Theoretical analysis on optimal configurations of heat exchanger and compressor in a two-stage compression air source heat pump system

Theoretical analysis on optimal configurations of heat exchanger and compressor in a two-stage compression air source heat pump system

Accepted Manuscript Title: Theoretical analysis on optimal configurations of heat exchanger and compressor in a two-stage compression air source heat ...

1MB Sizes 4 Downloads 87 Views

Accepted Manuscript Title: Theoretical analysis on optimal configurations of heat exchanger and compressor in a two-stage compression air source heat pump system Author: Yunxiang Li, Jianlin Yu PII: DOI: Reference:

S1359-4311(15)01395-2 http://dx.doi.org/doi: 10.1016/j.applthermaleng.2015.11.132 ATE 7429

To appear in:

Applied Thermal Engineering

Received date: Accepted date:

7-9-2015 27-11-2015

Please cite this article as: Yunxiang Li, Jianlin Yu, Theoretical analysis on optimal configurations of heat exchanger and compressor in a two-stage compression air source heat pump system, Applied Thermal Engineering (2015), http://dx.doi.org/doi: 10.1016/j.applthermaleng.2015.11.132. This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and review of the resulting proof before it is published in its final form. Please note that during the production process errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.

Theoretical analysis on optimal configurations of heat exchanger and compressor in a two-stage compression air source heat pump system Yunxiang Li, Jianlin Yu Department of Refrigeration & Cryogenic Engineering, School of Energy and Power Engineering, Xi’an Jiaotong University, Xi’an 710049, China

Highlights > Optimization of a flash tank cycle based heat pump system is conducted. >The optimal thermal conductance allocations are obtained under given conditions. >The system heating capacities are affected by thermal conductance allocation. > There exists an optimal compressor displacement ratio for optimum system COP. Abstract This paper presents an optimum system configuration analysis for a flash tank cycle (FTC) based two-stage compression air source heat pump system using a developed theoretical model with lumped parameter method. The analysis is carried out with respect to the thermal conductance allocation of total heat-exchanger inventory (condenser and evaporator) as well as the volume ratio of low-pressure compressor to high-pressure compressor in the system. The analysis results indicate that the heating coefficient of performance (COP) of the heat pump system can be maximized by optimally allocating the thermal conductance inventory of the two heat exchangers. Moreover, there also exists an optimal compressor volumetric displacement ratio, corresponding to the optimum system COP, when the cooling capacity of system is specified. The effects of main operation parameters on the configuration parameters and optimal performances have been discussed. The obtained results may provide some guides for the FTC based air source heat pump system optimization. Keywords: Air source heat pump; Performance optimization; Thermal conductance; Two-stage compression 

Corresponding author. Tel: +86-29-82668738. Fax: +86-29-82668725. Email: [email protected] 1

Page 1 of 25

Nomenclature C O P heating coefficient of performance -1

-1

c p specific heat (J kg K ) -1

h specific enthalpy (kJ kg ) -1

m mass flow rate (kg s ) P pressure (kPa)

Q heat transfer rate (kW)

r

volumetric displacement ratio of low-pressure compressor to high-pressure

compressor t

temperature (℃) -1

UA thermal conductance (kW K ) V v

volumetric displacement (m3 s-1) specific volume (m3 kg-1)

W power (kW)

Greek symbols 

adiabatic exponent

 effectiveness factor of heat exchanger  efficiency  allocation ratio

Subscripts 2

Page 2 of 25

a air c condenser side d

discharge

e evaporator side f

fluid

h

high

i

inlet

l

low intermediate

m

max

maximum

o outlet opt r

optimal

refrigerant

s isentropic v volumetric

1. Introduction Over the past years, the air source heat pumps have attracted a great deal of attention for their merits of energy-saving and environmental protection [1, 2]. But when they operate at low ambient temperatures, several problems, such as the reduction in the heating capacity and heating coefficient of performance (COP), high compressor discharge temperature, etc., cause some application limitations. In this case, the development of air source heat pumps with higher performances and wider operating temperature range has become a major challenge. For the issues regarding performance degradation of air source heat pumps, some solutions to enhance the heating performance and reliability of the heat pump have been studied, including 3

Page 3 of 25

refrigerant injection technique, two-stage compression systems and cascade system [3-9]. The use of those methods provides more opportunities to apply air source heat pumps in cold regions. Traditionally, two-stage compression systems consisting of two individual compressors have received much attention for refrigeration applications [10-13]. However, they have also been well justified to improve the heating performance of systems for air source heat pump applications in cold climates. Neeraj et al. [14] carried out optimization studies of two-stage transcritical carbon dioxide heat pump cycles, and indicated the flash gas bypass system yields the best performance among the three two stage cycles analyzed. Arif and Hilmi [15] also conducted the second law analysis for a two-stage compression transcritical CO2 heat pump cycle, and identified the main factors that affect the two-stage compression transcritical CO2 system efficiency. Bertsch and Groll [16] investigated an air-source two-stage heat pump using R410A as the refrigerant, and experimentally verified that the heat pump is able to operate at ambient temperatures between -30 ℃ and 10 ℃ with supply water temperatures of up to 50℃. Kwon et al. [17] evaluated a two-stage compression heat pump system for district heating utilizing waste energy, and obtained the system performance characteristics under various operating conditions. Cao et al. [18] analyzed different high-temperature two-stage heat pump systems for low-grade waste heat recovery, and showed that the two-stage heat pump system with flash tank was preferred. Overall, two-stage compression systems could be a good alternative to avoid the performance deterioration of air source heat pumps in cold climates, and those relevant researches can drive their development in low temperature ambient application. For two-stage compression heat pump systems, there are two typical cycle 4

Page 4 of 25

configurations, i.e. flash tank cycle (FTC), and internal heat exchanger cycle (IHXC) [19]. Among these two cycles, the FTC has received more attention in recent years. Basically, previous researches on the FTC are mainly focused on the cycle performance improvement, component optimization or cycle control strategies. In fact, these issues are closely related to the system configurations of FTC. As is well known, the FTC system mainly consists of a flash tank,two compressors, a evaporator and a condenser. The configuration for the FTC systems is particularly involved in the parameters of compressor and heat exchangers, such as the heat exchange area or thermal conductance of heat exchangers and compressor displacement volume [19, 27], which play a key influence on overall system performance. To make effective use of the FTC, it is necessary to explore the relationship between the configuration parameters and the main performance parameters. In this paper, we present an analytical model with lumped parameter method for a FTC based air source heat pump air conditioner. In the model, heat exchanger thermal conductance inventory is considered as a constraint condition for configuring the FTC system [20]. Based on the developed model, the performance and optimum design conditions of the FTC system are analyzed in detail for different configuration parameters and operating conditions. Furthermore we analyzed the relationship of the optimal compressor volumetric displacement ratio and the optimal thermal conductance allocation at different heat exchanger thermal conductance inventory. And the influences of the different refrigerant on system optimal compressor volumetric displacement ratio are investigated. The objective of this work is to provide some theoretical guidance for the optimal design and operation of air source heat pump using the FTC systems. 2. Analytical model of the FTC system 5

Page 5 of 25

The schematic diagram of the FTC system is shown in Fig.1 (a), where the system consists of two compressors, a condenser, a flash tank, two expansion valves and an evaporator. The cycle system includes two circuits: a main refrigerant circuit and a bypass refrigerant circuit. The main circuit refrigerant flow is circulated by the low-pressure compressor through the high-pressure compressor, the condenser, the high pressure expansion valve, the flash tank, the low pressure expansion valve and the evaporator, whereas the bypass circuit flow is circulated by the flash tank through the high- pressure compressor, the condenser, the high pressure expansion valve. Fig. 1(b) shows the detailed working process of the FTC system on pressure-enthalpy diagram. In the condenser, high pressure superheated refrigerant vapor from the highpressure compressor (state 4) is cooled to the saturated or subcooled liquid (state 5) by secondary fluid (indoor air); The refrigerant liquid is expanded through the high pressure expansion valve, and then the two-phase refrigerant at an intermediate pressure (state 6) enters into the flash tank, in which it is separated into the two phase refrigerant include the saturated liquid (state 7) and saturated vapor (state 8). On the one hand, after the saturated liquid passes through the low pressure expansion valve, it is heated by outdoor air in the evaporator to be a saturated or superheated vapor (state 1) and then flows into the low-pressure compressor. On the other hand, after the saturated vapor from the flash tank mixes with the superheating refrigerant vapor (state 2) at the outlet of the low- pressure compressor, the vapor mixture (state 3) is compressed by the high- pressure compressor and then enters to the condenser. For modelling the FTC based air source heat pump system, the condenser and the evaporator were modeled by using the



-NTU method, and two compressors were

modeled based on the efficiency of method, for simulations. Furthermore the following assumptions are made: 6

Page 6 of 25

(1) Refrigerant pressure drops are neglected in the evaporator, the condenser and inlet or outlet of the compressors; (2) Mixing process of refrigerant at the outlet of the low- pressure compressor occurs at a constant intermediate pressure; (3) Refrigerant leaving from the condenser and the evaporator is saturated liquid and saturated vapor, respectively; (4) No heat losses to the environment from the system; (5) The throttling processes in the expansion valves are isenthalpic. Based on the assumptions above, the heating capacity of the condenser can be obtained as (1)

Q c   c m fc c pfc ( t c  t fci )

where m fc and c pfc are the mass flow rate and specific heat of the heated fluid in the condenser; t c is the condensing temperature, and t fci is the temperature of the fluid heated, at the inlet of the condenser;  c is the heat exchanger effectiveness of the condenser, which can be given by Eqs. (2) and (3),  c  1  exp (  U c Ac / m fc c pfc )

c 

(2)

t fco  t fci

(3)

t c  t fci

where

U c Ac

is the thermal conductance of condenser, and t fco is the temperature of

the fluid heated, at the outlet of the condenser. It should be noted that when calculating the heating capacity of the condenser using the above Eq. (1) (including Eqs. (2) and (3)), the influence of the condenser superheat section is actually neglected. However, this simplicity may be appropriate because several literatures indicate that sufficient accuracy can be achieved for screening purposes when using an



-NTU model since the inherent errors of over

predicting the conductance in the effectiveness calculations and under predicting 7

Page 7 of 25

the temperature difference in the heat exchanger calculations tend to compensate each other [21, 22]. In addition, based on the energy conservation, the heating capacity of the condenser can be also written as Q c  m rc ( h4  h5 )

(4)

where m rc is the mass flow rate of refrigerant in the condenser, h4 and h5 are refrigerant specific enthalpies of inlet and outlet of the condenser. Similarly, the heat transfer rate of the evaporator can be obtained as Q e   e m ae c pae ( t aei  t e )

(5)

and Q e  m re ( h1  h9 )

(6)

where m re and m ae are the mass flow rates of refrigerant and air of the evaporator, h9

and h1 are refrigerant specific enthalpies at the inlet and outlet of the evaporator;

t e is the evaporating temperature, and t aei is the air temperature at the inlet of the

evaporator; c p ae is the air specific heat in the evaporator,  e is the heat exchanger effectiveness of the evaporator, which can be given by Eqs. (7) and (8),  e  1  exp( U e Ae / m ae c pae )

e 

t aei  t aeo

(7) (8)

t a ei  t e

where U e Ae is the thermal conductance of the evaporator, and t aeo is the air temperature at the outlet of the evaporator. The total input power of compressors can be obtained, W



m re ( h2 s

 sl

 h1 )



m rc ( h4 s

 sh

 h3 )

(9)

where h1 and h3 are the refrigerant specific enthalpies at the inlet of the low and high- pressure compressors, respectively; h 2 s and h 4 s are the refrigerant specific enthalpies at the outlet of the low and high- pressure compressors under the isentropic 8

Page 8 of 25

processes; h3 is calculated by the energy balance as given in Eq. (10). h3  h8 q 6  h2 (1  q 6 )

(10)

where h8 is the specific enthalpy of saturated refrigerant vapor in the flash tank, and q 6 is the vapor quality of two phase refrigerant in the flash tank.

In addition, the isentropic efficiencies of the low and high- pressure compressors,  sl and  sh , can be calculated by Eqs. (11) and (12) [19],  sl  1.41(1  e  sh  1.41(1  e

where P2

P1



p 2 / p1  0.30 0.21



)  0.52 ln( p 2 / p1  1)

(11)

)  0.52 ln( p 4 / p 3  1)

(12)

p 4 / p 3  0.30 0.21

and P3 are the inlet pressures of the low and high- pressure compressors,

and P4 are the outlet pressures of the low and high- pressure compressors,

respectively. The refrigerant mass flow rates of the low and high- pressure compressors can be calculated by Eqs. (13) and (14), m re



m rc 

 vlV l v1

(13)

 vhV h

(14)

v3

where V l and V h are the volumetric displacements of the low and high- pressure compressors; v1 and v 3 are the refrigerant specific volumes at the inlet of the low and high- pressure compressors;  vl and  vh are volumetric efficiencies of the low and high- pressure compressors, which are determined by Eqs. (15) and (16) [19].  vl   0.025( p 2 / p1 )  1.02

(15)

(16) Based on the mass balance, the refrigerant mass flow rate of the high- pressure

 vh   0 .0 2 5( p 4 / p 3 )  1.02

compressor can be also written as

9

Page 9 of 25

m rc 

m re

(17)

1 q

The volumetric displacement ratio between the low- pressure compressor and the high- pressure compressor is written as r 

Vl

(18)

Vh

It is well known that the total thermal conductance is usually constrained to be finite on both the evaporator side and condenser side for a real air source heat pump system [23]. In order to maximize the performances of the system, it makes sense to consider the total thermal conductance as a design constraint, which is a fundamental design aspect in any real air source heat pump system. Thus, it is assumed that the total thermal conductance is constrained as (19)

U A  U c Ac  U e Ae  C onstant

where

UA

is the total thermal conductance. Note that for a specified

UA ,

there

should be a thermal conductance allocation ratio between two heat exchangers, which represents the configuration relationship between the two heat exchangers. The configuration relationship between the thermal conductance of the two heat exchangers will play a key influence on overall system performance. The allocation of

UA

U e Ae   U A

U c Ac  (1   )UA

between the evaporator side and condenser side is written as (20) (21)

In general, introducing the thermal conductance allocation ratio  is to examine the effect of the configuration relationship between the two heat exchangers on the system performance COP, and then try to find the optimal configuration of the two heat exchangers for obtaining a maximum COP at other 10

Page 10 of 25

given conditions. In following sections, the above model is used for analyzing the configuration optimization of a FTC based air source heat pump air conditioner (ASHPAC) system. Analyses are made with respect to specified volumetric displacements of two compressors or cooling capacity of the system. The optimum configuration parameters, including the  and r , and system performances are evaluated under given operation and constraint conditions. An outline of the calculation procedure for the solution of the above model is shown in Fig2. It applied to compute that the variations of the

and Q c with  at different

COP

UA .

The calculation procedures

of other cases are similar to those in Fig 2, and need not be repeated here. 3. Simulation results and discussion Recently, the refrigerant R32 used in commercial ASHPACs has attracted much attention due to its relative safety and good environmental friendly properties [24, 25]. And R290 has also become a promising refrigerant used in small domestic ASHPACs to replace the refrigerant R22. Hence, three kinds of refrigerants R22, R32 and R290 are selected as the working fluids of an ASHPAC system to conduct relevant system performance simulations and configuration parameter comparison among systems with different refrigerant. The simulation program is written in Fortran Language, and the required refrigerant properties are calculated by using the property subroutines of REFPROP 8.0 [26]. The relevant configuration parameters of the system are assumed as V l  8.24  10  4 kW K  1 .

3

m s

1

,

V h  4.92  10  4

3

m s

1

, and the

UA

ranging from 0.5 to 0.8

The indoor and outdoor air specific heat is assumed as

c pfc  1 0 0 5 J kg

1

K

1

c pae  1004 J kg

1

K

1

,

, respectively. Considering the FTC based ASHPACs are mainly

applied in the regions with cold climates, simulations are conducted based on winter 11

Page 11 of 25

operating condition. Hence, inlet temperature of outdoor air is assumed as t aei   7 ℃. The inlet temperature of indoor air is assumed as t fci  20 ℃. The mass flow rate of m fc  0.2

indoor and outdoor air is assumed as

kg s

1

, m ae  0.26

kg s

1

,

respectively. Fig.3 shows the variations of the

COP

and Q c with the  , at different

where the refrigerant R32 is used in the ASHPAC system. It can be seen that the

UA ,

COP

of the system first increases and then decreases with increasing  , which means that there exists a maximum

COP

at the  o p t when fixing the

UA .

Furthermore, Fig.3

shows the system COPmax increases from 3.16 to 3.52 when the UA ranges from 0.5 to 1

0.8 kW K . The main reason for this case is that larger UA could lead to a higher evaporating temperature and a lower condensing temperature, resulting in smaller heat transfer temperature difference in both evaporator and condenser. This implies the irreversible losses in the system are reduced, and hence the system with increasing COPmax

UA .

As increasing the

UA ,

increases

however, the increasing tendency of

slows down. For example, the COPmax is increased by 5% when the 1

ranges from 0.5 to 0.6 kW K , while the UA

COPmax

COPmax

UA

is only increased by 3% when the

1

ranges from 0.7 to 0.8 kW K . The results indicate that the increase of

UA

to

improve the system COP should be properly considered in association with the cost of heat exchangers. On the other hand, it is seen from the figure that the system monotonically increasing function of  at a constant increasing  , the thermal conductance of condenser

UA .

U c Ac

Qc

is a

The reason is that as decreases and that of

evaporator U e Ae increases, which leads to the increases of t c and t e eventually. In this case, the increase of t c results in the decreasing in the specific heating capacity 12

Page 12 of 25

( h4  h5 ). Meanwhile, the p m also increases (as shown in Fig. 4), which leads to the increase of m rc due to the decease of v 3 . For both reasons above, the system Q c eventually shows an increasing tendency with  . When the  is changed from 0.25 1

to 0.5, the Q c increase by 12% - 19% at the UA in the range of 0.5 - 0.8 kW K . Fig.4 shows the variations of the optimal thermal conductance allocation  o p t and the corresponding system intermediate pressure p m with increasing be found that the  o p t increases from 0.37 to 0.40 when the

UA

UA .

It can

changes from 0.5 to

0.8 kW K . Obviously, the  o p t is smaller than 0.5 at the given conditions, which 1

means that the thermal conductance of the evaporator that of the condenser

U c Ac

should be smaller than

U e Ae

. Furthermore, the  o p t increases with the

UA ,

which

means that the thermal conductance allocated at the evaporator side should be increased at a larger

UA .

These results indicate that the performances of a ASHPAC

can be maximized by proper allocating between

U e Ae

and

U c Ac

an important thermal optimization principle, because the

UA

. This allocation is is finite and is

considered to be a significant constraint parameter in the ASHPAC designing. In addition, it can be found that the p m increases from 916.6 to 1001.6 UA

kP a

when the

1

ranges from 0.5 to 0.8 kW K . This results from the effect of two aspects.

Firstly, as increasing UA, the system t e increases, but the t c decreases. Furthermore, when the  o p t increases from 0.37 to 0.40, the

U e Ae

increases, and the

U c Ac

decreases, which leads to the increase of t e and t c . In this case, the increments in t e and t c reach 3.45 ℃ and 1.24 ℃ , respectively. Correspondingly, the saturation

13

Page 13 of 25

temperature t s ( p m ) at intermediate pressure increases from 3.79 to 6.68 ℃ , as shown in Fig.5. Thus, the system p m shows an increasing tendency with rising Moreover, the p m and the t e show similar variation trend with the

UA .

UA

.

The main

reason for this is that the t e plays dominant influence on the p m compared with the t c [27].

Figs. 6 shows the variations of the

COP

and discharge temperature t d

with the  , for the single-stage and two-stage compression systems, respectively, where the refrigerant is R32 and the

UA

1

is fixed at 0.6 kW K . It can be seen

that when the  is changed from 0.25 to 0.5, the

COP

of two-stage compression

system increase by 72% - 69% over that of the single-stage compression system. Furthermore, Fig.6 shows the t d of two-stage compression system varies from 112.6 to 115.1 ℃ when the  ranges from 0.25 to 0.5. It is greatly lower than that of the single-stage compression system. When the kW K  1

, the variations of the

is 0.5, 0.7 and 0.8

UA

and t d of single-stage and two-stage

COP

compression system are similar to that in Fig. 6. To sum up, the two-stage compression system is more favorable in terms of the

COP

increase and the

reduction of the discharge temperature. Fig.7 shows the variations of the

COP

and Q c with the  at different m fc , 1

where the refrigerant is R32 and the U A is fixed at 0.6 kW K . It can be seen that the maximum

COP

that corresponds to the optimal allocation of the U A inventory

can be obtained at different m fc . The

COPmax

increases from 2.37 to 3.63 when the

m fc ranges from 0.1 to 0.3 k g s  1 . When the m fc ranges from 0.1 to 0.2 k g s  1 , the 14

Page 14 of 25

COPmax

is increased by 40%, while the COPmax is only increased by 9%, when the

m fc ranges from 0.2 to 0.3 k g s  1 . Thus, as the increase of m fc , the increasing

tendency of COPmax weakens. From the figure, it is also observed that the  o p t 1

increases from 0.32 to 0.38 when the m fc ranges from 0.1 to 0.3 k g s . Obviously, the thermal conductance allocated at the evaporator side should be increased as increasing the m fc . In addition, it can be seen that the resulting Q c increases monotonically with the  , and decreases monotonically as the m fc increases. Note that further increasing m fc does not significantly affects Q c . Overall, The variations of the optimal performance coefficient and heating capacity with respect to the m fc and  should be considered compromisingly for optimally configuring the system parameters. Fig.8 further shows the variations of the

COP

and Q c with the  at different

m ae . It can be seen that the COP curves for m ae and  are similar to those in Fig.

7. Unlike the effect of m fc , however, the Q c increases with increasing m ae at a constant x. This means that the increase of m ae can be beneficial to increasing COPmax

and Q c at the  o p t when the U A is specified. In addition, it is found that

the  o p t increases from 0.31 to 0.38, when the m ae ranges from 0.06 to 0.26 k g s . 1

Considering the analysis results in both Fig. 7 and 8, it is clear that choosing the appropriate m ae and m fc is important, when designing an optimal ASHPAC system. Fig.9 shows the variations of COPmax and  o p t with increasing t aei at different t fci , where the refrigerant is R32 and the

UA

is fixed at 0.6 kW K  1 . It

15

Page 15 of 25

can be seen that when the t aei is changed from -20 to 10 ℃ , the system COPmax is increased by 23% and 22% at the t fci of 20 and 24

℃,

respectively. Fig.9 shows

that as increasing t fci the system COPmax decreases at a constant t aei , which is due to the fact that the system t c increases with increasing t fci . From the figure, it is also observed that the  o p t decreases from 0.40 to 0.34 when the t aei ranges from -20 to 10 ℃ . It means that the thermal conductance allocated at the evaporator side should be increased when the ASHPAC systems are applied in the regions with the lower outdoor temperatures. In addition, Fig.9 shows that the  o p t has the same values for different t fci , when the t aei is specified. It means that the indoor air temperature almost has no influence on the allocation of the thermal conductance between the evaporator side and condenser side. Furthermore, simulation results show that when the t aei is changed from 10 to -20 ℃ , the discharge temperature t d at the  o p t ℃

at the t fci of 20

℃.

increases from 101.8 to 129.7

It means that when the ASHPAC system uses refrigerant

R32, the outdoor temperature cannot be lower than -20 ℃ . As seen above, the previous optimization analysis of heat exchangers configuration is conducted for specifying the volumetric displacements of two compressors. In addition to that, it is usually necessary to specify a certain cooling capacity in the design of an ASHPAC system. In this case, optimization studies for the ASHPAC system, based on its cooling capacity duty, should be performed by considering both heat exchanger and compressor volumetric displacement configurations. Thus, the optimal configurations of heat exchangers and compressor 16

Page 16 of 25

volumetric displacements are analyzed at the specified cooling capacity in the following simulations. Fig.10 shows the variations of the COPmax at the  o p t and the corresponding with increasing kW K

1

r

, where the refrigerant is R32 and the

r

r

Qe

are fixed at 0.7

, which means that there exists an

with respect to an optimum value of the

the other hand, it is seen from the figure that the function of

at a constant

r

UA

pm

COPmax when

fixing the

UA .

On

is a monotonically increasing

. Furthermore, the system optimal configuration

parameters including the  o p t , ropt and the corresponding different

and

and 2.6 k W , respectively. It can be seen that the system COPmax firstly

increases and then decreases with increasing optimal

UA

pm

C O Pm ax,o ,

p m ,o and Q c,o at

are listed in Table 1. It can be found that the  o p t increases from 0.37

UA

to 0.41 and the ropt decreases from 1.69 to 1.59 when the 0.8 kW K  1 . This means that when the

Qe

UA

increases from 0.6 to

is specified, the thermal conductance

allocated at the evaporator side should be increased at a larger

UA ,

whereas the ratio

between the volumetric displacements of both low and high-pressure compressor should be decreased. In addition, it should be mentioned that when from 0.6 to 0.8 kW K  1 , the

C O Pm ax,o

UA

increases

and p m ,o are increased by 13.9% and 2%, and

the Q c,o is decreased by 5.5% under the condition of ropt . Figs. 11 and 12 further show the variations of the COPmax at the  o p t and the corresponding the

UA

COPmax

and

Qe

and the

pm

with

r

, at the refrigerant of R22 and R290, respectively, where

are fixed at 0.7 kW K  1 and 2.6 k W . It can be seen that both the pm

curves for

r

are similar to those in Fig. 10. Thus there also 17

Page 17 of 25

exist the ro p t with respect to an optimum value of the COPmax and the corresponding optimal

pm

in the ASHPAC system using the refrigerant R22 and R290.

Furthermore, it can be found from Table.2 that the system ro p t has an equal value of 1.63, when refrigerants R32 and R290 are used in the ASHPAC system, but when the system uses the refrigerant R22, the ro p t is 1.71. It means that when the refrigerant R22 is replaced by the R32 and R290 in the ASHPAC system, the volumetric displacement ratio of low-pressure compressor to high-pressure compressor should be decreased. Table 2 further shows that the  o p t of the system using R32 and R290 are slightly less and larger than that of the system using R22, at the ro p t . Obviously, the thermal conductance allocated at the evaporator side should be decreased when the system uses refrigerant R32 to replace R22, while it should be increased when the refrigerant R290 is used in the system. Moreover, the p m ,o of the system using R32 shows an obvious increase compared with that of the system using R22. On the contrary, the system using R290 yields lower p m ,o . 4. Conclusions In the study, a theoretical model with lumped parameter method is presented for the optimization of a FTC based air source heat pump air conditioner. The influences of the thermal conductance allocation ratio on system

COP

and the heating capacity

are investigated based on the model. Theoretical analysis results indicate that under the given conditions, there exist optimal thermal conductance allocation ratios corresponding to the maximum

COP

of the ASHPAC system. And the system

heating capacities always increase with the increasing thermal conductance allocation ratio. And then the effects of the main parameters on the determination of the optimal thermal conductance allocation ratio are discussed. When the total thermal 18

Page 18 of 25

conductance ranges from 0.5 to 0.8 kW K  1 , the optimal allocation ratios vary in the ranges of 0.37 - 0.40. In addition, the optimal allocation ratios increase from 0.32 to 0.38 and from 0.31 to 0.38 at the mass flow rate of the fluid heated ranging from 0.1 to 0.3 kg s -1 , and the mass flow rate of air in the evaporator ranging from 0.06 to 0.26 kg s  1 , respectively.

Moreover, the analysis results indicate that there exist the

optimal volumetric displacement ratios with respect to maximizing the system COPmax under the given conditions. When R22 is replaced by the R32 and R290 in the ASHPAC system, the optimal volumetric displacement ratios should be reduced in order to achieve the highest system COPmax . To sum up, the study provides some theoretical guidance for the optimization of ASHPAC system. Certainly, further experimental studies on optimizing the system should also be performed to offer useful validation for residential and commercial applications in the next step. References [1]. K. J. Chua, S. K. Chou, W. M. Yang. Advances in heat pump systems: A review, Appl. Energy 87 (2010) 3611-3624. [2]. W. Wang, Y. C. Feng, J. H. Zhu, L. T. Li, Q. C. Guo, W. P. Lu. Performances of air source heat pump system for a kind of mal-defrost phenomenon appearing in moderate climate conditions, Appl. Energy 112 (2013) 1138-1145. [3]. J. Heo, M. W. Jeong, C. Baek, Y. Kim. Comparison of the heating performance of air-source heat pumps using various types of refrigerant injection, Int. J. Refrig 34 (2011) 444-453. [4]. X. Xu, Y. Hwang, R. Radermacher. Refrigerant injection for heat pumping/air conditioning systems: Literature review and challenges discussions, Int. J. Refrig 34 (2011) 402-415. [5]. S. Xu, G.Y. Ma. Experimental study on two-stage compression refrigeration/heat 19

Page 19 of 25

pump system with dual-cylinder rolling piston compressor, Appl. Therm. Eng 62 (2014) 803-808. [6]. S. Jiang, S. Wang, X. Jin, T. F. Zhang. A general model for two-stage vapor compression heat pump systems, Int. J. Refrig 51 (2015) 88-102. [7]. H. W. Jung, H. Kang, W. J. Yoon, Yongchan Kim. Performance comparison between a single-stage and a cascade multi-functional heat pump for both air heating and hot water supply, Int. J. Refrig 36 (2 013) 1431-1441. [8]. H. Park, D. H. Kim, M. S. Kim. Performance investigation of a cascade heat pump water heating system with a quasi-steady state analysis, Energy 63(2013) 283-294. [9]. J. H. Wu, Z. G. Yang, Q. H. Wu, Y. J. Zhu. Transient behavior and dynamic performance of cascade heat pump water heater with thermal storage system, Appl. Energy 91(2012) 187-196. [10].

C. Nikolaidis, D. Probert. Exergy-method analysis of a two-stage

vapour-compression refrigeration-plants performance, Appl. Energy 60(1998) 241-256. [11].

E. Torrella, R. Llopis, R. Cabello. Experimental evaluation of the inter-stage

conditions of a two-stage refrigeration cycle using a compound compressor, Int. J. Refrig 32(2009) 307-315. [12].

L. Cecchinato, M. Chiarello, M. Corradi, E. Fornasieri, S. Minetto, P.

Stringari, C. Zilio.

Thermodynamic analysis of different two-stage transcritical

carbon dioxide cycles, Int. J. Refrig 32 (2009) 1058 - 1067. [13].

A. A. Safa, A. S. Fung, R. Kumar. Performance of two-stage variable

capacity air source heat pump: Field performance results and TRNSYS simulation, Energ Buildings 94 (2015) 80–90. 20

Page 20 of 25

[14].

N. Agrawal, S. Bhattacharyya, J. Sarkar. Optimization of two-stage

transcritical carbon dioxide heat pump cycles, Int. J. Therm. Sciences 46 (2007) 180-187. [15].

A. E. zgür , H. C. Bayrakc. Second law analysis of two-stage compression

transcritical CO2 heat pump cycle, Int. J. Energ. Res 32(2008)1202-1209. [16].

S. S. Bertsch, E. A. Groll. Two-stage air-source heat pump for residential

heating and cooling applications in northern U.S. climates, Int. J. Therm. Sciences 31 (2008) 1282 -1292. [17].

O. Kwon, D. Cha, C. Park. Performance evaluation of a two-stage

compression heat pump system for district heating using waste energy, Energy 57 (2013) 375-381. [18].

Q. C. Xing, W. W. Yang, F. Zhou, Y. L. He. Performance analysis of

different high-temperature heat pump systems for low-grade waste heat recovery, Appl. Therm. Eng 71 (2014) 291-300. [19].

A. Redón, E. Navarro-Peris , M. Pitarch, J. Gonzálvez-Macia, J. M. Corberán,

Analysis and optimization of subcritical two-stage vapor injection heat pump systems, Appl. Energy 124 (2014) 231-240. [20].

B. JAN, J. V. C. VARGAS, M. SOKOLOV. Optimal allocation of a

heat-exchanger inventory in heat driven refrigerators, Inter. J. Heat and Mass T. 38(1995) 2997-3004. [21].

S. S. Bertsch, E. A. Groll. Two-stage air-source heat pump for

residential heating and cooling applications in northern U.S. climates, Int. J. Refrig 31 (2008) 1282 -1292. [22].

S.A. Klein, Design consideration for refrigeration cycles, Int. J. Refrig.

15 (1992) 181–185. 21

Page 21 of 25

[23].

A. Bejan. Entropy generation minimization: the new thermodynamics of

finite-size devices and finite-time processes, J. Appl. Phys 79 (1996) 1191-1218. [24].

S. X. Xu, G. Y. Ma, Q. Liu, Z. L. Liu. Experiment study of an enhanced

vapor injection refrigeration/heat pump system using R32, Int. J. Therm. Sciences 68(2013)103-109. [25].

S. Mancin, D. D. Col, L. Rossetto. R32 partial condensation inside a brazed

plate heat exchanger, Int. J. Refrig 36(2013) 601-611. [26].

E. W. Lemmon, M. L. Huber, M. O. McLinden. 2007. NIST Thermodynamic

and Transport Properties of Refrigerants and Refrigerant Mixtures (REFPROP) Version 8.0. NIST. [27].

X. Jin, S. G. Wang, T. F. Zhang, F. Zu. Intermediate pressure of two-stage

compression system under different conditions based on compressor coupling model, Int. J. Refrig 35(2012) 827-840.

22

Page 22 of 25

Figure Captions Fig. 1 (a) Schematic diagram of air source heat pump system (b) p-h diagram of the cycle LC—low- pressure compressor HC—high- pressure compressor CON—condenser EVA —evaporator FL —flash tank HPT —high pressure throttle

LPT —low pressure throttle

Fig. 2 Flowchart of the calculation procedure Fig.3. The variations of the

and

COP

Fig.4. The variations of the 

opt

Qc

with  at different

and p m at different

UA

Fig.5. The variations of the t c , t e and t s ( p m ) at different Figs.6. The comparison of the

UA

for R32 UA

for R32

and t p with the 

COP

for R32

between the

one-stage and two-stage compression system for R32 Fig.7. The variations of the

COP

and

Qc

with  at different m fc for R32

Fig.8. The variations of the

COP

and

Qc

with  at different m ae for R32

Fig.9. The variations of the

C O Pm ax

and 

opt

with t aei at different t fci for R32

Fig.10. The variations of the

C O Pm ax

and p m with

r

for R32

Fig.11. The variations of the

C O Pm ax

and p m with

r

for R22

Fig.12. The variations of the

C O Pm ax

and p m with

r

for R290

23

Page 23 of 25

Tables Table1 The  opt , ro p t , C O Pm ax ,o , p m ,o and Q c,o at different UA for R32 -1 UA (KWK )

 opt

ro p t

C O Pm ax ,o

p m ,o (kPa)

0.6 0.7 0.8

0.37 0.39 0.41

1.69 1.63 1.59

3.10 3.33 3.53

931.35 940.39 949.68

Q c,o

(kW)

3.84 3.71 3.63

24

Page 24 of 25

Table 2 The  opt , ro p t , C O Pm ax, o , p m ,o and Q c,o for different refrigerant

Refrigerant

 opt

ro p t

C O Pm ax, o

p m ,o (kPa)

R32

0.39

1.63

3.33

940.39

3.71

R22

0.4

1.71

3.49

576.65

3.64

R290

0.41

1.63

3.57

551.01

3.61

Q c,o

(kW)

25

Page 25 of 25