Measurement 47 (2014) 919–928
Contents lists available at ScienceDirect
Measurement journal homepage: www.elsevier.com/locate/measurement
Stationary wavelet transform and single differentiator based decaying DC-offset filtering in post fault measurements A.A. Yusuff, A.A. Jimoh ⇑, J.L. Munda Department of Electrical Engineering, Faculty of Engineering and the Built Environment, Tshwane University of Technology, Private Bag X680, Staatsartillerie Road, Pretoria West, Pretoria 0001, South Africa
a r t i c l e
i n f o
Article history: Received 10 January 2013 Received in revised form 24 June 2013 Accepted 10 October 2013 Available online 23 October 2013 Keywords: Decaying DC offset Stationary wavelet transform Wavelets packet decomposition Phasor estimation
a b s t r a c t This paper presents a novel scheme for removing a decaying DC-offset from both current and voltage measurements irrespective of the time constant.The technique is based on stationary wavelet transform (SWT) cascaded with a differentiator. The performance of the scheme on two study cases is investigated; the statistical performance in relation to noise on a hypothetical signal, and a modeled segment of a utility network in South Africa. The proposed scheme is practically applied by testing it on a real life data obtained from Eskom’s network. The result shows that the scheme is robust, and that it can remove any DC-offset. The output of the scheme can be used for fault detection, classification and location. Crown Copyright Ó 2013 Published by Elsevier Ltd. All rights reserved.
1. Introduction In power system transmission line protection, most relays use the system frequency component in voltage and current to estimate appropriate phasors for impedance calculation, every other frequencies or harmonics are treated as noise. Although it is possible to remove all harmonics higher than the system frequency, by using various kind of low pass filters, however during faults, except in few cases the fault current will always have a decaying DC offset, which could be up to 20% of the steady state current value. Various digital filtering techniques are used in extracting the fundamental frequency component. Various approaches have been put forward to minimize the influence of the decaying DC component on phasor. In [1], a cosine filter was used in estimating both direct and quadrature components of a phasor. Digital mimic filtering schemes [2] has also been used extensively for the removal of a decaying DC offset. In this scheme, a preset value is chosen between 30 ms and 50 ms which is the range of EHV ⇑ Corresponding author. Tel.: +27 827870251; fax: +27 123824964. E-mail addresses:
[email protected] (A.A. Yusuff),
[email protected] (A.A. Jimoh),
[email protected] (J.L. Munda).
transmission line time constant, and the amplitude of the decaying DC offset is estimated. As long as there is no mismatch between the preset time constant and the actual time constant of the network, the scheme can totally remove the decaying DC offset. But in reality, since the time constant is dependent on the fault location and the network operating condition which are random variables, when the preset time constant is appreciably different from the network time constant, the error in the phasor estimate is appreciable. In [3], an adaptive mimic scheme was used to circumvent the deficiencies in using a pre-set time constant and the scheme produces a very accurate result irrespective of the time constant and the amplitude of the decaying DC offset. A few other techniques that have been used are Least Error Squares (LES) schemes [4,5], Kalman filtering techniques [6], as well as implementations in [7–13]. In recent times, time-scale and time–frequency signal decomposition techniques are used in the analysis and structural description of signals. The advances in computer hardware, software and mixed-domain signal transforms over the last decade has necessitated the need to rework the conventional approach to signals filtering and decomposition. These techniques expose Fourier transform
0263-2241/$ - see front matter Crown Copyright Ó 2013 Published by Elsevier Ltd. All rights reserved. http://dx.doi.org/10.1016/j.measurement.2013.10.022
920
A.A. Yusuff et al. / Measurement 47 (2014) 919–928
limitations, and point to techniques that are impossible using the Fourier tools. However, the computational burden of mixed domain signal filtering and decomposition is larger compared to its frequency domain counterparts. Unlike 4 decades ago, when computational power was a major problem in implementing algorithms, in the recent time computational power is now cheap, hence there might be a need to venture into untrodden path in filtering, provided we will get a better result in terms of time response albeit with more computational power. Hilbert–Huang Transform (HHT) based on Empirical Mode Decomposition (EMD) has been used to decompose non-stationary signals into a number of Intrinsic Mode Functions (IMFs), and subsequently Hilbert transform is used to calculate the instantaneous frequency and instantaneous amplitude of the IMFs [14–16]. However the major challenge of EMD is the inability to separate modes whose instantaneous frequencies simultaneously lie with an octave. In order to circumvent this deficiency, the use of masking was proposed in [17], while Olhede and Walden proposed a method based on wavelet packet decomposition to get the Hilbert spectrum on the narrow-band decomposition of the signal, with an appreciable performance compared to EMD based techniques [18,19].
Wavelets transform is a time scale technique that has been used extensively in multi resolution analysis of non-stationary signals. A typical example of its use in phasor amplitude estimation is given in [20–22]. However, this claims were debunked by Brahma and Kavasseri in [23]. They observed that the signal used in [20] is not realistic in power system, and that the assumptions of complete removal of decaying dc offset by a band pass anti aliasing filter in [22] or High pass 4th order Butterworth filter in [21] introduced unnecessary delays, without any appreciable performance justification. Stationary wavelet transform (SWT) was used in [24] for filtering and feature extraction of post fault measurements on power transmission lines. We propose the use of stationary wavelet transform (SWT) in cascade with a differentiator in removing decaying dc offset as well as other harmonics in both current and voltage measurements at the terminals of a transmission line. In this work we present a scheme for removing a decaying DC offset and estimation of the amplitude of the system fundamental frequency component that is applicable to both voltage and current. This could consequently be used in fault classification and estimating fault location. In Section 2, the theoretical background of the scheme was laid down. We look at the performance of our scheme for an hypothetical waveform with a decaying
Fig. 1. Stationary wavelet transform decomposition.
Fig. 2. The proposed scheme.
921
A.A. Yusuff et al. / Measurement 47 (2014) 919–928
dc offset as well as noise level varying from 20 dB to 80 dB, in Section 3. In Section 4, we show the application of our scheme, to a segment of a power utility network in South Africa (Eskom) by simulating a phase to ground fault. In addition, the performance of the scheme is checked on a real life data from a digital fault recorder (DFR). And conclusions are made in Section 5.
2. Stationary wavelet transform Stationary wavelet transform, unlike discrete wavelet transform (DWT) is time invariant caused by decimation [25]. It has been used in denoising, singularity detection [26], sharp transient detection [27] as well as HVDC line protection [28].
signal
det level 2
200
40
150
20 0 Amplitude
Amplitude
100 50 0
−40 −60
−50 −100 0
−20
−80 0.05
0.1
0.15 0.2 time
0.25
−100 0
0.3
0.05
0.1
300
100
200
50
100
0
−100
−100
−200
0.05
0.1
0.15 0.2 time
0.3
0.25
0.3
0.25
0.3
0
−50
−150 0
0.25
det level 4
150
Amplitude
Amplitude
det level 3
0.15 0.2 time
0.25
−300 0
0.3
0.05
0.1
app level 5
0.15 0.2 time
det level 5
600
400 300
500 200 100 Amplitude
Amplitude
400 300 200
0 −100 −200 −300
100 −400 0 0
0.05
0.1
0.15 0.2 time
0.25
0.3
−500 0
0.05
0.1
Fig. 3. Stationary wavelet transform decomposition.
0.15 0.2 time
922
A.A. Yusuff et al. / Measurement 47 (2014) 919–928
Table 1 Normalization constants Kc:fs is sampling frequency and di are detail coefficients at various levels. fs (kHz)
d1
d2
d3
d4
d5
d6
0.8 1.6 3.2 6.4 12.8 20.6
36.9411 73.5265 146.8759 293.6629 587.2815 945.1426
13.0922 26.0583 52.0538 104.0760 208.1364 334.9647
4.6737 9.3024 18.5823 37.1534 74.3012 119.5767
1.7178 3.4190 6.8298 13.6554 27.3088 43.9495
0.7115 1.4162 2.8290 5.6563 11.3117 18.2045
0.5031 1.0014 2.0004 3.9996 7.9986 12.8725
DC offset filtering using SWT based scheme for 20dB awgn
DC offset filtering using SWT based scheme for 40dB awgn
Amplitude estimate Orignal signal the proposed scheme output
5
Amplitude estimate Orignal signal the proposed scheme output
2
4 Amplitude (p.u)
Amplitude (p.u)
1.5 3 2 1 0
1 0.5 0 −0.5
−1
−1
−2
−1.5
−3 0
0.02
0.04
0.06
0.08
0.1 time (s)
0.12
0.14
0.16
0.18
0.2
0
DC offset filtering using SWT based scheme for 20dB awgn
0.5 0
−1
0.06
0.08
0.1 time (s)
0.12
0.14
0.16
0.18
0
−1 0.06
0.08
0.1 time (s)
0.12
0.14
0.16
0.18
0.08
0.1 0.12 time (s)
0.14
0.16
0.18
0.2
Amplitude estimate Orignal signal the proposed scheme output
0
−1 0.04
0.06
0.5
−0.5
0.02
0.2
1
−0.5
0
0.04
1.5 Amplitude (p.u)
Amplitude (p.u)
0.5
0.18
DC offset filtering using SWT based scheme for 40dB awgn
Amplitude estimate Orignal signal the proposed scheme output
1
0.16
Amplitude estimate Orignal signal the proposed scheme output
0.02
DC offset filtering using SWT based scheme for 20dB awgn 1.5
0.14
0
−1 0.04
0.1 0.12 time (s)
0.5
−0.5
0.02
0.08
1
−0.5
0
0.06
1.5
Amplitude (p.u)
Amplitude (p.u)
1
0.04
DC offset filtering using SWT based scheme for 40dB awgn
Amplitude estimate Orignal signal the proposed scheme output
1.5
0.02
0.02
0.04
0.06
0.08
Fig. 4. Levels 3–5 performance with respect to 20 dB and 40 dB SNR.
0.1 0.12 time (s)
0.14
0.16
0.18
0.2
923
A.A. Yusuff et al. / Measurement 47 (2014) 919–928 80
150
140
70
120
60
100
100
50
80
40 60
30
50
40
20
20
10 0
0
0.5
1
1.5
2
0 0.8
2.5
0.9
1
1.1
0
1.2
120
140
140
100
120
120
100
100
80
80
60
60
40
40
20
20
20
0
0
80
0.99
0.995
1
60 40
0.5
1
1.5
0 0.95
100
1
1.05
1.1
70
0.99
0.995
1
150
60
80
50 60
40
40
30
100
50
20 20
10
0 0.8
0.9
1
1.1
0 0.98 0.985 0.99 0.995 1
1.2
0
1.005 1.01
0.99
0.995
1
1.005
Fig. 5. Histogram of the amplitude estimates of the scheme.
Kendal
For any continuous time signal x(t), the discrete stationary wavelet coefficient at level i and sub-band k is [29]
Duvha L1
G1
G2 L2 Minerva
L3 Vulcan
wi;k ðtÞ ¼
Q i 1 X
fi;k ðqÞx½ðt qÞmod N
ð1Þ
q¼0
where {fi,k(q)} is the stationary wavelet packet filter at level i and sub-band k. Thus the component at level i and subband k, with the number of 2i 1 + k, is
di;k ðtÞ ¼
Q i 1 X
fi;k ðqÞwi;k ½ðt qÞmod N
ð2Þ
q¼0
Load1
Load2
Fig. 6. The simulated power system (Eskom subnetwork).
Stationary wavelet transform can decompose a signal into narrow-band components, which will meet singlecomponent signal analysis requirements like in phasor
924
A.A. Yusuff et al. / Measurement 47 (2014) 919–928
estimation. Fig. 1 shows the SWT decomposition tree and the up sampling of the filters.
4. Simulation and results In order to check the performance of the proposed scheme, we used two study cases as given below:
3. The proposed scheme
i Statistical performance analysis with dc offset and various noise levels. ii Simulation of a phase to ground fault in power system.
Consider a faulted phase current ip(t) that has a decaying DC offset component ie(t) and the sinusoidal components is(t) as given by (3)–(5)
ie ðtÞ ¼ Aet=s is ðtÞ ¼
ð3Þ
4.1. Statistical performance analysis
M X In cosðnxt þ /n Þ
ð4Þ Consider a hypothetical signal y(t) given by
n¼1
ip ðtÞ ¼ Aet=s þ
M X
In cosðnxt þ /n Þ
ð5Þ
yðtÞ ¼ Ie et=s þ IA cosðxt þ /n Þ þ
n¼2
n¼1
A is the magnitude of exponential decaying DC offset, s is the time constant of the decaying DC offset, In is the amplitude of the nth harmonics, /n is the phase angle of the nth harmonics, x is the electrical angular frequency. If we pre-process ip(t) in (5) with an anti-aliasing filter to band limit the signal, such that we have
if ðtÞ ¼ Ie et=s þ IA cosðxt þ /n Þ þ
Q X In cosðnxt þ /n Þ
ð6Þ
n¼2
The scheme shown in Fig. 2 can be used in totally removing a decaying dc offset and most of the high order harmonics. Consider t
if ðtÞ ¼ IA ½sinðxt þ h /Þ þ sinðh /Þes
ð7Þ
where h, / and s are phase angle, fault incidence angle and the decaying dc offset time constant respectively. Fig. 3 shows a 5 level stationary wavelet decomposition of a sinusoidal signal (7) with an amplitude IA = 100, s = 0.127 s, h = 12°, and / = 88.57°. Haar wavelet is used in the decomposition. It is easily observed from Fig. 3 that, the amplitude of detail coefficients at various levels greatly differ from the amplitude of the input signal which is 100, except for level 3 detail coefficients which gives a very close approximation. In addition the SWT decomposition has introduced a constant dc in the detail coefficients of levels 2, 4 and 5 as could be seen in Fig. 3b, d and f respectively. There is also a slight constant dc offset at level 3. It is apparent that the amplification factors for levels 2–5 are 0.4, 1, 2.5 and 3.5 respectively. Although, the detail coefficients at level 3 of SWT using Haar wavelet can completely filter a decaying dc offset and give a good representation of the original signal, however we will show later that level 3 does not have a good noise immunity when the signal to noise ratio (SNR) is 20 dB. In order to ensure that all amplitudes of the detail coefficients at various levels have a correlation with the amplitude of the input signal, a normalization constant Kc is introduced. Kc for various sampling rate and Haar wavelet based SWT levels is given in Table 1. This will ensure that the amplification factor is 1 irrespective of the level of the detail coefficients used.
Q X In cosðnxt þ /n Þ þ ðtÞ
ð8Þ y(t) can represent the current or voltage measurements from instrumentation devices in substations, in general they are not clean. The signals are perturbed by various noises in such an hostile environment. In order to check the effect of noise perturbations on the proposed scheme, an additive white Gaussian noise (t) of signal to noise ratio (SNR) between 20 dB and 80 dB is added to y(t) using the awgn function in MATLAB. The following signal parameters are used in the simulation: Ie = 1 p.u., IA = 1 p.u., the sampling frequency fs = 3.2 kHz. Fig. 4 illustrate the removal of decaying dc offset and various distortions in the amplitude estimates with a SNR of 20 dB and 40 dB. Although, the detail coefficients at level 3 is able to remove the decaying dc offset, however the sensitivity of the coefficient to noise is higher compared to the detail coefficients at level 5. Fig. 5 shows the histograms of amplitude estimates obtained from various SWT detail levels. Level 3 gives the worst estimate of the signal amplitude at 20 dB SNR. For
Table 2 Transmission lines parameter.
L1 L2 L3
Length (km)
R0 (X)
R1 (X)
X0 (X)
X1 (X)
84.74 96.23 39.18
32.50 35.98 15.27
1.91 1.44 0.88
92.82 104.11 43.01
27.32 26.76 12.48
Table 3 Generators parameter x00d ¼ x00q ¼ x0 ¼ x2 .
G1 G2
xd
xq
x0d
x0q
x0d
MVA
2.23 1.95
2.13 1.9
0.28 0.35
0.42 0.5
0.27 0.258
810 666
Table 4 Scheduled loads, at load buses.
Load1 Load2
Active (MW)
Reactive (MVar)
534.6 945.4
19.9 201.8
925
A.A. Yusuff et al. / Measurement 47 (2014) 919–928
a waveform having 1 as the amplitude, and a decaying dc offset, the amplitude estimate by using level 3 detail coefficients is between 0.4 and 2.5 for a noise level of 20 dB SNR, see Fig. 5a. However for the same noise level, the SWT detail level 5 gives amplitude estimate whose values lie between 0.9 and 1.1 as can be seen in Fig. 5g. If the noise level is around 40 dB SNR, we have amplitude estimates of 0.85–1.2, 0.95–1.05 and 0.985–1.01 for SWT detail levels 3–5 respectively. The practical implication of this is that the accuracy of the amplitude estimates
could be graded by using different detail levels. Using the level 3 detail coefficients gives the fastest result as could be seen in the phase difference between the original signal and the scheme output for various levels in Fig. 4b, d and f. 4.2. Simulated power system A segment of Eskom network simulated is shown in Fig. 6 to illustrate the performance of the scheme, the data used for simulation are given in Tables 2–4. The fault
Voltage amplitude estimation
Current dc−offset filtering
Amplitude estimate proposed scheme faulted voltage waveform
Amplitude estimate proposed scheme faulted current waveform
1
10
0.5
5
Amplitude (p.u)
Amplitude (p.u)
1.5
0
0
−0.5 −5
−1
1.9
1.92 1.94 time (s)
1.96
−10 1.88
1.98
1.9
Voltage amplitude estimation 2
1.92 1.94 time (s)
1.96
Current dc−offset filtering
Amplitude estimate proposed scheme faulted voltage waveform
Amplitude estimate proposed scheme faulted current waveform 10
1.5
1 Amplitude (p.u)
Amplitude (p.u)
5
0.5
0
−0.5
0
−5
−1 −10 1.88
1.9
1.92
1.94 time (s)
1.96
1.98
1.9
1.92
1.94 time (s)
Fig. 7. The proposed scheme with levels 2 and 3 on a LN fault at 53 km.
1.96
1.98
926
A.A. Yusuff et al. / Measurement 47 (2014) 919–928 Voltage amplitude estimation
Current dc−offset filtering
Amplitude estimate proposed scheme faulted voltage waveform
Amplitude estimate proposed scheme faulted current waveform
15
1 10
Amplitude (p.u)
Amplitude (p.u)
0.5
0
5
0
−5 −0.5 −10
−1 1.88
1.9
1.92
1.94 time (s)
1.96
1.98
−15 1.88
1.9
Voltage amplitude estimation 1.5
1.92
1.94 time (s)
1.96
1.98
Current dc−offset filtering 15
Amplitude estimate proposed scheme faulted voltage waveform
Amplitude estimate proposed scheme faulted current waveform
1 10
Amplitude (p.u)
Amplitude (p.u)
0.5
0
5
0
−0.5
−5 −1
1.9
1.92
1.94 time (s)
1.96
1.98
1.88
1.9
1.92 1.94 time (s)
1.96
1.98
Fig. 8. The proposed scheme with levels 4 and 5 on a LN fault at 53 km.
current at Kendal bus is first preprocessed through an antialiasing filter, a 2nd order Butterworth filter with cutoff frequency of 200 Hz was used for the anti-aliasing. The output of the anti-aliasing filter was then fed into the proposed scheme as shown in Fig. 2. The outputs of the scheme for a line to neutral fault on the simulated power system are shown in Figs. 7 and 8. Fig. 7a has the fastest response in terms of the time lag between the actual simulated measurements and the scheme output as could be seen in the current and the voltage plot. But this is at the expense of noise immunity and the over
shoot in the voltage amplitude estimates. The time lag is clearly evident SWT detail coefficients at level 5 in Fig. 8b, however there is no overshoot in the voltage amplitude estimate, and it seems to have a better noise immunity compared to the other levels. 4.3. A phase to ground fault current from digital fault recorder (DFR) in Eskom Eskom has DFRs installed on most of their transmission lines to record disturbances. These records are used for
927
A.A. Yusuff et al. / Measurement 47 (2014) 919–928 Record from a DFR
Record from a DFR 300
8000
200 Amplitude (A)
Amplitude (A)
6000 4000 2000 0 −2000
100 0 −100 −200 −300 −400
−4000
−500
−6000
−600 −700 0.54
−8000 0.4
0.5
0.6
0.7
0.8 time (s)
0.9
1
1.1
0.6
0.62 time (s)
0.64
0.66
0.68
10000 ia ib ic
swt ia swt ib swt ic ia ib ic
8000
6000
6000 Amplitude (A)
Amplitude (A)
0.58
Plot of fault voltage with fault location 53.5 km
Plot of fault current with fault location 53.5 km 8000
0.56
4000 2000 0
4000 2000 0
−2000
−2000
−4000
−4000 −6000
−6000
−8000
−8000 0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1
1.01
1.02
0.93
0.94
0.95
0.96
0.97
time (s)
0.98 time (s)
0.99
1
1.01
1.02
Fig. 9. The output of the proposed scheme in response to the DFR record.
post disturbance analysis of various relays operations. We tested the performance of the scheme on real life data recorded by one of the DFR for Duvha – Kendal 400 kV transmission line. The data is for a phase to ground fault on red phase at a fault location of 53.5 km from Duvha substation. The DFR record is first converted from a proprietary format to IEEE COMTRADE and ASCII format, which then are later imported into MATLAB workspace. as shown in Fig. 9a. The scanning frequency of the DFR is 2.5 kHz, which translate to a sampling frequency of 2.5 kHz for the measurement. The measurement is re sampled to give a sampling rate of 3.2 kHz using ‘‘resample’’ function in MATLAB. The reason for this is based on the fact that SWT needs a data length of 2Q, where Q is an integer. A sampling rate of 3.2 kHz give 64 samples per cycle. The expanded views of Fig. 9a before the fault and after the fault are given in Fig. 9b and c respectively. It is easily seen that the current measurement is corrupted by noise even before the fault and by a decaying DC offset after the fault. The output of the proposed scheme in response to the DFR record is shown in Fig. 9d. The proposed scheme is able to totally remove the decaying dc offset in addition to high frequency noise in the measurements. However, there is a phase shift between the original measurement and the output of the scheme.
5. Conclusion The paper presents a new scheme based on stationary wavelet transform for a complete removal of a decaying dc offset from fault current and voltage measurements irrespective of the time constant of the network. The scheme is able to achieve this at various accuracy depending on the level of SWT detail coefficients used. The delay is lowest when level 3 detail coefficients are used, however this comes at a cost of a poor noise immunity. Although, the delay in level 5 is appreciable compared to the others, level 5 offers a better noise immunity. Based on the three study cases investigated, the detail level used in filtering should be based on the SNR prevalent in the application context. The new scheme is robust and efficient even in the presence of noise level 20 dB. References [1] E.O. Schweitzer, D. Hou, Filtering for protective relays, in: Proceedings of the 19th Western Protective Relay Conference, Spokane, Washington, 1992. [2] Gabriel, Benmouyal, Removal of dc offset in current waveforms using digital mimic filtering, IEEE Transactions Power Delivery 10 (2) (1995) 621–630. [3] Chi, Shan, Yu, A discrete-fourier-transform based adaptive mimic phasor estimator for distance relaying applications, IEEE Transactions on Power Delivery 21 (4) (2006) 1836–1846.
928
A.A. Yusuff et al. / Measurement 47 (2014) 919–928
[4] M.S. Sachdev, M.A. Baribeau, A new algorithm for digital impedance relays, IEEE Transactions on Power Apparatus and Systems 98 (1979) 2232–2240. [5] M.S. Sachdev, M. Nagpal, A recursive least error squares algorithm for power system relaying and measurement application, IEEE Transactions on Power Delivery 6 (3) (1991) 1008–1015. [6] A.A. Girgis, R.G. Brown, Application of Kalman filtering in computer relaying, IEEE Transactions on Power Apparatus and Systems 100 (7) (1981) 3387–3397. [7] S.G. Srivani, K.P Vittal, On line fault detection and an adaptive algorithm to fast distance relaying, in: Joint International Conference on Power System Technology and IEEE Power India Conference, 2008, POWERCON 2008, New Delhi, 12–15 October 2008, pp. 1–7. [8] Kleber M. Silva, Washington L.A. Neves, Benemar A. Souza, Distance protection using a wavelet-based filtering algorithm, Electric Power Systems Research 80 (2010) 84–90. [9] Tarlochan S. Sidhu, Xudong Zhang, Vinayagam Balamourougan, A new half-cycle phasor estimation algorithm, IEEE Transactions on Power Delivery 20 (2) (2005) 1299–1305. [10] J.F. Minambres Arguelles, M.A. Zorrozua Arrieta, J. Lazaro Dominquez, B. Larrea Jaurrieta, M. Sanchez Benito, A new method for decaying dc offset removal for digital protective relays, Electric Power Systems Research 76 (2006) 194–199. [11] Dong-Gyu Lee, Ye-Jun Oh, Sang-Hee Kang, Byung M. Han, Distance relaying algorithm using a dft-based modified phasor estimation method, in: IEEE Bucharest Tech Conference, IEEE, Bucharest Romania, 2009, pp. 1–6. [12] Jorge Lazaro Domnguez, Jos Flix Minambres Argelles, Miguel Angel Zorrozua Arrieta, Begona Larrea Jaurrieta, Maribel Sanchez Benito, Zugazaga Inigo Antiza, New quick-convergence invariant digital filter for phasor estimation, Electric Power Systems Research 79 (2009) 705–713. [13] Ching-Shan Chen, Chih-Wen Liu, Joe-Air Jiang, Application of combined adaptive fourier filtering technique and fault detector to fast distance protection, IEEE Transactions on Power Delivery 21 (2006) 619–626. [14] N.E. Huang, Z. Shen, S.R. Long, S.R. Long, M.C. Wu, H.H. Shilh, Q. Zheng, N.C. Yen, C.C. Tung, H.H. Liu, The empirical mode decomposition and the hilbert spectrum for nonlinear and nonstationary time series analysis, Proceedings of the Royal Society of London, Series A 454 (1998) 903–995. [15] J.K. Wu, B.T. He, Y. Hu, D.S. Luo, Y. Liang, A novel method for removal of dc component in non-sinusoidal signals of power systems, in: IEEE PES, Power Systems Conference and Exposition, 2004.
[16] P. Flandrin, G. Rilling, P. Goncalves, Empirical mode decomposition as a filter bank, IEEE Signal Processing Letters 11 (2) (2004) 112–114. [17] R.R. Deering, J.K. Kaiser, The use of masking signals to improve empirical mode decomposition, IEEE International Conference on Acostics and Speach Signal Processing 4 (2005) 485–488. [18] S. Olhede, A.T. Walden, The hilbert spectrum via wavelet projections, Proceedings of the Royal Society of London, Series A 460 (2004) 955– 975. [19] S. Olhede, A.T. Walden, A generalized demodulation approach to time-frequency projections for multicomponent signals, Proceedings of the Royal Society of London, Series A 461 (2005) 2159–2179. [20] Chi kong Wong, Leng tak Leong, Chu san Lei, Jing tao Wu, Ying duo Ham, A novel algorithm for phasor calculation based on wavelet analysis, in: Proc IEEE Power Engineering Society Summer Meeting, vol. 3, 2001, pp. 1500–1503. [21] F. Liang, B. Jeyasurya, Transmission line distance protection using wavelet transform algorithm, IEEE Transactions on Power Delivery 19 (2) (2004) 545–553. [22] A.H. Osman, O.P. Malik, Transmission line distance protection based on wavelet transform, IEEE Transactions on Power Delivery 19 (2) (2004) 515–523. [23] S.M. Brahma, R.G. Kavasseri, Investigating the performance of discrete wavelet transform for phasor estimation in digital relays, in: Power and Energy Society General Meeting – Conversion and Delivery of Electrical Energy in the 21st Century, 2008, IEEE, 2008, pp. 1–6. [24] A.A. Yusuff, Ultra fast fault feature extraction and diagnosis in power transmission lines, PhD thesis, Department of ELectrical Engineering, Tshwane University of Technology, 2012. [25] S. Mallat, W.L. Wang, Singularity detection and processing, IEEE Transactions on Information Theory 38 (2) (1992) 617–643. [26] C.K. Jung, J. B Lee, X. H Wang, Y. H SOng, A study of the fault location algorithm on underground power system, IEEE Power Engineering society General Meeting 1 (2005) 763–769. [27] A.H. Osman, Transmission line protection technique based on wavelet transform, PhD thesis, Department of ELectrical and Computer science Engineering, the University of Calgary, 2003. [28] X. Liu, A.H. Osman, O.P. Malik, Stationary wavelet transform based hvdc line protection, in: 39th American Power Symposium, 2007. [29] Y. Hua, Liu, G. Z. Zhao, Power system fault detection based on stationary wavelet packet transform and hilbert transform, in: Congress on Image and Signal Processing, 2008, CISP ’08, Sanya, China, 2008, pp. 307–310.