESE Fig.10. Effect of spray cooling inlet water temperature on PUE and CLF Fig.11. Total power consumption of cooling system, Wcool, during one year Fig.12. Power usage effectiveness, PUE, during one year Fig.A4. Experimental setup: (a) Schematic diagram of single and multi-nozzle spray cooling. (b) Compact spray chamber and Multi-nozzle array. Fig.A5. Experimental results of multi-nozzle spray cooling capacity at different water flow rate in non-boiling regime (Results reported in previous work[15,34]).
ACCEPTED MANUSCRIPT
Fig. 1. Schematic diagram of integrated energy system in supercomputer.
ACCEPTED MANUSCRIPT
Fig. 2. Schematic diagram of plug-type spray cooling system.
ACCEPTED MANUSCRIPT
Fig. 3. Schematic diagram of two-stage absorption chiller.
ACCEPTED MANUSCRIPT
Fig.4. Basic cycle process and P-T-X diagram of two-stage absorption chiller
ACCEPTED MANUSCRIPT
90
200
85
o
85 C 2
Heat removal capacity (W/cm )
o
Outlet water temperature ( C)
o
Control temperature: 80 C Outlet temperature: Heat removal capacity:
150
80
100
75
50
70
0 40
50
60
70
80
o
Inlet water temperature ( C)
Fig.5. Effect of inlet water temperature on outlet water temperature and spray cooling heat removal capacity.
ACCEPTED MANUSCRIPT
30 o
25
Thermal control temperature: 80 C o 85 C
COPsc
20 15 10 5
COPwc=4.8
0 40
50
60
70
80
o
Inlet water temperature ( C)
Fig.6. Effect of spray cooling inlet water temperature on COPsc.
ACCEPTED MANUSCRIPT
100
50
Cooling capacity Power consumption
Cooling capacity (kW)
40
60 30 o
Chiller water outlet temperature at 7 C o Cooling water inlet temperature at 32 C
40
20
Power consumption (kW)
80
20 10 60
65
70
75
80
85
o
Waste heat temperature ( C)
Fig.7. Effect of waste heat temperature on cooling capacity and power consumption of absorption chiller.
ACCEPTED MANUSCRIPT
0.5
3
Thermal COP Electrical COP
0.4
Thermal COP
o
Chiller water outlet temperature at 7 C o Cooling water inlet temperature at 32 C
0.2
1
Electrical COP
2 0.3
0.1
0.0
0 60
65
70
75
80
85
o
Waste heat temperature ( C)
Fig.8. Effect of waste heat temperature on thermal COP and electrical COP of absorption chiller.
220
200
70
In winter: Wcool ESE
60
180 50 160
140
40
Tspray,in=Tg,out Tspray,out=Tg,in
30
Energy saving efficiency (%)
Wcool of integrated cooling system (kW)
ACCEPTED MANUSCRIPT
120 50
55
60
65
70 o
Spray cooling inlet water temperature ( C)
Fig.9. Effect of spray cooling inlet water temperature on Wcool and ESE.
ACCEPTED MANUSCRIPT
0.5
PUEoriginal=1.66
CLForiginal=0.44
1.6
0.4
Tspray,in=Tg,out Tspray,out=Tg,in
1.5
0.3
In winter: PUE CLF
1.4
0.2
1.3
Cooling Load Factor (CLF)
Power usage effectiveness (PUE)
1.7
0.1 50
55
60
65
70 o
Spray cooling inlet water temperature ( C)
Fig.10. Effect of spray cooling inlet water temperature on PUE and CLF.
ACCEPTED MANUSCRIPT
500 o
Wcool (kW)
400
Spray cooling inlet water temperature: 55 C Wcool of integrated cooling system Wcool of original cooling system
300
200
100
0
Winter
Spring/autum
Summer
Four seasons in one year
Fig.11. Total power consumption of cooling system, Wcool, during one year
ACCEPTED MANUSCRIPT
2.5
Power usage effectiveness (PUE)
o
2.0
Spray cooling inlet water temperature: 55 C PUE of integrated cooling system PUE of original cooling system
1.5
1.0
0.5
0.0
Winter
Spring/autum
Summer
Four seasons in one year
Fig.12. Power usage effectiveness, PUE, during one year
ACCEPTED MANUSCRIPT
Fig.A4. Experimental setup: (a) Schematic diagram of single and multi-nozzle spray cooling. (b) Compact spray chamber and Multi-nozzle array.
200
7 6 5
100
4 0
0
10
20
30
40
50
o
60
Temperature difference, Tsurf-Tinlet, ( C)
(a) Single-nozzle results [34]
3 70
Multi-nozzle spray cooling results[15]: 2 Heating surface area of 9 cm Multi-nozzle plate composed of 8 nozzles
6
Flow rate
5
Q
h
100 15.4 L/m2s 2
12.3 L/m s 2 9.3 L/m s
4
50
3 2
0
10
20
30
40
o
Temperature difference, Tsurf-Tinlet, ( C)
50
2
2
2
8
150
Heat transfer coefficient, h, (W/cm K)
300
9
Heat removal capacity,Q, (W/cm )
10
Single-nozzle spray cooling results[34]: 2 Heating surface area of 1 cm Spray height: 2.3mm Flow rate Q h 3.6 L/h 4.2 L/h 5.20L/h
2
Heat removal capacity,Q, (W/cm )
400
Heat transfer coefficient, h, (W/cm K)
ACCEPTED MANUSCRIPT
(b) Multi-nozzle results [15]
Fig. A5. Experimental results of multi-nozzle spray cooling capacity at different water flow rate in non-boiling regime (Results reported in previous work[15,34]).
ACCEPTED MANUSCRIPT Figure captions Fig.A1. Experimental setup: (a) Schematic diagram of single and multi-nozzle spray cooling. (b) Compact spray chamber and Multi-nozzle array. Fig.A2. Experimental results of multi-nozzle spray cooling capacity at different water flow rate in non-boiling regime (Results reported in previous work[15,34]).
Fig.A1. Experimental setup: (a) Schematic diagram of single and multi-nozzle spray cooling. (b) Compact spray chamber and Multi-nozzle array.
200
7 6 5
100
4 0
0
10
20
30
40
50
o
60
Temperature difference, Tsurf-Tinlet, ( C)
(a) Single-nozzle results [34]
3 70
Multi-nozzle spray cooling results[15]: 2 Heating surface area of 9 cm Multi-nozzle plate composed of 8 nozzles
6
Flow rate
5
Q
h
100 15.4 L/m2s 2
12.3 L/m s 2 9.3 L/m s
4
50
3 2
0
10
20
30
40
o
Temperature difference, Tsurf-Tinlet, ( C)
50
2
2
2
8
150
Heat transfer coefficient, h, (W/cm K)
300
9
Heat removal capacity,Q, (W/cm )
10
Single-nozzle spray cooling results[34]: 2 Heating surface area of 1 cm Spray height: 2.3mm Flow rate Q h 3.6 L/h 4.2 L/h 5.20L/h
2
Heat removal capacity,Q, (W/cm )
400
Heat transfer coefficient, h, (W/cm K)
ACCEPTED MANUSCRIPT
(b) Multi-nozzle results [15]
Fig. A2. Experimental results of multi-nozzle spray cooling capacity at different water flow rate in non-boiling regime (Results reported in previous work[15,34]).
ACCEPTED MANUSCRIPT Table captions Table.1. Cooling capacity and heat load in Dawning 5000A supercomputer Table.2. Power consumption of each subsystem in Dawning 5000A supercomputer Table 3. Simulation conditions of two-stage absorption chiller Table.4. Configuration of spray cooling system in Dawning 5000A supercomputer Table.5. Comparison of original and novel system at optimal design Table 6. Cost of novel energy system and original energy system
ACCEPTED MANUSCRIPT
Table 1. Cooling capacity and heat load in Dawning 5000A supercomputer Component
Rack number
Maximum heat load
Cooling method
Compute racks
42
966 kW
Water-cooled cabinets
I/O and communication racks
10
45 kW
Air conditioners
Storage racks
13
70 kW
Air conditioners
ACCEPTED MANUSCRIPT
Table 2. Power consumption of each subsystem in Dawning 5000A supercomputer Subsystem
Description
IT equipment
Power consumption (kW) Winter
Spring/autumn
Summer
Computing system
692.2
714.4
789.2
Cooling
Water-cooled cabinet
207.3
232.6
301.1
system
Air conditioner
97.6
102.2
118.3
Power supply
Power supply loss of
loss
power distribution unit
145.7
89.2
88.6
6.6
4.1
4.1
1149.4
1142.5
1301.3
3.6℃
9.8℃
27.8℃
Else
Lightening and other equipments
Total
\
Average ambient temperature in Shanghai
ACCEPTED MANUSCRIPT
Table 3. Simulation conditions of two-stage absorption chiller Design parameters Waste heat temperature Tin
Values/Ranges 65~85℃
Chilled
Tchw,in
14℃
water
Tchw,out
7℃
Cooling
Tcw,in
32℃
water
Tcw,iout
27℃
PC
7.37 kPa
PE
0.93 kPa
ACCEPTED MANUSCRIPT
Table 4. Configuration of spray cooling system in Dawning 5000A supercomputer Parameters
Values/Ranges
Inlet cooling water temperature, Tin (℃)
40~80
Waste heat temperature, Tout (℃)
65-85
Total volume flow rate of water, Vin ( L/s)
3.85
Cold plate number per rack
4
Nozzle number per cold plate
100
Total cold plate number
168
ACCEPTED MANUSCRIPT
Table 5. Comparison of original and novel energy system at optimal design in winter Original energy system
Novel energy system Thermal control temperature 85℃
80℃
207.3 kW Spray cooling system
99.1 kW
124.5 kW
97.6 kW
Air conditioner
20.5 kW
23.2 kW
Absorption chiller
35.4 kW
34.1 kW
Power consumption
Power consumption
Water-cooled cabinet Air conditioner
Parameter
Value
Parameter
Value
Wcool/Wtotal
27%
Wcool/Wtotal
16%
18%
WIT/Wtotal
60%
WIT/Wtotal
69%
67%
PUE
1.66
PUE
1.44
1.48
CLF
0.44
CLF
0.22
0.26
ESE
0.49
0.40
ACCEPTED MANUSCRIPT
Table 6. Cost of novel energy system and original energy system Items
Components
Value
Novel energy system
Investment cost (cost per cooling capacity)
Operation cost
Cooling water tank
25$/kW
Liquid pump
40$/kW
Multi-nozzle array
200$/kW
Else
50$/kW
Cooling tower
150$/kW
Else
100$/kW
Air conditioner (35kW)
40$/kW
Total cost
325,690$
Electricity and maintenance
3500$/day
Spray cooling system (966kW)
Absorption chiller (80kW)
Original energy system
Investment cost
Operation cost Payback period
Water-cooled cabinet (966kW)
100$/kW
Air conditioner (115kW)
40$/kW
Total cost
101,200$
Electricity and maintenance
3900$/day 1.5years